17
If the parameter for the closed door is active, the afore-
mentioned section is omitted and the doors remain closed.
In this case, the safety circuit can be opened manually
us-
ing an integrated switch (UCM Test, 2S300), which is
provided with the control system if ordered by the cus-
tomer.
The test is started by selecting the
directional key in the upward or
downward position.
The safety circuit for bypassing
the door lock switch is activated.
The elevator will now move with the maximum rated speed
or only by opening the brake.
A braking system tested in accordance with UCM engages
and brings the cabin to a stop.
The traveled distance is shown on the display.
Display of initial point prior to start of test:
After the test, the traveled distance can be read off using
the display.
If this distance is outside of the permissible range, the
zone area must be reduced accordingly, and the test be
repeated until a permissible distance is reached.
By acknowledging the "OK" button, the elevator moves
back to the initial position (after closing the doors).