16
5.3.7
Switch on the battery backed power supplies connected to the unit or connect power
circuits to the contacts “+U
main
” and “+U
back
”.
5.3.8
Ensure the unit is in Quiescent Mode as the indicator shows. READY LED shall be lit
steady, COM LED shall be lit steady or flash, indicators of outputs shall indicate the initial status of
their control programs (see Table 2), MASS and PRESS LEDs shall operate in accordance with the
programmed configuration of the alarm loops (see Table 1).
5.3.9
Generate a command or event to activate control programs for each executive output.
5.3.10
Ensure the executive devices connected to the unit respond (or light diodes of the
simulators turns on in accordance with the given programs).
5.3.11
Ensure that indicators “1” to “6” double operation of the control program for each output.
5.3.12
One-by-one simulate a short circuit failure of the circuit of the used output “1”, “2”, “3”,
“4”, “5”, “6” of the unit for which the unit’s configuration specifies the function of monitoring short
circuit failures.
5.3.13
Ensure that on closing the circuit the relevant output status indicator flashes in amber once
per two seconds.
5.3.14
Ensure that the control device (the network controller) displays the event of short circuit
failure for the relevant address.
5.3.15
One-by-one, simulate open circuit failures for the used outputs “1”, “2”, “3”, “4”, “5’, “6”
of the unit for which the unit’s configuration specifies the function of monitoring open circuit failures.
5.3.16
Ensure that on opening the circuit the status indicator of the relevant output double flashes
in amber once per two seconds.
5.3.17
Ensure that the control device (the network controller) displays the event of open circuit
failure for the relevant address.
5.3.18
One-by-one, connect to the “loop 1” and “loop 2” terminals the resistors nominal values of
which are defined in the configuration of the S2000-KPB.
5.3.19
Ensure that the control device (the network controller) displays the events which
correspond to each resistance value and MASS and PRES indicators operate as shown in Table 1.
5.3.20
Switch off the battery backed power supplies connected to the unit or disconnect the power
circuits from the contacts “+U
main
” and “+U
back
”.
5.3.21
Connect the circuits to the outputs of the S2000-KPB unit as specified by the design
documentation.
5.3.22
Switch on the battery backed power supplies connected to the unit or connect the power
circuits to the contacts «+U
main
» and «+U
back
».
5.3.23
Close the cover of the unit and seal if necessary.
5.3.24
Ensure the unit LEDs indicates the unit’s being in Quiescent Mode. READY LED shall be
lit steady, COM LED shall be lit steady or flash, indicators of outputs shall indicate the initial status of
the control program (Table 2), MASS and PRESS LEDs shall operate in accordance with the
programmed configuration of the alarm loops (Table 1).