4.4.3 Installation criteria
The UPS must be so installed as to ensure its serviceability and to allow a correct air
flow as much as possible.
The table below shows the air volume required for an optimal ventilation and cooling
of the UPS.
Power (kVA)
10
15 20 30 40 50 60
B8031FXS/ B8033FXS
B8033FXS
Air volume (m
3
/h)
500
600 800 900 1100 1100
4.4.4 Environmental installation conditions
The air is classified by the EN 60721-3-3 standard (Classification of environmental
parameters and their severities – Stationary use at weather-protected locations) based
on climatic and biological conditions as well as on mechanically and chemically active
substances.
Therefore the place of installation must meet specific requirements to ensure
compliance with the conditions for which the UPS was designed.
Climatic conditions according to the technical specification of B8000FXS
Environmental parameter
Minimum operating temperature (°C)
– 10
Maximum operating temperature (°C)
+ 40
Minimum relative humidity (%)
5
Maximum relative humidity (%)
95
Condensation
NO
Rainfall with wind (rain, snow, hail, etc.)
NO
Water with an origin other than rain
NO
Ice formation
NO
Classification of biological conditions (EN 60721-3-3)
Environmental
parameter
Classe
3B1 3B2
3B3
a) Flora
NO
Presence of mildew, fungus,
etc.
Presence of mildew, fungus,
etc.
b) Fauna
NO
Presence of rodents and
other animals that are
harmful to products,
excluding termites
Presence of rodents and
other animals that are
harmful to products, including
termites