BOGE Operating instructions trinity 

Page 7

General

1.4

Parameter change

Number of compressors 
and interval period 
‚Priority Change’

The control can be used as follows for 2 or 3 compressors. Independently of 
this, if the compressors are the same size, a cyclical (cycle time greater than 
0) or if the compressors are different, a time-dependent (cycle time to 0) prior-
ity time change can be carried out as follows:

1. Input 

Code 832

, as described in ‚Fundamental Procedures’ 

 In the dis-

play appears for example: 3 x 002 h, and the left number (here ‚3’) blinks.

2. Use 

arrow keys 

/

 to set the number of compressors to be consid-

ered, then use 

ENTER key

 

 to quit 

 now the right number blinks (here 

‚002’).

3. Use 

arrow keys 

/

 to set the priority change interval time to the de-

sired value and then use 

ENTER key

 

 to quit 

 the display changes 

according to the following criteria:

If the selected interval time is greater than zero, the display mentioned 
in 8.) appears ‚Pr Time to next priority change’

otherwise the text under 

‚Switching Times’

 appears and as soon as the 

switch time input is completed text under 

‚Time’

 appears.

Switching times

As soon as the cycle time has been set to ‚zero’, the control considers the 
switching times, which are input, as described, in the 26 timer channels A...Z.

1. Input 

code 798

, as described in ‚Fundamental Procedures’ – For example: 

A 0 00:00h = 123, appears in the display and the left letter (here ‚A’) blinks.

2. Use 

arrow keys 

/

 to select the desired switching channel (A...Z) and 

use 

ENTER key

 

 to enable its change 

 now the left number blinks 

(here ‚0’ means: this switching canal is not active).

3. Use 

arrow keys 

/

 to input the desired Switching -day -No. (1...7) and 

use 

ENTER key

 

 to change to Switching hour, set it and change to 

Switching minute and to priority sequence 

sequence 000 means ‚Output release will be removed for all compres-
sors from the set time’.

sequence 123 means: From the switching time onwards ‚Compressor 
No. 1 takes the base load, Compressor No. 2 the middle load and 
Compressor no. 3 the peak load.

sequence 312 means: From the switching time onwards ‚Compressor 
no. 3 takes the base load, Compressor no. 1 the middle load and Com-
pressor no. 2 the peak load.

4. Use 

ENTER key

 

 to assign the selected Priority sequence to this switch-

ing canal 

 the display of the next switching canal blinks (here ‚B’).

5. If all desired switching channels were parameterized the same way (and 

the letter of the next canal blinks) you can leave the setting area of the 
switching channel by holding down 

arrow key 

 and pressing 

ENTER 

key

 

. After first parameterization (by setting the interval time to zero), 

the display automatically changes to the area described in the section 
Time, otherwise the display described in 9.) appears ,Pr Day + 
Time’.

Содержание trinity

Страница 1: ...www boge com Operating instructions Control for several compressors trinity ...

Страница 2: ......

Страница 3: ... Operating instructions trinity BOGE KOMPRESSOREN Postfach 10 07 13 33507 Bielefeld Otto Boge Straße 1 7 33739 Bielefeld Phone 49 5206 601 0 Fax 49 5206 601 200 Mail info boge com Net www boge com Issue 01 2010 No 596 1031 01 Nominal price 5 00 ...

Страница 4: ......

Страница 5: ... Correct usage 2 Inadmissable usage 3 Transport damage 3 Customer service 3 1 3 Components Range of application 4 Hardware 4 Operating and control panel 4 Electrical connections 5 Software 5 1 4 Parameter change 6 Fundamental Procedures 6 Pressure range 6 Number of compressors and interval period Priority Change 7 Switching times 7 Time 8 Messages 8 Parameterization codes 8 1 5 Brief operating ins...

Страница 6: ......

Страница 7: ...ately shipped pressure transmitter of the trinity is installed directly to the central compressed air receiver of the compressed air network Should as an exception the pressure transmitter of the trinity be installed in the switch cabinet of the compressor like the compressor pressure transmit ter and not on the external receiver the following steps are to be observed If the compressor with the in...

Страница 8: ...nctions These instructions must be available to the operating staff at all times at the place the control unit and compressors are used The instructions must be read and followed by all persons who carry out the following work on the control unit operation including troubleshooting commissioning Correct usage The BOGE Multisystem control unit together with its options is solely designed for contro...

Страница 9: ...ll other complaints within six days of delivery Customer service The BOGE Customer Service is always pleased to help you in case you have any questions Please call Telephone 49 5206 601 0 Please always provide the following information about your control unit in order to prevent delays 1 Circuit diagram no 2 Order no 3 Machine no 4 Type 5 Year of manufacture 6 Software no Attention The following a...

Страница 10: ... cycle rest time when the mains fail Time operation capacitor for 10h Operating and control panel Single line 16 digit background luminous alphanumeric LC display 3 keys arrow keys and Return Enter The display unit comprises a graphic display and 3 indicator lamps LEDs for an additional illustration of the operating modes Fig 1 1 Operating and control panel trinity 1 LC Display alphanumeric 16 dig...

Страница 11: ... pressure values all compres sors first get output releases 4 For different compressor use week switching time mode can be parame terized set cyclic priority change time via Code 832 to 0 h 26 switch points A Z can be used All possible priority combinations including total output lock can be set 5 Integrated clock with operation reserve 10 h in case of power failure 6 Pressure display combined wit...

Страница 12: ...input the first place of code 4 Press ENTER key the second number of the three digit number flashes in the place of the first 5 Input the second place of the code via arrow keys 6 Press ENTER key the third number of the three digit number flashes in the place of the second 7 Use arrow keys to input the third place of the code 8 Press ENTER key corresponding to the selected code the param eter disp...

Страница 13: ...nnels A Z 1 Input code 798 as described in Fundamental Procedures For example A 0 00 00h 123 appears in the display and the left letter here A blinks 2 Use arrow keys to select the desired switching channel A Z and use ENTER key to enable its change now the left number blinks here 0 means this switching canal is not active 3 Use arrow keys to input the desired Switching day No 1 7 and use ENTER ke...

Страница 14: ...er this is an error message according to the following table By pressing the ENTER key when the specific message is displayed the message is acknowledged and the previous display reappears presupposed the reason responsible for the message has been eliminated Parameterization codes Num ber Meaning Remedy Others 16 Pressure transmitter is defective Replace pressure transmitter 25 Balance storage Re...

Страница 15: ...pressure value to the desired value use ENTER key quit now the right number blinks yy yy 9 Use arrow keys to bring the lower pressure to the desired value and then use ENTER key to quit now the display Pressure Target Val ues appears All other those in between pressure switch points are automatically calculated by the microprocessor Set number of compressors and interval period Priority Change 1 I...

Страница 16: ... Meaning Remedy Others 16 Pressure transmitter is defective Replace pressure transmitter 25 Balance storage Repeat software loading Replace control 32 Pressure transmitter line break Correctly connect pressure trans mitter 24 V to 1 Replace pressure transmitter or its plug Parameter type Code Remark Page Pressure target values 360 Highest lowest switching point 6 Number of compressors Interval tim...

Отзывы: