AGL-STOV0-01SV0-05
06/12
6.3
Specification of the Safety Function 2 (SF2): SS1
Type of Safety function SF2
According to EN 61800-5-2:
Safe Stop 1,
SS1 c
Active Principle of SF2
•
Delay of motor with suitable braking ramp
•
Disconnection of energy supply to the
motor after elapsing of a safe time delay
Demand
rate
High
SIL-Level (IEC 61508)
2 with suitable safety switching device
Redundancy
On two channels (2)
Performance Level (EN ISO 13849-1) d with suitable safety switching device
Amount of Processs interfaces
•
External safety switching device according
to requirements of risk analysis
•
Two (2) on AGL
Design of Processs interface
•
External safety switching device according
to requirements of risk analysis
•
Two yellow marked spring terminals X11.3
and X13.3 (inputs STOA und STOB)
Type of Processs interface STO
SPS-Type 1 compatible according to
IEC61131-2
Operation modes with limited func-
tionality of SF 2
None
Response time SF2
•
External safety switching device: accord-
ing to data sheet of device
•
AGL: Less than or equal to 150 ms
Fault Reaction time DF2
•
External safety switching device: accord-
ing to data sheet of device
•
AGL: Less than or equal to 220 ms
The security function corresponds to a controlled stop to EN 60204-1, Stop
Category 1.
V Speed
axis
t Time
axis
t1
Time frame, when braking ramp is triggered (non safe path)
t2
Time frame, when STO is triggered
Δ
t
Time between activation of braking ramp and triggering STO
Are of maximum braking Time,
Set up on external safety control device.