background image

 AGL-STOV0-01SV0-05

06/12

 

 

 

 

CONTENT 

 

1

 

General information about the documentation ............................................................. 6

 

1.1

 

Instruction manuals .................................................................................... 6

 

1.2

 

Pictograms and signal words used ............................................................. 7

 

1.3

 

Copyright .................................................................................................... 7

 

2

 

General Safety Instructions and Information on Use .................................................... 8

 

2.1

 

General Information ................................................................................... 8

 

2.2

 

Designated use ........................................................................................... 8

 

2.3

 

Transport and Storage ................................................................................ 8

 

2.4

 

Handling and installation ............................................................................ 9

 

2.5

 

Electrical Installation .................................................................................. 9

 

2.6

 

Information on Use ................................................................................... 10

 

2.6.1

 

Operation with products from other manufacturers ............................................ 10

 

2.7

 

Maintenance and service .......................................................................... 10

 

2.8

 

Disposal ..................................................................................................... 10

 

3

 

Safety Instructions on Function „Safe Torque Off“ (STO) ........................................... 11

 

3.1

 

Approved Devices ..................................................................................... 12

 

3.1.1

 

Connection 3x AC 400/480 V ............................................................................ 12

 

3.1.2

 

Connection 1x AC 230 V / 3x AC 230 V ............................................................. 12

 

4

 

Information of Risk Analysis and Risk Assessment ..................................................... 13

 

5

 

General Description of Safety Function ....................................................................... 14

 

5.1

 

Integrated Safety Function ....................................................................... 14

 

5.2

 

Functional Safety ...................................................................................... 14

 

5.3

 

Classification the safety requirement ....................................................... 14

 

6

 

Description of ACTIVE Cube Safety Function ............................................................... 15

 

6.1

 

Definitions of the AGL Safety functions .................................................... 16

 

6.2

 

Specification of the Safety Function 1 (SF1): STO .................................... 17

 

6.3

 

Specification of the Safety Function 2 (SF2): SS1 .................................... 18

 

6.4

 

Description of Safety Function.................................................................. 19

 

6.5

 

Two-Channel Monitoring .......................................................................... 21

 

6.6

 

Diagnosis function and enforced dynamizing ........................................... 23

 

7

 

Requirements to be met by installation ....................................................................... 23

 

7.1

 

Instructions on installation of safety equipment ..................................... 23

 

7.2

 

External Safety Control Equipment .......................................................... 24

 

7.3

 

External DC 24 V power supply ................................................................ 24

 

7.3.1

 

External DC 24 V voltage supply for group stop ................................................. 25

 

7.4

 

DC 24 V power supply by AGL ................................................................... 25

 

8

 

Requirements to be met in operation .......................................................................... 25

 

Содержание Agile Series

Страница 1: ...Agile Application manual Functional Safety...

Страница 2: ......

Страница 3: ...ding to the customer specific requirements made on the frequency inverter Quick Start Guide The Quick Start Guide describes the basic steps required for mechanical and electrical installation of the f...

Страница 4: ...30 V 12 4 Information of Risk Analysis and Risk Assessment 13 5 General Description of Safety Function 14 5 1 Integrated Safety Function 14 5 2 Functional Safety 14 5 3 Classification the safety requi...

Страница 5: ...C with error exclusion short circuit in the cabinet 29 10 2 SS1 according to Stop Category 1 30 10 2 1 SS1 Direct Stop 30 10 2 2 SS1 Direct Stop with error exclusion short circuit in the cabinet 31 10...

Страница 6: ...ects connected with the use of the frequency inverter is described specific to the application If you need a copy of the documentation or additional information contact your local representative of BO...

Страница 7: ...n death serious injury or material damage Caution Caution refers to an indirect threat Non compliance may result in personal or material damage Attention Attention refers to a possible operational beh...

Страница 8: ...y inverters are electrical drive components intended for installation in industrial plants or machines Commissioning and start of operation is not allowed until it has been verified that the machine m...

Страница 9: ...nstallation from all possible sources of electrical power Secure against reconnection Only the persons working on the installation may re commission the relevant part of the installation Verify there...

Страница 10: ...be performed while the system is in operation 2 6 1 Operation with products from other manufacturers Please note that Bonfiglioli Vectron will not accept responsibility for compatibility with product...

Страница 11: ...of the frequency inverter Resetting of an emergency stop must not result in uncontrolled starting of the drive The drive is started again when the function STO is no longer triggered In order to compl...

Страница 12: ...requency inverter High voltage levels may be present at the motor Do not touch live terminals Permanent magnet synchronous motors PMSM must be operated only up to the synchronous speed PMSM cannot be...

Страница 13: ...que Off the risk assessment must con sider the fact that the motor will coast to a standstill in the case of an error Depend ing on the application a mechanical brake may be required Responsibility Th...

Страница 14: ...ent The integrated safety function Safe Torque Off of the AGL frequency inverter meets the following requirements according to EN 61800 5 2 up to safety integrity level SIL 2 according to DIN EN 61508...

Страница 15: ...llsetzen nach EN 60204 1 Stopp Kategorie 1 Definitions according to EN 60204 1 Stop category 0 Stop by immediate disconnection of energy supply to the machine drive elements i e uncontrolled stop Stop...

Страница 16: ...switches from above DC 15 V to less than DC 5 V Latest when falling below DC 5 V the response time begins and ends at the moment where torque can no longer be generated Fault Response time Time betwee...

Страница 17: ...Level EN ISO 13849 1 d Kategorie EN ISO 13849 1 3 Amount of Processs interfaces Two 2 Design of Processs interface Two yellow marked spring terminals X11 3 and X13 3 inputs STOA und STOB Type of Proce...

Страница 18: ...ce according to requirements of risk analysis Two yellow marked spring terminals X11 3 and X13 3 inputs STOA und STOB Type of Processs interface STO SPS Type 1 compatible according to IEC61131 2 Opera...

Страница 19: ...s The Safe Torque Off can be limited to certain plant areas in this way Another advan tage is the fact that it is not necessary to wait until the frequency inverter has been charged and discharged Thu...

Страница 20: ...Off Safe Torque Off can be achieved by Intentional triggering during operation in order to stop a drive and safely prevent restarting e g for maintenance work on a machine Triggering by actuation of...

Страница 21: ...rotection device is actuated the control voltages are interrupted the energy supply to the motor is switched off Disconnec tion is effected at a delay according to chapter 6 2 If the function STO is t...

Страница 22: ...e status changes to STO triggered and the output stage is inhibited In this state the monitoring function checks that during the next 5 seconds the second input is switched off If this has not been do...

Страница 23: ...installed in electrical cabinets with high IP protection e g IP 54 If external forces act on the drive axis e g in the case of vertical axes sus pended loads or round axes with asymmetrical weight di...

Страница 24: ...nsor signals that safety door is open is reset emergency stop unlocked safety door closed this alone shall not result in a restart of the drive Restart may only occur after the safety control device h...

Страница 25: ...safety function at regular intervals The test intervals are to be determined according to the risk analysis However the check should be performed once every year at the latest 9 Requirements to be me...

Страница 26: ...IL 2 When operating the emergency stop device with two stop channels both release paths paths STOA and STOB of the Agile frequency inverter are interrupted and the integrated safety function is trigge...

Страница 27: ...IEC 61508 SIL 2 Safety control equipment with one enable path and interconnection line is implemented instead of safety con trol equipment with two enable paths Comply with the following conditions S...

Страница 28: ...can start the drive profiles via commands If the protective device is actuated e g safety door open the release paths of the safety module are interrupted Through the interruption of the control volta...

Страница 29: ...d Category 3 or IEC 61508 SIL 2 Safety control equipment with one enable path and interconnection line is implemented instead of safety control equipment with two enable paths Comply with the followin...

Страница 30: ...avel command Clockwise is reset first After a delay tv the contacts on the safety switch interrupt the two enable paths STOA and STOB of the Agile frequency inverter and the integrated safety func tio...

Страница 31: ...LC and safety module Safety control equipment with one enable path and interconnection line is implemented instead of safety control equipment with two enable paths Comply with the following condition...

Страница 32: ...e g safety door open the release paths of the safety module are interrupted The PLC is triggered first that the safety function was actuated which then decele rates the motor by resetting the start co...

Страница 33: ...d Category 3 or IEC 61508 SIL 2 Safety control equipment with one enable path and interconnection line is implemented instead of safety control equipment with two enable paths Comply with the followin...

Страница 34: ...tacts on the safety switch interrupt the two enable paths STOA and STOB of the ACTIVE Cube frequency inverter and the integrated safety function is triggered by interrupting the inverter release The d...

Страница 35: ...d in a controlled way After a delay tv the controller enable signal of the frequency inverters is interrupted via the disconnection of the control voltages from STOA and STOB and the integrated safe p...

Страница 36: ...unction Installation EMC instructions in the operating instructions considered The DC 24 V supply was selected and installed based on the requirements of this manual The shield of the 24 V power suppl...

Страница 37: ...according to EN ISO 13849 1 and SIL 2 SILCL 2 according to EN 62061 IEC 61508 EN 61800 5 2 erf llt The requirements of the manual have to be complied with 12 1 Characteristical Data The following dat...

Страница 38: ...38 AGL STOV0 01SV0 05 06 12 14 Change index AGL STOV0 01SV0 05 First release in English language...

Страница 39: ...cy switch off 11 Enforced dynamizing 23 Fault exclusion 23 FMEA 14 Information on Use 10 Installation 9 Requirements 23 Instruction manuals 6 Machinery Directive 13 Norm EN 60204 1 23 EN 61800 5 2 23...

Страница 40: ...84 650 3577422 www bonfiglioli vn salesvn bonfiglioli com Bonfiglioli Australia 2 Cox Place Glendenning NSW 2761 Locked Bag 1000 Plumpton NSW 2761 Tel 61 2 8811 8000 Fax 61 2 9675 6605 www bonfigliol...

Страница 41: ......

Страница 42: ...aly tel 39 051 647 3111 fax 39 051 647 3126 bonfiglioli bonfiglioli com www bonfiglioli com Bonfiglioli has been designing and developing innovative and reliable power transmission and control solutio...

Отзывы: