5.0 Commissioning
BONAIRE
EAC
•
Where a Bonaire Aquamiser is fitted and is set up for regular timed draining periods during
operation, the bleed may not need to be switched off. Check the water quality and if it is
below 300ppm Total Dissolved Solids (TDS), timed draining periods will be all that is
necessary to maintain TDS concentration levels. Over 300ppm TDS you may need a
combination of both bleed and drain. Please contact our technical support for more
information if needed. (www.bonaire.com.au)
•
Where a Bonaire Aquamiser is only used for the purpose of a dry sump when not in use, the
bleed rate will have to be set for the conditions of operation.
5.3.1 Setting the Draining Cycle Times (Dump Interval)
In the setting of Draining Cycle Times, Navigator Control
must be in the OFF mode. To set the Draining Cycle Time,
1. Press and hold the ENTER button for 3 seconds.
2. Press and release the “UP”, “DOWN”, and “SETUP”
buttons in sequence.
3. The word “InST”, “nSTA”, “STAL”, “TALL”, “ALLE”,
“LLER” (Installer) will scroll across the upper part of
the display. Press the ENTER button now to access.
4. When the CodE “11 11” appears input the code “98
76” using the UP/DOWN buttons and ENTER button
to move on to the next digit.
5. The display will flash the type of unit and address of
the unit. For example “EC 53” (EC- Evaporative
cooler, 53- Different number for every Unit) and “
1
1
1
1 1
11
1
”
parameter on the screen. Press the ENTER button to
go to the”1 1” parameter.
6. The display will flash the first number “1”. Move to
parameter “3” by pressing the UP/DOWN button then
press the ENTER button.
7. The display will flash the second number “1”. User
can set “0, 1, 2, 4, 8 or 12” hours by pressing
UP/DOWN button. The default dumping time is 4
hours.
8. Press ON/OFF button to finish.
The draining cycle times have now been set.