background image

 

1

S2000-KPB 

EXECUTIVE UNIT

 

Version 3.02 

INSTRUCTION MANUAL 

1

 

TECHNICAL DESCRIPTION 

1.1

 

General 

1.2 1.

 

This Instruction Manual describes how to operate and maintain the S2000-KPB Executive 

Unit of version 3.02 (hereinafter referred to as the unit). 

1.2 2.

 

The  unit  is  designed  to  be  used  with  an  S2000M  panel,  an  S2000-ASPT  fire  alarm  and 

extinguishing  control  unit,  or  a  PC  as  a  component  of  modular  control  and  indicating  equipment  in 
such  system  as  a  fire / intrusion / panic  alarm  system,  a  voice  alarm  and  evacuation  system,  a  fire 
suppression system, an access control system, or a CCTV system. 

1.2 3.

 

The  unit  is  designed  to  control  executive  devices  (light  panels,  light  alarms,  sirens,  video 

cameras,  electromagnet  locks  etc.)  as  well  as  clean  agent  suppression  systems  and  fire-fighting 
equipment  in  gas,  dry  powder,  and  aerosol  fire-fighting  systems.  The  unit  controls  executive  devices 
by switching voltage from its power input terminals U

main

 and U

back

 to its output terminals. Connecting 

external power supplies to output terminals is prohibited and can damage the unit. 

1.2 4.

 

The  unit  is  designed  to  be  installed  on  a  vertical  surface  inside  the  protected  premises 

closely to the executive devices. The unit is designed for round-the-clock operation. 

1.2 5.

 

The  unit  must  not  be  used  in  aggressive  medium  or  dust  condition,  or  in  explosion-

hazardous premises. 

1.2 6.

 

As to the resistance to mechanical stress, the unit falls in the placement category 03 of 

ОСТ

 

25 1099-83. 

1.2 7.

 

As  to  immunity  to  climate  effects  of  environment,  the  unit  corresponds  to  version  03  in 

accordance with 

ОСТ

 25 1099-83 but for ambient temperatures from minus 30 to +55°

С

1.2

 

Specifications 

1.2 1.

 

Power Supply:  

An  external  dc  power  supply  with  power 
voltage  between  10.2  V  dc  and  28.4 V  dc 
(RIP-12, RIP-24) 

1.2 2.

 

Power Inputs: 

Two 

1.2 3.

 

Consumed Current 

(without executive devices): 

100 mA max 

1.2 4.

 

Outputs: 

Six 

 

Switching Voltage: 

10.2 dc  to  28.4 V dc  (from  the  power 
supply of the unit) ; 

 

Switching Current: 

5 mA 

÷

 2.5 A; 

 

Circuit Failure Monitoring Current: 

1.5 mA max 

1.2 5.

 

Max Total Switched Current of the Unit: 

6 A 

1.2 6.

 

Inputs: 

Two 

1.2 7.

 

Resistance of the loop wires 

without termination resistance:  

 

100 Ohm max 

1.2 8.

 

Leakage resistance between the loop wires 

or each wire and ground: 

At least 50 kOhm 

1.2 9.

 

Overall Dimensions: 

156 mm 

×

 107 mm 

×

 39 mm max 

1.2 10.

 

Weight: 

0.3 kg max 

Содержание S2000-KPB

Страница 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Страница 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Страница 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Страница 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Страница 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Страница 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Страница 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Страница 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Страница 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Страница 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Страница 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Страница 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Страница 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Страница 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Страница 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Страница 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...

Страница 17: ...17 6 OVERALL AND MOUNTING DIMENSIONS ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru Technical Support support bolid ru http bolid ru ...

Отзывы: