12.5.24
0x6071/0 Target Torque
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6071
0
Target Torque
Integer16
rw
Rx
0
The value transmitted via Object 0x6071 is selectable as source 808 for various param-
eters (e.g.
FT Input buffer percentage
1381).
It is also available as operation mode 95 or inverted as 195 (e.g. for parameter
Refer-
ence Percentage Source
476 in configurations with torque control p.30 = x30).
A value of 0x3E8 (=1000) corresponds to rated motor torque (100.0 %).
By default, the object 0x6071 is not connected to a device function. To use the object
0x6071 at least one device function has to be linked to the object by parameterization.
The values of Object 0x6071 is limited to -3000 to 3000 (=-300.0…300.0 %).
Parameter
Setting
No.
Object
Min.
Max.
0x6071/0 Target Torque
-3000
(= 0xF448)
3000
(= 0x0BB8)
Hexadecimal value 0x6071
Decimal value 0x6071
Percentage of Target Torque
0x03E8
1000
100.0
0x0064
100
10.0
0x0001
1
0.1
0xFF18
-1000
-100.0
0xFF9C
-100
-10.0
0xFFFF
-1
-0.1
12.5.25
0x6077/0 Torque actual value
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6077
0
Torque actual value
Integer16
ro
Tx
Object 0x6077
Torque actual value displays the torque actual value (see parameter
Torque
224).
A value of 0x3E8 (=1000) corresponds to rated motor torque (100.0 %). Please refer
as well to Object
12.5.26
0x6078/0 Current actual value
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6078
0
Current actual value
Integer16
ro
Tx
Object 0x6078
Current actual value displays the current actual value (see parameter
R.m.s current
211).
A value of 0x3E8 (=1000) corresponds to the rated motor current (100.0 %). The rated
motor current is set during the commissioning in parameter
Rated Current
371.
90
CM-EtherCAT
07/13