Installation Instructions
Page
23
5.0 Commissioning
BONAIRE
EAC
5.3.2 Setting the Drain Off delay time (Dump Delay)
DRAIN OFF Delay Time gives the option for immediate
draining of the water from the tank or a one hour delay after
the unit has been turned OFF. Setting the 1 hour delay is
preferable if the unit is going to be used in thermostat (AUTO)
mode. To set the 1 hour delay:
1. Press the ENTER button for 3 seconds.
2. Press the “UP”, “DOWN”, and “SETUP” buttons in
sequence.
3. The word “InST”, “nSTA”, “STAL”, “TALL”, “ALLE”,
“LLER” (Installer) will scroll across the upper part of
the display. Press the ENTER button now to access.
4. When the CodE “11 11” appears input the code “98
76” using the UP/DOWN buttons and ENTER button
to move on to the next digit.
5. The display will flash the type of unit and address of
the unit. For example “EC 53” (EC- Evaporative
cooler, 53- Different number for every Unit) and “1 1”
parameter on the screen. Press the ENTER button to
go to the “1 1” parameter.
6. The display will flash the first number “1”. Enter “1” by
pressing the UP/DOWN button and press the ENTER
button.
7. The display will flash the second number “1”. User
can set “0, 1” value by pressing the UP/DOWN
button. Set “0” for immediate draining of water from
the tank or “1” for 1 hour dump delay. (If an
Aquamiser is connected the user can set “0, 1, 2, 3,
4, 5” hours dependant on Hour setting parameter).
The default HOUR is 1 and default day is 1.
8. Press ON/OFF button to finish.
NOTE: It is the responsibility of the installer to set the
correct draining period to suit local water conditions.