![bonitron M3534B Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/bonitron/m3534b/m3534b_customer-reference-manual_2787127034.webp)
M3534R 20A
34
6.2. W
ATT
L
OSS
S
TANDBY
M
ODE
Less than 15 watts for 20 A units
Approximately 3 watts for DP Series panels
B
OOST
M
ODE
All units are 95% efficient or better at full load.
6.3. F
USE
/C
IRCUIT
B
REAKER
S
IZING AND
R
ATING
6.3.1. R
ECOMMENDED
I
NPUT
P
OWER
W
IRING
S
IZES
A
ND
P
OWER
S
OURCE
F
USING
The following data is supplied for assistance in selecting the appropriate field
wiring sizes and power source fuse ratings for the model M3534R Cabinet
Mounted and Open-chassis Ride-Thru systems.
Wire size must be coordinated with circuit protection devices and IR drop
of wire. It is NOT necessary to size wire for continuous duty. Maximum
allowed duty cycle for the M3534R Ride-Thru is one 2-second run every
4 minutes.
Table 6-4: Input Power Wiring Sizes and Fusing
S
YSTEM
HP
S
YSTEM
K
W
R
IDE
-T
HRU
DC
B
US
C
URRENT
R
ATING
M
IN
.
S
OURCE
F
USING
S
EMICONDUCTOR
R
ECOMMENDED
F
IELD
W
IRING
S
IZES
MCM
E
QUIVALENT
W
IRING
S
IZES
13 - 16
10 - 12.5
20 Amps
30 Amps
14-10 AWG
4 MCM