Bogart Engineering SC-2030 Скачать руководство пользователя страница 7

5. Useful Information for everyday users 

See also the Trimetric Installation guide and TriMetric Technical Manual for more information 

5.2 A useful display item for seeing if your batteries are being properly charged 

If you partially drain your batteries on a daily basis, we suggest understanding the new display function on the TM-2030 called 
"

Replaced Percentage from Last Discharge

" This is listed as a secondary display shown near the bottom of the TM-2030 

front panel, identified as  “

rPC”

.  

This will be of lesser significance when your batteries are charged and on “float” most 

of the time—when this may go to high values

. Many battery companies recommend that when recharging your batteries that 

you completely  replace the amount of charge most recently discharged by your batteries, plus add an additional 
percentage.  This depth of discharge is recorded by the TM-2030 during the previous discharge.  For "wet cell" lead acid 
batteries it is often recommended that 110-120% be replaced.  For AGM type (sealed) batteries 104-108% is often 
suggested.  At the end of a day of solar charging, the “

rPC”

 (“replaced percentage”) display will tell you how much you have 

replaced.  This level of charge may not happen every day—however if less than the ideal is achieved for a day or two, it would 
be good to go even higher on subsequent days if possible. Soon after you start discharging your batteries again this will read 
0%—to anticipate the next day's recharge. 

New with Version 2.2 of the TM-2030 monitor

 

With this version, it is possible when viewing “

rPC

” function, to push and 

hold the RESET button to momentarily observe the previous depth of discharge in amp hours upon which the 

rPC

 percentage 

is based. This is useful, because if this discharge was small compared with your battery capacity, a large value of 

rPC

 should be 

of much less, if any concern.

 

5.3 A useful display item to see if you have extra solar power in the afternoon 

 

When charging with solar, often in the afternoon the batteries will begin to accept less solar energy—and as a result this energy 

may be wasted although it could be used for some extra loads, such as a dishwasher or vacuum. With the TM-2030 connected, 
there is a “secondary display” item that is not shown on the front panel called “

UPr”

 (Unused power) which displays this. If 

most of the solar power is now surplus (because the batteries are getting well charged), 

"YES" 

will show on the display.  If a 

lesser amount, the display will indicate the approximate number of watts that are being wasted. Refer to the 

Quick Reference 

Guide

, section 2.1 Also listed there is information about observing solar amps (“

SOL”)

 and battery temperature (

ºC

).

 

5.4 For information about the meaning of the LED lights on the SC-2030 charger 

Section 6 in this 

SC-2030 User's Manual

 describes in detail the meaning of the various charging modes referred to there.

 

5.5  There are two different standards you can select to define a “full charge.” 

The highest (more stringent) standard is selected by using TM-2030 program P7 to choose 

L4 

instead of  

L1, L2,

 or 

L3 

which 

use a lower standard, which requires only that the battery voltage exceed the value in  P1, and that the charging amps be less 
than P2. The L4 level requires  that in addition either the required "absorb time"  or "percent overcharge" be achieved,  such 
that the "float"  state has  been reached.  This establishes a better, but more difficult, level to reach. Refer to the 

TM-2030 

User's Instructions

, section 6.2 for details. 

5.6 Using History Data to diagnose system problems 

The TM-2030 (TriMetric) makes history data available when the user level P7 has been set to “L2,” “L3,” or “L4” in 
programming code “P7.” History is recorded daily for the past five days or the last five charge cycles, depending on the 
parameter. This data can be used to diagnose some system problems. Please refer to the 

TM-2030

 

User’s Instructions, 

section 

6.3 for instructions on interpreting this data. 

6. Technical information for interested and advanced users 

6.1 Charging lead acid batteries—basic information 

Charging a battery is very different than loading a tank with gasoline. First, when filling a tank it is very clear when the tank is 
full, and trying to overfill simply results in gasoline being spilled without any damage to the tank. Second, using up the 
gasoline until the tank is completely empty may be inconvenient, but again that does not damage the tank, even if the tank 
remains empty for a long time. Thirdly, filling the tank slowly or fast, whether the weather is hot or cold, or whether one is 
starting from a nearly-empty or nearly-full tank, does not affect the eventual amount of gasoline in the tank. Finally, a fuel 

Содержание SC-2030

Страница 1: ...to better preserve the capacity of your battery system 1 Amp hour counting Many battery companies recommend that when batteries are recharged they should be overcharged so that 104 to 120 percent of the charge that was previously removed should be replaced before going into float Most controllers don t measure this When connected with the TriMetric this controller measures the amp hours used and a...

Страница 2: ...r full efficiency May be safely used with panels up to 45A however charging current will be reduced to protect charger MINIMUM in out power efficiency at 30A 97 5 12V systems 98 5 24 V systems MINIMUM in out power efficiency at 15A 99 Battery capacity 10 to 10 000 amp hours Terminal block wire gauge Up to 6 AWG Larger stranded cables you can remove some strands to fit Charging profiles Three stage...

Страница 3: ...GM or liquid electrolyte These determine the charging only when the TM 2030 is not connected otherwise they are ignored In this case there is an absorb stage set to 14 6 or 29 2 volts for 12 or 24V liquid electrolyte systems or 14 3 or 28 6 for AGM systems which runs for two hours followed by a float stage of 13 2 or 26 4 volts 4 1 3 Temperature Compensation The optional temperature sensor is reco...

Страница 4: ...s Check volts For accurate battery voltage control the TriMetric s voltage measurement wire called B1 in TriMetric wiring diagram must be connected directly or close to the battery s positive terminal Check amps on the AMPS TriMetric display Under zero current conditions when all loads and charging sources are off the TriMetric s ampere indicator must show 0 0A or 0 1A at most when using the stand...

Страница 5: ...tool and correct RJ14 connector to avoid drilling a larger hole you could pass wire through a small drilled hole through TM 2030 enclosure then use crimp tool to install connector carefully observing polarity Fig 1 Don t yet connect the communication cable to the TM 2030 unless connectors at each end are attached and you don t intend to put them on or change them later 4 4 3 Remove front panel and...

Страница 6: ...t the absorb voltage Flashing 3 times indicates floating mode Flashing 4 times in higher voltage finish limited current charging With TM 2030 connected only Flashing 5 times at maximum voltage finish limited current charging With TM 2030 connected only Flashing 6 times Was in float now discharging but still at least 98 full With TM 2030 connected only Flashing zero times Discharging and less than ...

Страница 7: ...t shown on the front panel called UPr Unused power which displays this If most of the solar power is now surplus because the batteries are getting well charged YES will show on the display If a lesser amount the display will indicate the approximate number of watts that are being wasted Refer to the Quick Reference Guide section 2 1 Also listed there is information about observing solar amps SOL a...

Страница 8: ...energy electrons into the battery The battery always tends to resist the tendency to push the electrons in the voltage of the charger must be high enough to overcome the resisting force of the battery This is a little like pushing water into a pipe which is under pressure enough force must be provided to push it in or it will not go The current or amperes is a measure of how much charge energy is ...

Страница 9: ...e variations on this method 1 Charge above the gassing voltage until the amperes drop to a sufficiently low value say an ampere value that is 1 or 0 5 of the amp hour capacity of the batteries 2 Charge until the value of amps into the batteries stops decreasing for a specified period of time and stays at this constant value for perhaps a couple of hours 3 Charge until the charger has replaced a sp...

Страница 10: ...r current until it reaches the limiting absorb voltage shown After that it charges for an absorb time of two hours Then it regulates at the float voltage shown 6 4 Two Graphs of charging profiles for SC 2030 when TM 2030 is connected The first profile figure 2 is more typical of most good solar chargers However the SC 2030 has an additional unusual option of setting a percentage of overcharge valu...

Страница 11: ...rops below P2 P3 AND overcharge P20 OR Timer expires with P14 time For the 4 state profile Timer starts counting with P14 time as shown on 4 state charging profile The first time after the charger is turned on Goes into float when Amps drops below P2 P3 OR Timer expires After the first time Amps drops below P2 P3 at least once during Absorb AND overcharge P20 OR Timer expires with P14 time 6 6 Bat...

Страница 12: ...r repaired at Bogart Engineering s discretion provided it has not been subjected to abuse or misapplication For warranty service please email bogart bogartengineering com A return merchandise authorization is required for all merchandise to be returned to Bogart Engineering How to obtain customer service Please review our support page before attempting to contact us Our distributors are able to an...

Страница 13: ...es compared to the most recent discharge before going into float Also it has been considered best suited for AGM or Gel type lead acid batteries however recently some manufacturers are recommending the four stage profile next page for AGM type batteries Liquid electrolyte batteries can usually benefit from four state solar charging Figure3 To select three stage charge control set program P21 finis...

Страница 14: ...Max over voltage time allowed 0 1 10 0 hours Absorb stage terminates when Charged setpoint amps When P21 not OFF Max finish volts P15 value When P21 is OFF Max finish volts P1 value 4 state charging profile for liquid electrolyte batteries Figure 3 Bulk Absorb Finish Absorb Float Time counting P14 starts here when P21 is not off Starts here when P21 is off Time counting temporarily stops whenever ...

Страница 15: ...tery systems Up to 30 amps of panels can be used If more than 30 amps is used the SC 2030 will safely limit current 1 A FUSE Optional battery temperature sensor Small wires go to connector in SC 2030 SHUNT Choose 500A 50 mV or 100A 100mV TWO KELVIN SCREWS 4 small wires from battery to meter up to 100 feet Usually a cable with four 22 or 24 wires is used Optional connection for measuring voltage on...

Страница 16: ...les previously connected to the battery negative pole must then be reconnected to the load side of the shunt Connect four wires from shunt and battery to Meter Cable consisting of small wires 22 up to 100 feet long need to connect from the TriMetric to the shunt and batteries WHAT S INVOLVED IN INSTALLING THE BOGART ENGINEERING SC 2030 Solar Charger Brief description Complete description is in the...

Отзывы: