Maintenance  

 
 
 
 
 
Maintenance UK 

It is a legal requirement, under regulation 9 of the COSHH 
regulations that all local exhaust ventilation systems are 
thoroughly examined and tested at least once every 14 
months (typically carried out annually). The approved code 
of practice recommends that a visual check should be 
carried out at least once a week. 
 
COSHH requires the annual inspection and testing to be 
carried out by a competent person and specifies that 
documentation results are recorded in a log.  
 
Contact the seller for more information about inspection 
and certification.  
 

Maintenance General 

User maintenance is limited to cleaning the unit and filter 
replacement, only the manufacturers trained maintenance 
technicians are authorised to carry out component testing 
and replacement. Unauthorised work or the use of 
unauthorised replacement filters may result in a potentially 
dangerous situation and/or damage to the extractor unit 
and 

will invalidate the manufacturer’s warranty.

 

 

Cleaning the unit 

The stainless steel units should be cleaned with a 
proprietary stainless steel cleaner, in accordance with the 

manufacturer’s 

 user instructions 

The powder coat finished units can be cleaned with a damp 
cloth and non-aggressive detergent, do not use an abrasive 
cleaning product as this will damage the finish. 
 
The cooling inlets and outlets should be cleaned once a year 
to prevent build-up of dust and overheating of the unit.  
 

Replacing Filters 

The iQ system constantly monitors the condition of the 
individual filters. As the filters block the LCD display will 
show the relevant filter symbol filling up. (see section

 

for 

LCD details) Each filter symbol fills up in 5% increments, 
when the filter icon is filled that particular filter will need 
replacing.  

 
 
                          Pre Filter blocking      Combined Filter Blocking 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
A log of the changes should be maintained by the user. 
The filters require attention when the display shows the 
filter blocked icon/ filter output signal (if fitted) or when the 
extractor no longer removes fume efficiently. 
 
All filters are tested to EN1822. A certificate of conformity 
for each filter is available on request. 
 
It is recommended that a spare set of filters are kept on site 
to avoid prolonged unit unavailability. Part numbers for 
replacement filters can be found on the filters fitted in your 
system.  
 
 
To prevent overheating, units should not be run with a 
blocked filter condition, or with dust obstruction of Inlets / 
Outlets. 
 

75% filter blocked indication 

When the filters become 75% blocked the buttons on the 
front of the extraction unit will turn from Green to Amber 
and if fitted the iQ system will output a signal to indicate 
this. At this time it is recommended spare filters are 
available as a change may be needed shortly. 
 
 

 

 

 

01 

 

T

IME

 

Содержание AD500 iQ

Страница 1: ...AD500 iQ V3 AUG 17 ...

Страница 2: ...afety notes Safety labels Unpacking and unit placement Fume capture methods Connecting to power supply Optional added features Optional added features cont d Turning extractor On changing display units Setting the airflow Airflow auto adjust first installation only Cleaning the unit Pre filter replacement Combined filter replacement iQ Display features Visual alarms Visual alarms cont d USB Connec...

Страница 3: ...Overview 1 01 Lockable Castors USB Port Door Catches Key Lock Door Catch Control Panel Company Branding LCD Display Combined Filter Pre Filter Filter Stops Combined Filter Lever ...

Страница 4: ...Overview 1 02 Air Inlet Exhaust Outlet Motor Cooling In Out Main Isolation Switch Mains Inlet Signal Cable Inlet Compressor Connection Optional ...

Страница 5: ...me pre filter condition Real time Combined filter condition Internal unit temperature 0 C 0 F Motor run hours Alarm window Target airflow set point Actual airflow in CFM or m3 h Motor status icon Overview 1 03 ...

Страница 6: ...scribed in this manual 3 Connect the system to a properly grounded outlet Dangers to eyes breathing and skin Once used the filters within the AD 500 iQ system may contain a mixture of particulates some of which may be sub micron size When the used filters are moved it may agitate some of this particulate which could get into the breathing zone and eyes of the operative Additionally depending on th...

Страница 7: ...oad Operating frequency Year of Manufacture Relevant approval markings logos PLEASE NOTE If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment maybe compromised Fire Risk Warning In the very rare event that a burning ember or spark is drawn into the fume extraction unit it may be possible that the filters will ignite Whilst any resultant fi...

Страница 8: ... Caution Due to the weight of the extractor suitable lifting equipment should be used and with regard to appropriate safety precautions See Appendix for product weight details Ensure that 500 mm space is available around any vented panels on the extractor to ensure adequate airflow 3 With the unit in position lock the 2 front castors Caution Do not block or cover the cooling vents on the unit as t...

Страница 9: ...d be kept to a minimum where possible to prevent the fume being blown away from the nozzle High speed bottling lines may need bigger scoops or nozzles both sides of the bottles because of the turbulence caused by the speed of the bottles Moving products For applications where the product to be marked is moving past the stationary laser head the capture nozzle should be positioned as close as possi...

