For the Periodic Load Shutdown monitoring type the minimum current for the output is 5mA. 

Once per 30 seconds the unit will shut the load down for 125 ms when it will be inspecting integrity of 
the line up to the termination element (the load connection module) of the monitored circuit. 

o

 

For  the  Current  Drop  Monitoring  type  the  unit,  switching  the  output  on,  accumulates  the 

average  value  of  the  current  in  the  monitored  circuit.  When  the  operating  current  drops  more  than  a 
quarter  of  the  average  value  an  open  circuit  failure  in  the  monitored  circuit  is  diagnosed.  Smooth 
changes of the operating current in the monitored circuit due to changes in the supply voltage are taken 
into account in the accumulated average value. 

The  monitoring types other than Normal are recommended to be used when several load devices 

are  connected  into  the  monitored  circuit,  for  example  for  several  light  and  sound  alarms  in  a  single 
monitored circuit. 

For example,  for normally  closed light alarm appliances the Periodic Load Shutdown  monitoring 

type is preferable. This type provides monitoring the circuit along the entire length to the termination 
element  (LCM)  provided  that  the  number  of  appliances  is  restricted  only  by  the  maximum  current 
value.  If  an  open  circuit  failure  has  happened  and  a  part  of  the  monitored  circuit  with  the  LCM  is 
isolated  then  the  unit,  switching  off  the  output once  again,  detects  the  open  circuit  and  generates  the 
relevant message. The connection diagram is shown in Figure 4. 

If  a  load  doesn’t  allow  short-time  shutting  down,  the  Programmable  Open-Circuit  Threshold  or 

Current  Drop  Monitoring  monitoring  types  is  suitable.  When  a  part  of  the  monitored  circuit  with 
several executive devices is isolated and as a consequence the operating current has dropped below a 
programmed threshold the unit generates an Open Circuit message. 

Current  Drop  Monitoring  is  recommended  to  be used  when  no  more  than  four  executive  devices 

with  the  same  current  consumption  are  connected  to  the  output  of  the  monitored  circuit.  Correct 
operation of this monitoring type with a larger number of executive devices is not guaranteed. 

When  a  short  or  open  failure  of  a  monitored  circuit  is  detected  the  unit  transmits  a  Loop  Short 

Circuit message or Loop Open Circuit message correspondently over the RS-485 interface. When the 
monitored circuit has returned to the Norm state, the unit sends the relevant recovery message over the 
RS-485 interface. 

Note:  If a short circuit failure has been detected while the output is activated then without regard 

to the circuit monitoring type the executing program will be aborted and will continue running in 10 s. 

States of the control outputs and the monitored circuits connected to them in Quiescent Mode are 

indicated by “1” to 6” LEDs in accordance with Table 4. 

Table 5. Indication of States of Outputs 

Circuit’s 

Condition 

Output’s 

Condition 

Indicator Performance 

Norm 

On 

Lit steady in green 

Off 

Off 

Open Failure 

On 

While lighting in green, double flashes in yellow once per two seconds 

Off 

Double flashes in amber once per two seconds 

Short Failure 

On 

Flashes in amber once per two seconds 

Off 

Содержание S2000-KPB

Страница 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Страница 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Страница 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Страница 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Страница 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Страница 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Страница 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Страница 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Страница 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Страница 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Страница 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Страница 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Страница 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Страница 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Страница 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Страница 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...

Страница 17: ...17 6 OVERALL AND MOUNTING DIMENSIONS ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru Technical Support support bolid ru http bolid ru ...

Отзывы: