D_M3460_D_CMAN_vall_00a
4/17/2020
39
5.
S
TART
-
UP
,
M
AINTENANCE AND
T
ROUBLESHOOTING
5.1. M3460R
S
TART
-
UP
/
F
IELD
T
EST
P
ROCEDURE
1.
Ensure the M3460R has been properly installed and is disabled.
2.
Ensure the M3460R DC bus is disconnected from the drive DC bus.
3.
Ensure the drive is operating properly with the M3460R disconnected.
4.
Apply power to the input of the M3460R and observe the following conditions:
•
The display screen status indicates (Ride-Thru Disabled)
•
The display has Green LED on, that means the display is receiving power
from the Ride-Thru.
5.
Enable the M3460R with either the enable input or the digital display.
•
The display screen status indicates (Ride-Thru Standby)
•
No present fault on display.
6.
Initiate the test mode with the display panel.
•
The DC bus should rise for as long as the test is performed. A timeout may
occur when holding the test bottom longer than 2 seconds.
•
The display screen status indicates (Ride-Thru Testing)
7.
Turn off the power to the M3460R and watch the DC bus voltage fall.
•
The Ride-Thru Active light should turn ON when the M3460R starts to
operate.
•
The DC bus will hold at the DC bus threshold voltage setting momentarily
while the filter capacitors drain.
8.
With the M3460R and drive power off, connect the DC bus of the M3460R to
the DC bus of the drive.
9.
Turn on power to the drive and ensure it is working properly without any fault,
the drive must be ON before applying power to the Ride-Thru
. apply power
to M3460R and ensure proper function without any faults.
10.
Monitor the DC bus voltage and current with the display or with separate
meters. Also, monitor the AC input current to the attached drive.
11.
Load the drive as much as practical and put the M3460R into Test mode by
activating the Test input or using the display panel.
•
DC bus voltage should rise to the test boost level.
•
Motor should not lose speed or torque.
•
DC bus current should flow from M3460R to drive.
•
Drive input current should decrease.
The M3460R and drive system should now be ready to be put into service.
CAUTION!
•
I
F THE
M3460R
IS ACTIVE FOR LONGER THAN THE TIMEOUT SETTING
,
IT WILL
SHUT DOWN SWITCHING AND THE
DC
BUS WILL DROP TO THE NORMAL LEVEL
.
•
I
F THE OUTPUT
DC
BUS DROPS BELOW
70%
THE
M3460R
WILL HAVE TO GO
THROUGH PRE
-
CHARGE AGAIN
.
5.2.
Содержание M3460
Страница 6: ...D_M3460_D_CMAN_vall_00a 4 17 2020 6 This page intentionally left blank ...
Страница 24: ...D_M3460_D_CMAN_vall_00a 4 17 2020 24 This page intentionally left blank ...
Страница 38: ...D_M3460_D_CMAN_vall_00a 4 17 2020 38 This page intentionally left blank ...
Страница 49: ...D_M3460_D_CMAN_vall_00a 4 17 2020 49 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Страница 50: ...D_M3460_D_CMAN_vall_00a 4 17 2020 50 Figure 6 3 M3460 E3 Enclosure Dimensional Outline ...
Страница 51: ...D_M3460_D_CMAN_vall_00a 4 17 2020 51 Figure 6 4 M3460 E4 Enclosure Dimensional Outline ...
Страница 52: ...D_M3460_D_CMAN_vall_00a 4 17 2020 52 Figure 6 5 M3460 E5 Enclosure Dimensional Outline ...
Страница 64: ...D_M3460_D_CMAN_vall_00a 4 17 2020 64 This page intentionally left blank ...
Страница 65: ...D_M3460_D_CMAN_vall_00a 4 17 2020 65 NOTES ...
Страница 66: ...D_M3460_D_CMAN_vall_00a 4 17 2020 66 This page intentionally left blank ...
Страница 67: ...D_M3460_D_CMAN_vall_00a 4 17 2020 67 This page intentionally left blank ...
Страница 68: ...D_M3460_D_CMAN_vall_00a 4 17 2020 ...