Status word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
Ready to switch on
1
Switched on
2
Operation enabled
3
Fault
4
Voltage enabled
5
Quick stop (Low active)
6
Switch on disabled
7
Warning
8
-
9
Remote
10
Target reached
11
Internal limit active
12
-
13
-
14
-
15
Warning 2
NOTE
The mode “Move away from limit switch” works under normal conditions with hard-
ware limit switches. For Software limit switches the mode only works if a Software
limit switch
Fault Reaction
1144 with reaction “error” is selected. If a setting with
warning (in example “10-Warning”) is selected, the software limit switch is not trig-
gering a fault and therefore the mode “Move away from limit switch” won’t move
away from the software limit switch.
NOTE
The mode “Move away from Limit Switch” must not be used after one of the follow-
ing error messages occurred:
•
F1444 Pos. SW Limit Switch < Neg. SW Limit Switch
•
F1445 Pos. and Neg. HW-Limit Switch Simultaneously
•
F1446 Limit Switch Incorrect Wired
If one of these faults has occurred, the wiring and parameterization must be
checked before the operation is continued.