Service & Maintenance
PROBLEM
PROBABLE CAUSE
SUGGESTED REMEDY
•
Pump motor failure.
•
Replace complete pump.
•
Loose electrical connections.
•
Tighten electrical connections.
Pump fails to
operate
•
Pump control switch faulty.
•
Replace pump control switch.
•
Insufficient water in pan.
•
Adjust float level.
•
Pump strainer blocked.
•
Clean strainer.
•
Blocked water in tubing.
•
Clean the tubing.
Pump runs but
does not
circulate water;
Pump runs but
pads lack water
•
Foreign matter lodge in the water
distribution piping.
•
Clean out foreign matter.
•
Fan rubbing on housing.
•
Re-position fan.
•
Fan out of balance due to dirt, etc.
•
Clean fan.
•
Air conditioner delivering more air
than needed.
•
Adjust ducting baffles to reduce airflow
or balance flow to outlets.
•
Belt ‘squealing’.
•
Tighten belt by adjusting motor. Apply
belt dressing to belt. In some cases it
may be necessary to replace belt.
Check the pulley alignment
Noisy air
conditioner
•
Inadequately sized ducts or grilles.
•
Increase size or add additional ducts or
grilles.
Continuous
overflow of
water
•
Float valve adjustment incorrect.
•
Adjust float valve.
•
Loose water tubing connections.
•
Tighten all connections.
•
•
Break in water tubing.
Too much water from the pump
•
•
Replace any cracked or broken tubing.
Adjust the dialflo outer knob to reduce
the flow of water to the filter pads.
Water into the
duct work
•
Air conditioner located near source
of unpleasant odour.
•
Remove source of odour or place a
barrier between air conditioner and
source of odour.
•
Algae in pan water.
•
Drain pan and clean thoroughly. Fill
with fresh water. Install new pads.
Unpleasant
odour
•
Pads remain wet after shut down.
•
Allow fan to run for about 10 minutes
after pump is shut off to dry out pads.
Rapid formation
of white
deposits
•
High mineral content of supply
water.
•
Increase the bleed rate. Fit a dump
valve and timer for cyclic dumping.
Page 26
Содержание 1200C
Страница 5: ...INSTALLATION OPERATION MAINTENANCE Unit Installation DUCT CONNECTION DETAILS B18 B23 36 ...
Страница 8: ...INSTALLATION OPERATION MAINTENANCE Water Connections WATER CONNECTIONS UNIT BASE LAYOUT B18 B23 ...
Страница 9: ...INSTALLATION OPERATION MAINTENANCE Water Connections B33 B36 ...
Страница 14: ...INSTALLATION OPERATION MAINTENANCE Electrical Connections Three Phase B36 Page 14 ...
Страница 15: ...INSTALLATION OPERATION MAINTENANCE Electrical Connections Variable Speed Single Phase B18 B23 Page 15 ...
Страница 28: ...Manufactured by Climate Technologies ABN 13 001 418 042 www climatetechnologies com au P N 1 M00 05 915 E ...