Rated Mech. Power
376 - enter the power (in kW) indicated on the type plate of the
asynchronous motor.
Setting:
0.1
⋅
P
FIN
... 10
⋅
P
FIN
Switching Frequency
400 - The rated operating point of the frequency inverter is
defined at a switching frequency of 2 kHz. Higher switching frequencies require a
reduction of the output current (see technical data).
Setting:
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
Min. Switching Frequency
401 – defines the minimum value the switching frequency
is reduced automatically in the case of a thermal overload of the frequency inverter.
Setting:
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
Minimum Frequency
418 - the start command entered via the control unit or digital
inputs S2IND, S3IND results in an acceleration of the drive to the minimum
frequency.
Setting:
0.00 Hz ... 999.99 Hz
Maximum Frequency
419 - The speed range of the drive is limited by the maximum
output frequency of the frequency inverter.
Setting:
0.00 Hz ... 999.99 Hz
Acceleration (Clockwise)
420,
Deceleration (Clockwise)
421 - the ramps define
how fast the output frequency is changed after a start, stop or brake command or
when the reference value is changed.
Setting:
0.00 Hz/s ... 9999.99 Hz/s ...
Operation Mode
452 (for multi-function input); the set point at input MFI1 can be
adjusted according to the connected signal source.
1 -
voltage signal, 0 V ... 10 V (factory setting)
2 -
current signal, 0 mA ... 20 mA
Setting:
3 -
digital fixed frequency change-over, 0 V ... 24 V, digital input
Fixed Frequency 1
480,
Fixed Frequency 2
481 - change-over between the two
fixed frequencies is effected via the fixed frequency change over function of the
multi-function input MFI1
Operation Mode
452 (multi-function input on setting 3). Via the data set change-
over S4IND, S5IND, the fixed frequency in one of the four data sets can be selected.
Up to 8 fixed frequencies can be parameterized and selected via the control of the
digital inputs.
Setting:
-999.99 Hz ... 999.99 Hz
Op. Mode Digital Output 1
530,
Op. Mode Digital Output 3
532 - various control
and monitoring functions can be assigned to the digital output S1OUT and the relay
output S3OUT.
0 -
switched off
2 -
run signal, drive turning/not turning message
3 -
fault message
11 -
Warning
41 -
trigger electro-mechanical brake
Setting:
1xx - inverted operation mode (LOW active)