![bonitron M3534B Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/bonitron/m3534b/m3534b_customer-reference-manual_2787127015.webp)
User’s Manual
15
fuses. (See Figure 3-1.) Connections can be made using 10 AWG wire.
Torque terminal screws to 20 lb-in maximum.
G
ROUND
Earth ground stud is provided on the chassis for all models.
Make the Ground interconnection to Ground stud located on the lower left
inner wall of the RTM enclosure. Connection to the Ground terminal can be
made using 10 AWG wire. Terminal will accept a #10 ring or fork lug
termination. Torque nut on ground stud to 20 lb-in maximum.
3.4.1.1. S
OURCE
C
ONSIDERATIONS
Input feed must be capable of delivering 2x rated current for 2 seconds at
50% sag levels. Feeds sized to account for 150 - 200% inverter starting
torque are adequate.
NOTE: Drive and Ride-Thru will not pull power at the same time.
3.4.2. C
ONTROL
I
NTERFACE
W
IRING
3.4.2.1. T
EST
I
NPUT
C
ONNECTIONS
Test input connections may be made across
TB3-5
(+) and
TB3-6
(-) of
the ASB 3534R2 Control Board. Torque terminal screws to 2 lb-in max.
See Figures 3-2 and 4-2.
3.4.2.2. D
ISABLE
I
NPUT
C
ONNECTIONS
Disable input connections may be made across
TB4-1
(Positive) and
TB4-
2
(Negative) of the ASB 3534R2 Control Board. Torque terminal screws
to 2 lb-in max. See Figures 3-2 and 4-2.
For units utilizing the DP10 Option, connect at I3 TB4-6 (+) and 5 (-). See
Figure 4-3.
3.4.2.3. F
AULT
/
S
TATUS
M
ONITORING
C
ONNECTIONS FOR
S
TANDARD
M
ODELS
On the ASB 3534R2 Control Board:
OVERTEMP (OT) Relay
:
TB4-5-5
(OT) and
TB5-3
(Common). See
Figures 3-2 and 4-2.
Ride-Thru Active (RTA) Relay: TB5-4
(RTA) and
TB5-3
(Common).
Torque all connections to 2 lb-in max.
See Figures 3-2 and 4-2.
3.4.2.4. F
AULT
/
S
TATUS
M
ONITORING
C
ONNECTIONS FOR
M
ODELS WITH
DP10
(3534I3
B
OARD
)
On the ASB 3534I3 Interface Board:
Ride-Thru Active (RTA) Relay
:
TB4-1
(J2 post) and
TB4-2
(common).
See Figures 4-3, 6-2 and 6-3.
Over-Temp (OT) Relay
:
TB4-3
(J1 post) and
TB4-4
(common). See
Figure 4-3.
Torque all connections to 2 lb-in max.
Содержание M3534B
Страница 6: ...M3534R 20A 6 This page intentionally left blank ...
Страница 18: ...M3534R 20A 18 This page intentionally left blank ...
Страница 44: ...M3534R 20A 44 NOTES ...
Страница 45: ...User s Manual 45 ...
Страница 46: ...M3534R 20A 46 ...
Страница 47: ......