Profibus DP V1 Agile
57
06/2010
Handling of the Objects
Example:
Actual Value
Parameter
DP-Master OUT
281
= C: 6 480 I: 0300 V: -005500 000F 2000 0000 0000 0000 0000
Meaning
C: 6
Request identification = 6 (Read parameter value Array)
C: 480
Parameter number = 480 (Fixed frequency 1)
I: 0300
Data set = 3
V: -005500
Parameter value = -5500 = -55.00 Hz (0xFFFEA84 hexadecimal)
000F
Release command (transition 4)
2000
Set point = 0x2000 = 50% of the reference value
0000
not used
0000
not used
0000
not used
0000
not used
Actual Value
Parameter
DP-Master IN
284
= C: 5 480 I: 03 00 V: -005500 06A7 2000 1147 0CCC 0800 0000
Meaning
C: 5
Reply identification = 5 (Transmit parameter value long Array)
C: 480
Parameter number = 480 (Fixed frequency 1)
I: 03 00
Data set = 3
V: -005500
Parameter value = -5500 = -55.00 Hz (0xFFFEA84 hexadecimal)
06A7
State = 0x27 "Operation enabled“ (Bit 0 ... 6),
Warning 2 present (Bit 15 = 1 threat of fault switch-off),
reference value reached (Bit 10 = 1),
remote operation (Bit 9 = 1),
Warning present (Bit 7 = 1)
2000
Actual value = 0x2000 = 50% of the reference value
1147
Abs. current = 0x1147 = 27% of the rated motor current
0CCC
Active current = 0x0CCC = 20% of the rated motor current
0800
Warning, Warning motor temperature available
0000
Fault, no fault pending
Parameter List
17 Parameter List
The parameter list is structured according to the menu branches of the Operator Panel. For better
clarity, the parameters have been marked with pictograms:
The parameter is available in the four data sets
The parameter value is set by the SET-UP routine
This parameter cannot be written when the frequency inverter is in operation
17.1
Actual Values
Actual Values of the Frequency Inverter
No.
Description
Units
Display Range
Chapter
228 Internal Reference Frequency
Hz
-1000,00 ... 1000,00
16.4.5
249 Active Data Set
-
1 ... 4
16.4.1
250 Digital Inputs
-
0 ... 255
16.4.4
260 Actual Error
-
0 ... 0xFFFF
18.2
270 Warnings
-
0 ... 0xFFFF
18.1
274 Application Warnings
-
0 ... 0xFFFF
18.2
281 DP-Master OUT
-
String
16.5
282 Reference bus frequency
Hz
-1000,00 ... 1000,00
16.4.5
283 Reference ramp frequency
Hz
-1000,00 ... 1000,00
16.4.5
284 DP-Master IN
-
String
16.5
365 Status Control
-
0 … 7
11
366 Status Fieldbus Module
-
1 … 15
11
411 Status Word
-
0 ... 0xFFFF
16.4.1
Note:
The Parameters
DP Master OUT
281 and
DP Master IN
284 can only be displayed via
the VPlus PC-Software.
The Parameters
Actual Error
270,
Warnings
270 and
Application Warnings
274 are
only accessible via the communication channel of objects PPO1, PPO2 and DP-V1. They
cannot be accessed via the VPlus PC-Software or the Operator Panel.