The  unit  monitors  the  total  operating  current  of  all  the  monitored  circuits.  If  the  total  operating 

current  has  exceeded  the  maximum  permitted  value  (6  Amperes)  the  unit  generates  an  Overcurrent 
message  and  shuts  off  one-by-one  the  outputs  with  the  maximum  operating  current.  As  soon  as  the 
total  current  doesn’t  exceed  the  maximum  permitted  value  the  unit  generates  a  Power  Restored 
message. 

1.2 3.

 

Power Inputs 

While operating, the unit monitors the voltage at its power inputs U

main

 and U

back

. When the power 

voltage has dropped at any input (if Both Power Inputs Monitoring is set on) or at both inputs (Both 
Power Inputs Monitoring is set off) down to 10 V and lower the unit sends a Power Failure message 
over the RS-485 interface. 

When the power voltage has been restored for both inputs (if Both Power Inputs Monitoring is set 

on)  or  for  any  input  (if  Both  Power  Inputs  Monitoring  is  set  off)  up  to  11 V  and  higher,  the  unit 
transmits a Power Restored message over the RS-485 interface. 

Power input conditions are indicated by READY LED as shown in the table below: 

Table 6. Indication of Operation Modes of the Unit 

Power Voltage 

Both Power Inputs 

Monitoring 

READY LED Performance 

1. OK for both inputs 

On 

Lit steady 

Off 

Lit steady 

2. Below the normal range for an input 

On 

On for 0.25 s and off for 1.75 s 

Off 

Lit steady 

3. Below the normal range for both inputs 

On 

On for 0.25 s and off for 1.75 s 

Off 

On for 0.25 s and off for 1.75 s 

The internal circuits of the unit and output circuits are supplied with power by a power input with a 

higher voltage. 

The values of the current consumed in various conditions are shown in the table below: 

Table 7. Consumed Current 

Conditions 

Power 

Voltage 

Max Consumed 

Current 

All outputs are switched off and OK. 
All inputs are in open circuit conditions. 

12 

35 mA 

24 

30 mA 

All outputs are switched off and in open circuit conditions.  
All inputs are in open circuit conditions. 

12 

40 mA 

24 

35 mA 

All outputs are switched off and in short circuit conditions. 
All inputs are in short circuit conditions. 

12 

45 mA 

24 

40 mA 

One output is switched on and in open circuit conditions, 
Other outputs are switched off and OK. 
All inputs are in short circuit conditions. 

12 

75 mA 

24 

55 mA 

All outputs are switched on and in open circuit conditions. 
All inputs are in short circuit conditions. 

12 

100 mA 

24 

75 mA 

 

2.2

 

Device Failed Mode 

The  unit  proceeds  to  the  Device  Failed  mode  when  a  fatal  error  has  occurred  on  calculating  the 

checksum of the program memory of the built-in microprocessor. 

In the Device Failed mode READY and COM LEDs flash alternately while other indicators change 

color from green to amber synchronously. 

Содержание S2000-KPB

Страница 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Страница 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Страница 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Страница 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Страница 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Страница 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Страница 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Страница 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Страница 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Страница 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Страница 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Страница 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Страница 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Страница 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Страница 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Страница 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...

Страница 17: ...17 6 OVERALL AND MOUNTING DIMENSIONS ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru Technical Support support bolid ru http bolid ru ...

Отзывы: