12.4.4
0x3004/0 Boolean Mux
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x3004
0
Boolean Mux
Unsigned16
ro
Tx
Via object 0x3004 up to 16 Boolean values can be transferred from the ACU to a PLC
in a compressed manner. Each bit in 16 bit object 0x3004 displays the actual value of
the connected Boolean source.
Bit number 0 … 15 corresponds with index number 1 … 16!
The sources for the 16 bits can be chosen from a choice list via the index parameter
CANopen
®
Mux Input.
1422. Parameters 1420 and 1421 are the associated write
and read parameters which you have to set prior to writing/reading parameter 1422.
By using VTable this process is easier and more clearly laid out.
For writing and reading index parameters refer to chapter 12.3.2 “Handling of index
Default value is 7 – Off.