Bogart Engineering SC-2030 Скачать руководство пользователя страница 8

tank’s capacity does not vary over time. 

 

None of these analogies apply to batteries. Lead-acid batteries can accept higher charge currents when they are nearly empty, 

but must be charged more slowly when they are nearly full because then they will not readily accept the charge. Batteries need 
to be frequently fully charged. If a battery is allowed to operate consistently at a low charge level, its capacity to hold charge 
decreases over time. This means that a battery needs to be fully charged every now and then for the proper maintenance of its 
capacity. In solar applications, this sometimes cannot be achieved in the course of a single day, depending on sunshine and 
energy usage.

 

Sometimes a generator is used instead of sunlight to charge the battery at a high current for one or two hours each day. This can 
easily shorten the life of lead-acid batteries, which cannot get fully charged in two hours even with a very powerful generator. If 
only charged with very high currents over a short time, a battery’s charge capacity will decline over time. A “hybrid” generator-
solar system would be preferable with a strategy of using the generator to provide a fast charge early in the morning, when the 
battery is at its lowest charge level, and stop when the battery can no longer accept high charging currents. By the time the sun 
is high enough, the solar panel can take over the charging at a lower current for the following six to nine hours. Alternatively, a 
surplus of solar panels can accomplish something similar, but that means the peak solar power in the afternoon, when batteries 
are accepting  less current, may not be used. To overcome this, plan to use heavier loads, such as laundry, dish washing or well 
pumping, during the mid afternoon, when batteries accept less solar energy. 

6.2 Specifically how solar chargers, including the SC-2030 charge batteries 

The following charging description applies when the SC-2030 Solar charger is connected with the TM-2030. If for some reason 

the TM-2030 is not connected, it uses a basic charging procedure, to be described in section 6.3.  

This discussion refers to 12V systems—for 24V systems multiply voltages by two.  

To charge batteries, a charger supplies electrical energy to the battery with a certain "voltage." "Volts" is a measure of how hard 

the charger is attempting to push the energy (electrons) into the battery. The battery always tends to resist the tendency to push 

the electrons in—the voltage of the charger must be high enough to overcome the resisting force of the battery.  This is a little 

like pushing water into a pipe which is under pressure—enough force must be provided to push it in or it will not go.  The 

"current" or "amperes" is a measure of how much (charge) energy is actually flowing in.  The actual flow (“amps” or amperes) 

depends on two factors: how hard the charger is pushing (voltage) and how much the battery is resisting.   

When batteries are at a lower state of charge they do not push back very hard, and the battery will easily absorb all the charge 

(amperes) that the charger can supply.  This is called the "bulk" stage of charging, and the "voltage" from the charger during 

charging will be below 14 volts or so.  This is when most of the charge can go into the battery, and is the simplest part of the 

charging process; usually the batteries will be able to absorb all the energy the charger is capable of delivering.  

When the batteries reach about 85% full, the job of the charger gets more difficult. The batteries begin to resist more, and 

absorb amps at a lower rate, meaning that it takes a longer time to do the rest of the charging.  One might say, "why bother, then 

to go beyond 85% full?  Wouldn't this make the job easy on the charger?  Just always operate the batteries from 55%-85% 

charged."  Well, yes it would, but the reason this is not a satisfactory strategy for lead acid batteries is that if you don't fully 

charge them regularly, it makes it harder in the future to charge them as much.  It is remarkable how often even authoritative 

sources on lead acid battery charging repeat the phrase that "lead acid batteries do not have memory."     Lead acid batteries DO 

have a memory—if you do not fully charge them, they will remember that, and if this is repeated often their capacity will 

gradually "walk down" as is correctly described in charging information from the Concorde battery company. 

This presents a challenge to solar charging— because the solar day starts to end as the batteries become more resistant.  This 

can result in a battery that is not fully charged when the day ends. It is frequently observed that batteries being charged only by 

solar tend to lose capacity to hold energy— described as batteries becoming “sulfated”.  This conveys the fact that the lead 

sulfate, which is the byproduct of discharging gets more difficult to convert back to fully charged lead  and sulfuric acid if it sits 

Содержание SC-2030

Страница 1: ...to better preserve the capacity of your battery system 1 Amp hour counting Many battery companies recommend that when batteries are recharged they should be overcharged so that 104 to 120 percent of the charge that was previously removed should be replaced before going into float Most controllers don t measure this When connected with the TriMetric this controller measures the amp hours used and a...

Страница 2: ...r full efficiency May be safely used with panels up to 45A however charging current will be reduced to protect charger MINIMUM in out power efficiency at 30A 97 5 12V systems 98 5 24 V systems MINIMUM in out power efficiency at 15A 99 Battery capacity 10 to 10 000 amp hours Terminal block wire gauge Up to 6 AWG Larger stranded cables you can remove some strands to fit Charging profiles Three stage...

Страница 3: ...GM or liquid electrolyte These determine the charging only when the TM 2030 is not connected otherwise they are ignored In this case there is an absorb stage set to 14 6 or 29 2 volts for 12 or 24V liquid electrolyte systems or 14 3 or 28 6 for AGM systems which runs for two hours followed by a float stage of 13 2 or 26 4 volts 4 1 3 Temperature Compensation The optional temperature sensor is reco...

Страница 4: ...s Check volts For accurate battery voltage control the TriMetric s voltage measurement wire called B1 in TriMetric wiring diagram must be connected directly or close to the battery s positive terminal Check amps on the AMPS TriMetric display Under zero current conditions when all loads and charging sources are off the TriMetric s ampere indicator must show 0 0A or 0 1A at most when using the stand...

Страница 5: ...tool and correct RJ14 connector to avoid drilling a larger hole you could pass wire through a small drilled hole through TM 2030 enclosure then use crimp tool to install connector carefully observing polarity Fig 1 Don t yet connect the communication cable to the TM 2030 unless connectors at each end are attached and you don t intend to put them on or change them later 4 4 3 Remove front panel and...

Страница 6: ...t the absorb voltage Flashing 3 times indicates floating mode Flashing 4 times in higher voltage finish limited current charging With TM 2030 connected only Flashing 5 times at maximum voltage finish limited current charging With TM 2030 connected only Flashing 6 times Was in float now discharging but still at least 98 full With TM 2030 connected only Flashing zero times Discharging and less than ...

Страница 7: ...t shown on the front panel called UPr Unused power which displays this If most of the solar power is now surplus because the batteries are getting well charged YES will show on the display If a lesser amount the display will indicate the approximate number of watts that are being wasted Refer to the Quick Reference Guide section 2 1 Also listed there is information about observing solar amps SOL a...

Страница 8: ...energy electrons into the battery The battery always tends to resist the tendency to push the electrons in the voltage of the charger must be high enough to overcome the resisting force of the battery This is a little like pushing water into a pipe which is under pressure enough force must be provided to push it in or it will not go The current or amperes is a measure of how much charge energy is ...

Страница 9: ...e variations on this method 1 Charge above the gassing voltage until the amperes drop to a sufficiently low value say an ampere value that is 1 or 0 5 of the amp hour capacity of the batteries 2 Charge until the value of amps into the batteries stops decreasing for a specified period of time and stays at this constant value for perhaps a couple of hours 3 Charge until the charger has replaced a sp...

Страница 10: ...r current until it reaches the limiting absorb voltage shown After that it charges for an absorb time of two hours Then it regulates at the float voltage shown 6 4 Two Graphs of charging profiles for SC 2030 when TM 2030 is connected The first profile figure 2 is more typical of most good solar chargers However the SC 2030 has an additional unusual option of setting a percentage of overcharge valu...

Страница 11: ...rops below P2 P3 AND overcharge P20 OR Timer expires with P14 time For the 4 state profile Timer starts counting with P14 time as shown on 4 state charging profile The first time after the charger is turned on Goes into float when Amps drops below P2 P3 OR Timer expires After the first time Amps drops below P2 P3 at least once during Absorb AND overcharge P20 OR Timer expires with P14 time 6 6 Bat...

Страница 12: ...r repaired at Bogart Engineering s discretion provided it has not been subjected to abuse or misapplication For warranty service please email bogart bogartengineering com A return merchandise authorization is required for all merchandise to be returned to Bogart Engineering How to obtain customer service Please review our support page before attempting to contact us Our distributors are able to an...

Страница 13: ...es compared to the most recent discharge before going into float Also it has been considered best suited for AGM or Gel type lead acid batteries however recently some manufacturers are recommending the four stage profile next page for AGM type batteries Liquid electrolyte batteries can usually benefit from four state solar charging Figure3 To select three stage charge control set program P21 finis...

Страница 14: ...Max over voltage time allowed 0 1 10 0 hours Absorb stage terminates when Charged setpoint amps When P21 not OFF Max finish volts P15 value When P21 is OFF Max finish volts P1 value 4 state charging profile for liquid electrolyte batteries Figure 3 Bulk Absorb Finish Absorb Float Time counting P14 starts here when P21 is not off Starts here when P21 is off Time counting temporarily stops whenever ...

Страница 15: ...tery systems Up to 30 amps of panels can be used If more than 30 amps is used the SC 2030 will safely limit current 1 A FUSE Optional battery temperature sensor Small wires go to connector in SC 2030 SHUNT Choose 500A 50 mV or 100A 100mV TWO KELVIN SCREWS 4 small wires from battery to meter up to 100 feet Usually a cable with four 22 or 24 wires is used Optional connection for measuring voltage on...

Страница 16: ...les previously connected to the battery negative pole must then be reconnected to the load side of the shunt Connect four wires from shunt and battery to Meter Cable consisting of small wires 22 up to 100 feet long need to connect from the TriMetric to the shunt and batteries WHAT S INVOLVED IN INSTALLING THE BOGART ENGINEERING SC 2030 Solar Charger Brief description Complete description is in the...

Отзывы: