Profibus DP V1 Agile
06/2010
18
Status Parameters
11 Status Parameters
The Profibus module CM-PDPV1 has two actual value parameters which display the current status of
the module itself as well as that of the controlling software in the inverter.
Status Control
365 displays the software state of the controlling software in the inverter.
Status Fieldbus Module
366 displays the module state.
Status Control
365
Description
Wait_Process_PDP
Waiting for connection to Profibus master
Wait_Process2_PDP
Waiting for reconnection to Profibus master after
connection loss
Process_Active_PDP
Connection to Profibus master established, Data-
Exchange with Profibus master running
Status Fieldbus Module
366
Description
WAIT_PROCESS
Waiting for connection to Profibus master
PROCESS_ACTIVE
Connection to Profibus master established,
Data-Exchange with Profibus master running
These parameters can show other messages that are usually not of interest. These messages are of
interest for BONFIGLIOLI VECTRON support in the case of problems and trouble shooting.
12 Error Behavior
393 Profibus Error Reaction
In the event of Profibus errors (e.g. Profibus OFF), the behavior of the inverter can be set with
Profibus Error Reaction
393.
Parameter
Setting
No.
Description
Min.
Max.
Factory
Setting
393 Profibus Error Reaction
0
5
1
Operation Mode 393
Function
0 - No Reaction
Inverter remains in the current state.
1 - Error
Inverter enters the error state.
2 - Coast to Stop
Inverter power stages are switched off and drive stops in free run.
3 - Quick-Stop
The drive is decelerated with the quick stop ramps.
4 - Ramp-Stop + Error The drive is decelerated with the ramp. An error is generated after
reaching standstill.
5 - Quick-Stop + Error The drive is decelerated with the emergency stop ramp. An error is
generated after reaching standstill.
Note:
The operation modes “2 - Coast to Stop” and “3 - Quick Stop” are only available when
Local/Remote
412 is set to “1 - Control via Statemachine”.