7 Troubleshooting 

The error code will be displayed on the wired controller and the main board of the outdoor unit 
The meaning of each error, as shown in table 13. 

Table 12 

Name of malfunction 

The indicator display 

Yellow light  

Red light 

Green light 

Compressor runs 

Flash once 

Defrost 

Flash twice 

Anti-freezing protection 

Flash 3 times 

IPM    protection 

Flash 4 times 

AC over-current protection 

Flash 5 times 

Over-burden protection 

Flash 6 times 

Compressor exhaust high temperature protection 

Flash 7 times 

Compressor overload protection 

Flash 8 times 

Power protection 

Flash 9 times 

EEPROM reads and write protection 

Flash 11 times 

Low PN voltage protection 

Flash 12 times 

Over voltage protection for PN 

Flash 13 times 

PFC protection 

Flash 14 times 

PFC module temperature protection 

Flash 15 times 

Low pressure protection

 

Flash 17 times 

High pressure protection

 

Flash 18 times 

Limit/decline frequency(electric current) 

Flash 1 times 

Frequency limit

exhaust

 

Flash 2 times 

Frequency limit

Over-burden

 

Flash 3 times 

Outdoor ambient sensor malfunction 

Flash 6 times 

Outdoor tube sensor malfunction 

Flash 5 times 

Exhaust sensor malfunction 

Flash 7 times 

Attain the temperature of switch on 

Flash 8 times 

Frequency limit(power) 

Flash 13 times 

Outdoor fan malfunction 

Flash 14 times 

Frequency limit(PFC module temperature) 

Flash 15 times 

PFC module sensor malfunction 

Flash 16 times 

Liquid pipe temperature sensor malfunction of A 

Flash 17 times 

Gas pipe temperature sensor malfunction of A 

Flash 18 times 

Liquid pipe temperature sensor malfunction of B 

Flash 19 times 

Gas pipe temperature sensor malfunction of B 

Flash 20 times 

Liquid pipe temperature sensor malfunction of C 

Flash 21 times 

Gas pipe temperature sensor malfunction of C 

Flash 22 times 

Liquid pipe temperature sensor malfunction of D 

Flash 23 times 

Gas pipe temperature sensor malfunction of D 

Flash 24 times 

Liquid pipe temperature sensor malfunction of E 

Flash 25 times 

Gas pipe temperature sensor malfunction of E 

Flash 26 times 

Exit of the condenser tube sensor malfunction 

Flash 27 times 

Correspondence is normal 

Flash n times

n=indoor 

unit number

 

Communication  failure  between  indoor  unit  and 
outdoor unit 

Often bright 

indoor unit all 

Communication failure

 

Содержание Brisa MBRS42HPJ1OA

Страница 1: ...For proper operation please read and keep this manual for future reference If you have lost the Owner s Manual please contact the local agent or visit www borealintl com or send an email to borealsale...

Страница 2: ...e normal condition by harmonizing their running modes the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode If the supply power fails when the unit is...

Страница 3: ...n of such waste separately for special treatment is necessary Exception Clauses Manufacturerwillbearnoresponsibilitieswhenpersonalinjuryorpropertylossiscausedbythefollowingreasons 1 Damagetheproductdu...

Страница 4: ...3 3 Piping Connection 7 4 Installation Instruction 8 4 1 Outline and dimension of the outdoor unit 8 4 2 Installation of the Connection Pipe 9 4 3 Air Purging and Refrigerant Charge 11 4 4 Electric Wi...

Страница 5: ...pes 10 Never short circuit or cancel the pressure switch to prevent unit damage 11 Please firstly connect the wired controller before energization otherwise wired controller can not be used 12 Before...

Страница 6: ...eries 2 We are not responsible of personal injury or equipment damage caused by improper installation and commission unnecessary service and incapable of following the rules and instructions listed in...

Страница 7: ...roduct lineup is provided with capacity range from 30KBtu to 42KBtu which can be widely used in boarding house and working area and especially applicable to the place with variable load change Our com...

Страница 8: ...drive up to five indoor units which can be cassette type duct type wall mounted or floor ceiling type The outdoor unit will run as long as any one indoor unit receives the running command and all indo...

Страница 9: ...before outgoing 2 The parameters below are tested under rated working condition If there is any change to them please refer to the nameplate 3 The parameters of heating capacity of indoor unit for hea...

Страница 10: ...orrosive gas or exhaust gas 4 Leave some space for heat exchanging and servicing so as to guarantee unit normal operation 5 Keep the indoor and outdoor units close to each other as much units close to...

Страница 11: ...oor Unit and Outdoor Unit ft Liquid Gas 30K 1 4 3 8 229 6 When the outdoor unit is above maximum height difference between indoor and outdoor units is up to 49 2ft When the indoor unit is above maximu...

Страница 12: ...ee match series 8 4 Installation Instruction 4 1 Outline and dimension of the outdoor unit MBRS42HPJ1OA Outline dimension and Mounting holes Fig 5 40 42 1 2 24 5 6 17 1 3 14 1 4 15 3 4 43 3 7 Unit inc...

Страница 13: ...never pull any joints of the indoor unit by force otherwise the capillary pipe or other pipe may crack which then would result in leakage 2 The refrigerant pipe should be supported by brackets that i...

Страница 14: ...nd plastic tape in order to prevent condensation and water leakage 2 The joints of the indoor unit should be wrapped with the insulating material and no gap is allowed on the joint of the indoor unit...

Страница 15: ...rging 1 The refrigerant has been charged into the outdoor unit before shipment while additional refrigerant still need be charged into the refrigerant pipe during the field installation 2 Check if the...

Страница 16: ...ot pull the power cord by force 4 The electric installation should be carried out by the technician as instructed by the local laws regulations and also this manual 5 The diameter of the power cord sh...

Страница 17: ...nnect well according to the instruction 3 The electric installation should be carried out by the technician as instructed by the local laws regulations and also this manual 4 The installation location...

Страница 18: ...test It may cause insufficient cooling heating capacity Is the unit get proper thermal insulation It may causecondensation and dripping Does the unit drain well It may causecondensation and dripping I...

Страница 19: ...blown out again NOTICE If problem can not be solved after checking the above items please contact service center and show phenomena and models Following circumstance are not malfunction Table 11 Malfu...

Страница 20: ...hat of outdoor unit indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes Indoor unit stops to run and meanwhile change outdoor operating mode as the sam...

Страница 21: ...h 3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on Flash 8 times Freq...

Страница 22: ...remote wireless controller has been replaced 4 Check if the filter screen has been set soundly 5 After long period of shutdown open the main power switch 8 hours before re operating the unit so as to...

Страница 23: ...agency designated by us Warranty should meet the following requirements 1 First run of the unit should be operated by professional personnel from appointed service center 2 Only our manufactured acces...

Страница 24: ...Boreal International a Watsco Inc subsidiary borealsales borealintl com www borealintl com 10300 NW 19th St 105 Doral FL 33172 786 621 8250 66129935471...

Отзывы: