OMD91046 rev D
44
5.2
OPTIONS PROVIDED ON REQUEST
1. THERMAL
COMPENSATION
PROBE FOR BATTERY VOLTAGE
2.
INSULATION TRANSFORMER ON BYPASS LINE
3.
SEPARATE INPUT KIT
4.
AUTO-TRANSFORMER FOR THE ADAPTATION OF INPUT VOLTAGE
5. ALARM
CARD
6. SERIAL
INTERFACE
RS-485 (ModBus protocol)
7. SNMP
ACCESSORY
8. REMOTE
PANEL
9. PARALLEL
KIT
10. BATTERY
CABINET
11. WALL MOUNTED ISOLATOR WITH BATTERY FUSES
12. SPECIAL
PAINTING
13. “LOAD-SYNC BUS” KIT
14. DIESEL
GENERATOR
15. AUXILIARY
CONTACT FOR EXTERNAL EPO
16. AUXILIARY
CONTACT FOR EXTERNAL MBCB
17. BACK FEED PROTECTION
5.2.1 Thermal compensation of battery charge
This option provides a temperature sensor to be installed near the battery room in
order to detect the operating temperature. This transducer is able to interface with the
control logic of the rectifier in order to modify its floating voltage based on temperature,
according to the typical curve supplied by the battery manufacturer. It is normally used
for sealed batteries, which are particularly temperature sensitive.
The temperature measured by the probe can be visualized on the front display. If it is
outside the limits set with the software, the UPS will activate an alarm.
Picture 30 – Charging voltage / temperature curve
The temperature sensor installed is provided with a connection cable that must be
connected to an interface card installed in the UPS’ terminal board section. The
temperature sensor can be installed at a maximum distance of 15 meters from the UPS.