User’s Manual
21
J
UMPER
J2
–
R
IDE
-T
HRU
A
CTIVE
S
TATUS
O
UTPUT
:
This jumper allows the user to select the output contact state of Ride-Thru
Active status relay K3. This jumper
must
be set to “Normally Open” (NO)
for cabinet systems.
Table 4-1: Control Signal Details- 3534R2 Control Board for Standard Models
B
OARD
D
ISABLE
T
EST
3534R2
Rating
6mA at 24V
3kV Isolation
8mA at 24V
3kV Isolation
Terminal
TB4-1(+) ,2(-)
TB3-5(+) ,6(-)
State
24V to disable
24V to test
Table 4-2: Control Board Control Signal Details for Modules with DP1
0 “I3” Option
B
OARD
D
ISABLE
3534I3
Rating
20mA at 24V
3kV Isolation
Terminal
TB4-6(+) ,5(-)
State
Jumper Selectable
Table 4-3: Status Signal Component Details- 3534R2 Control Board for Standard Models
B
OARD
F
AULT
/S
TATUS
C
OMPONENTS
F
AULT
/
S
TATUS
S
IGNAL
C
OMPONENT
ID
O
VER
T
EMP
(OT)
R
IDE
-T
HRU
A
CTIVE
(RTA)
3534R2
Jumper
J1
J2
Relay Contact
Ratings
1 Amp at 24VDC
.5 Amp at 115 VAC
1 Amp at 24VDC
.5 Amp at 115 VAC
Indicator
LD2
LD3
Control Board
Terminations
TB5-5,3
TB5-4,3
Isolation
1kV
1kV
Table 4-4: Status Signal Component Details
for Modules with DP10 “I3” Option
B
OARD
F
AULT
/S
TATUS
C
OMPONENTS
F
AULT
/
S
TATUS
S
IGNAL
C
OMPONENT
ID
R
IDE
-T
HRU
R
EADY
(RTR)
R
IDE
-T
HRU
A
CTIVE
(RTA)
3534I3
Jumper
J1
J2
Relay Contact
Ratings
120mA at 350VDC
120mA at 350VDC
Indicator
None
None
Interface Board
Terminations
TB4-3&4
TB4-1&2
Isolation
3kV
3kV