Bolero Manual 

Adjusting load sensitivity (cont.) 

3. 

Adjust the pot until the LED is steady green, now turn the pot back the opposite way until the LED flashes green.  

Allow 10 seconds in between adjustments for stabilisation. 

Clockwise = less sensitive, anti clockwise = increased sensitivity. 

Note: the trim pot is extremely sensitive.

 

When the LED flashes 

GREEN

, the unit is in standby mode. 

4. 

Turn on the smallest AC load in the home.  The unit should now deliver power, and the AC Status LED should be  

GREEN.  However, if the LED is ORANGE the sensitivity must be increased. 

5. 

Now turn OFF the AC load.  The LED should return to flashing GREEN, if this does not occur, reduce sensitivity. 

 

Troubleshooting 

AC Load does not stay ON 

Some AC loads may not be large enough to hold the inverter ON.  This condition may be recognised by the load turning off after 

every eight to ten seconds, then back on again.  AC Status LED will also be flashing orange.  

There are two possible solutions to this: 

a) 

Increase the sensitivity of the inverter by turning the Standby Pot slightly counter clockwise until the LED shows steady 

green;  

b) 

Increase the amount of AC load on the inverter. 

Inverter shuts down due to Over Temperature 

Your inverter will safely provide the output power as described in the technical data section in the conditions specified.  If your 

inverter shuts down and indicates over temperature, it may be that you have exceeded one of the parameters.  

Check for the following: 

• 

Ensure the inverter has adequate ventilation; insufficient ventilation can severely restrict the power output of your inverter. 

• 

Ensure the true power rating of your appliance (including power factor) does not exceed the rating of your inverter. 

Inverter shuts down when trying to start a load. 

When starting a load such as a motor it may cause the inverter to shut down.  If this is the case: 

a) 

ensure the battery voltage is within spec when the appliance is trying to start, if not, you may need to increase the size 

of your batteries. 

b) 

If battery voltage is OK then the inverter may be too small, consult your Solar Energy Australia representative. 

Screeching noise on radio when inverter is operating. 

Your Solar Energy Australia inverter is manufactured to the highest standards for the reduction of EMI (Electro Magnetic 

Interference). It is still possible however that in extreme cases, interference may be noticeable in radios or Television sets. Below 

are some suggestions to try to reduce this noise. 

 

Troubleshooting (cont.)

 

Содержание SEAP-12-800

Страница 1: ...ture and Adjustment Page 9 Adjusting Load Sensitivity Troubleshooting Page 10 How long will my battery last Page 11 Technical Data Page 12 Mounting Specifications Solar Energy Australia Pty Ltd ACN 08...

Страница 2: ...and or service please do not hesitate to contact us to discuss your thoughts Remember As soon as your Solar Energy Australia inverter has been installed please complete and return your warranty card...

Страница 3: ...are strictly adhered to Failure to do so will void your warranty Units which are to be permanently used within 1km of the coast should have the marine version of our product this will help to avoid co...

Страница 4: ...Ah Ampere Hours This is the amount of energy a battery can store In theory this means that a 200 Ah battery could supply 1 Amp for 200 hours Alternatively if an appliance draws 2 Amps for 4 hrs then...

Страница 5: ...solid surface capable of withstanding temperatures of 60 C Allow a cooling space of at least 200mm all around the inverter Placing the inverter in a cupboard or small enclosure may reduce the availabl...

Страница 6: ...y a short distance from the inverter in order to obtain best results but not closer than 500mm A battery fuse must be installed no closer than 500mm from the battery to protect all wiring connected to...

Страница 7: ...n specifications b Ensure the DC circuit breaker is set to the OFF down position c Plug in the AC connector but do not switch ON d Switch DC circuit breaker to the ON up position e If all is well the...

Страница 8: ...the internal temperature has been reduced to a safe level Load Sense Feature and Adjustment Your Bolero inverter features a Standby circuit for automatic load sensing which allows the inverter to rema...

Страница 9: ...the amount of AC load on the inverter Inverter shuts down due to Over Temperature Your inverter will safely provide the output power as described in the technical data section in the conditions speci...

Страница 10: ...xample a 16 inch TV 67 Watts running on 130AH battery Note Use a figure of 20 if your battery voltage is 24V DC Only 50 of the batteries capacity will be used to allow it to recover How can I tell if...

Страница 11: ...no load AC ON 38A 34A DC Current draw at full continuous load 81A 49A DC Current draw maximum 250 160A Efficiency 10 of load 92 91 Efficiency 50 of load 92 92 Efficiency 90 of load 87 88 Peak Efficie...

Страница 12: ...Solar Energy Australia Doc No SPN 1601A Rev0803 Page 12 Bolero Manual 243 mm 229mm...

Отзывы: