D_M3460_D_CMAN_vall_00a
4/17/2020
46
Table 6-5: M3460R Model Specifications for 230
– 480 VAC Systems
DC
B
US
C
URRENT
B
ACKPLATE
S
IZE
C
IRCUIT
C
ONFIGURATION
R
ECOMMENDED
F
USE
R
ATING
SCCR
R
ATINGS
D
RIVE
B
US
AC
L
INE
85 A
R10
2-stage
80 A, 700 V
125 A, 600 V
10 kA
127 A
R10
2-stage
125 A, 700 V
200 A, 600 V
170 A
R9
4-stage
175 A, 700 V
250 A, 600 V
255 A
R11
4-stage
250 A, 700 V
400 A, 600 V
340 A
R11
4-stage
350 A, 700 V
500 A, 600 V
18 kA
425 A
R11
4-stage
400 A, 700 V
600 A, 600 V
The input power source must be capable of handling a 2-second current surge at twice the nominal rating
for the M3460R. Maximum duty cycle is 1% at full rated load.
Fuses recommended for use with the M3460R are Gould-Shawmut A70QS series, Buss FWP series, or
equivalent semiconductor fuses. These are required for UL 508C compliance.
Suitable for use on a circuit capable of delivering not more than 10,000 RMS symmetrical amperes, 700
volts maximum when protected by recommended fuses.
Suitable for use on a circuit capable of delivering not more than 18,000 RMS symmetrical amperes, 700
volts maximum when protected by recommended fuses.
Table 6-6: M3460B Model Specifications for 230
– 480 VAC Systems
DC
B
US
C
URRENT
B
ACKPLATE
S
IZE
C
IRCUIT
C
ONFIGURATION
R
ECOMMENDED
F
USE
R
ATING
SCCR
R
ATINGS
D
RIVE
B
US
S
TORAGE
B
US
85 A
R10
1-stage
80 A, 700 V
125 A, 700 V
10 kA
127 A
R9
2-stage
125 A, 700 V
175 A, 700 V
170 A
R9
2-stage
175 A, 700 V
250 A, 700 V
255 A
R2
4-stage
250 A, 700 V
350 A, 700 V
340 A
R2
4-stage
350 A, 700 V
500 A, 700 V
18 kA
The input power source must be capable of handling 1.5 times the nominal current rating for the
M3460B
.
Maximum duty cycle is 1% at full rated load.
Fuses recommended for use with the M3460B are Gould-Shawmut A70QS series, Buss FWP series, or
equivalent semiconductor fuses. These are required for UL 508C compliance.
Suitable for use on a circuit capable of delivering not more than 10,000 RMS symmetrical amperes, 540
volts maximum when protected by recommended fuses.
Suitable for use on a circuit capable of delivering not more than 18,000 RMS symmetrical amperes, 540
volts maximum when protected by recommended fuses.
Содержание M3460
Страница 6: ...D_M3460_D_CMAN_vall_00a 4 17 2020 6 This page intentionally left blank ...
Страница 24: ...D_M3460_D_CMAN_vall_00a 4 17 2020 24 This page intentionally left blank ...
Страница 38: ...D_M3460_D_CMAN_vall_00a 4 17 2020 38 This page intentionally left blank ...
Страница 49: ...D_M3460_D_CMAN_vall_00a 4 17 2020 49 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Страница 50: ...D_M3460_D_CMAN_vall_00a 4 17 2020 50 Figure 6 3 M3460 E3 Enclosure Dimensional Outline ...
Страница 51: ...D_M3460_D_CMAN_vall_00a 4 17 2020 51 Figure 6 4 M3460 E4 Enclosure Dimensional Outline ...
Страница 52: ...D_M3460_D_CMAN_vall_00a 4 17 2020 52 Figure 6 5 M3460 E5 Enclosure Dimensional Outline ...
Страница 64: ...D_M3460_D_CMAN_vall_00a 4 17 2020 64 This page intentionally left blank ...
Страница 65: ...D_M3460_D_CMAN_vall_00a 4 17 2020 65 NOTES ...
Страница 66: ...D_M3460_D_CMAN_vall_00a 4 17 2020 66 This page intentionally left blank ...
Страница 67: ...D_M3460_D_CMAN_vall_00a 4 17 2020 67 This page intentionally left blank ...
Страница 68: ...D_M3460_D_CMAN_vall_00a 4 17 2020 ...