9.3
Fault message
The error code saved after a fault in parameter
Last Error
310 facilitates
troubleshooting and error diagnosis. The error code consists of the error group FXX
and the code number XX. The error message is to be acknowledged via the keys of
the control unit and digital input S1IND.
Error messages
Code Meaning
F00
00 No fault has occurred.
Overload
02 Frequency inverter overloaded (60 s), check load behavior
F01
03 Short-term overload (1 s), check motor and application parameters
Heat sink
00 Heat sink temperature too high, check cooling and fan.
F02
01 Temperature sensor defective or ambient temperature too low.
Inside temperature
00 Inside temperature too high, check cooling and fan.
F03
01 Inside temperature too low, check electrical cabinet heating.
Motor connection
00
Motor temperature too high or sensor defective, check connection
S6IND.
F04
03 Phase failure, check motor and wiring.
Output current
00 Overloaded, check load situation and ramps.
03 Short circuit or earth fault, check motor and wiring.
05 Asymmetric motor current, check motor and wiring.
06 Motor phase current too high, check motor and wiring.
F05
07 Message from phase monitoring, check motor and wiring.
DC link voltage
00
DC link voltage too high, check deceleration ramps and connected
brake resistor
01 DC link voltage too low, check mains voltage.
02 Power failure, check mains voltage and circuit
03 Phase failure, check mains fuses and circuit.
04 Mains voltage UDC too high on switch-on, check voltage.
05 Mains voltage BC too high on switch-on, check voltage.
F07
06 Mains voltage MC too high on switch-on, check voltage.
Electronics voltage
01 Electronics voltage too low, check control terminals.
F08
04 Electronics voltage too high, check wiring of control terminals.
Output frequency
00 Output frequency too high, check control signals and settings.
F11
01 Max. frequency achieved by control, check deceleration ramps and
connected brake resistor.
Motor connection
00 Earth fault on output, check motor and wiring.
F13
10 Minimum current monitoring, check motor and wiring.
Control connection
01 Reference value signal on multifunctional input 1 faulty, check signal.
F14
07 Overcurrent on multifunctional input 1, check signal.