5.0 Commissioning
BONAIRE
EAC
The water pump operates correctly when turned ON at the controller.
The Aquamiser cycle times and / or dialflow water bleed rate are set to suit local
water conditions.
Aquamiser drain valve is operating correctly and the tank drains correctly when unit
turns off.
The fan operates through the entire speed range.
Water distribution is even with the filter pads fitted and the air conditioner operating
pump and fan.
All Controller functions for the appliance operate
Ductwork and general
The Enviroseal functions correctly with the shutters opening downwards at 90°
All roof penetrations are fully sealed and watertight.
All ductwork is completed to plan, correctly supported and airtight, with no bend
tighter than 1.5 x the ductwork diameter.
Air distribution checked, dampers are adjusted and all outlets correctly adjusted and
wiped clean.
Man hole cover replaced.
Site
All rubbish has been removed from inside and on the roof.
Customer Hand Over
You have explained the following to the customer:
The operation of the Controller.
The need to open windows and doors for the correct operation of Evaporative Air
Conditioning
The operation of the bleed or dumping system and it’s importance to operate all the
time
Stick the Serial Number Label of the unit in the owners manual
Maintenance requirements