Страница 10: ... to the mains The supply cord should only be replaced by a BOFA engineer as an electrical safety test may be required after replacement The iQ system MUST be connected to a properly earthed outlet If your iQ system was ordered with any optional extras please read section 4 03 before the power connection is made as additional connections may be required before power is connected to the extractor Co...

Страница 11: ... is removed the motor will slow down and come to a stop The extractor will need to be turned on and be out of standby mode See section 5 for turning the extractor on in order for this feature to operate Volt free input This configuration requires the Black Red cores of the signal cable see section 1 for location to be connected together in order to start the extractor When the 2 cables are connect...

Страница 12: ...he connection between the Green White cables will become Open When the extraction system is running normally the connection between the Green White cables will become Closed Separated Signal With this configuration the Filter blocked System fail signals will be separated to give 2 individual signals When the filters become blocked the connection between the Green White cables will become Open If t...

Страница 13: ...t to the combined filter handle To enable the iQ system to function the front door must be closed and the latches secured A second switch is located in the iQ extraction unit behind the pre filter If there is no pre filter fitted the iQ system will prevent the extraction unit from starting up A pre filter will need to be installed see section 6 02 and the front door closed before the unit is able ...

Страница 14: ... depressed to power the unit To start the extraction unit press the front panel power button refer to section 1 for switch location the button will change from Red to Green indicating the extraction unit is now fully On It is recommended that the rear isolation switch is left in the On position and the front standby switch is used to toggle the extractor On Off Changing the display units The Airfl...

Страница 15: ...Enter middle button Refer to section 1 for button location for 3 seconds or until all 3 button lights flash green 2 Release the Enter button the iQ system is now in set mode Press either the Up or Down button to adjust the airflow accordingly Real time airflow is displayed on the LCD screen Refer to section 1 for Display information 3 Once you have your desired airflow leave the controls after aro...

Страница 16: ...e installation is causing too much restriction for the desired airflow to be reached the Auto Adjust feature will be activated The procedure events are listed below 1 The 3 buttons will begin flashing Red along with the airflow setting on the LCD screen 2 The airflow setting on the screen will drop to display the highest airflow that can be achieve 3 The airflow will stabilise and the buttons will...

Страница 17: ...duct as this will damage the finish The cooling inlets and outlets should be cleaned once a year to prevent build up of dust and overheating of the unit Replacing Filters The iQ system constantly monitors the condition of the individual filters As the filters block the LCD display will show the relevant filter symbol filling up see section 1 for LCD details Each filter symbol fills up in 5 increme...

Страница 18: ...e buttons will glow Red and if fitted the filter blocked signal will be given To remove and replace the Combined filter follow the procedure detailed below Warning The combined filter is very heavy Over 40Kgs therefore the procedure below must be carried out by 2 people lifting together 1 Isolate the electrical supply to the extractor 2 Undo the catches on the front of the unit and open the door 3...

Страница 19: ... system features a 2 stage Hose blocked alarm Partial hose blockage Full hose blockage Partial hose blocked alarm This alarm will become active when the iQ system detects a part blockage in the installation The iQ system interprets a partial blockage as a vacuum spike within the ductwork but is only a partial blockage as the extractor is still able to maintain its set airflow During this time it i...

Страница 20: ...ront door and re connect the mains supply Gas Filter monitoring VOC Sensing If the VOC Volatile Organic Compound sensing option has been fitted to your iQ system then this will be constantly monitoring the exhaust gas of the extraction unit If the VOC level in the exhaust exceeds the PPM Parts per million level pre set at BOFA then the Gas alarm will be triggered and display the Gas icon as shown ...

Страница 21: ...e from the seller if specification has been pre arranged with the seller Or download original settings from your master iQ unit Max capacity USB Stick 4GB 2 Download this file to a blank memory stick 3 Place the iQ system in standby mode Front power button glowing Red 4 Open the front door and insert the memory stick into the USB slot 5 The LCD display will show upload press the button correspondi...

Страница 22: ...a To download the information from the iQ system please follow the procedure below 1 Obtain a memory stick Max capacity USB Stick 4GB 2 Place the iQ system in standby mode Front power button glowing Red 3 Open the front door and insert the memory stick into the USB slot 4 The LCD display will show download press the button corresponding to this 5 The display will show a progress complete bar and w...

Страница 23: ...ion Shows the percentage of the iQ system capacity that is taken up by the installation pipe work this value would also rise if the inlet or pipe work becomes blocked Motor output Shows the percentage the motor is being run at to achieve the airflow set by the user This value will increase as the filters begin to block Internal temperature Shows the internal temperature of the extraction unit the ...

Страница 24: ...r that outputs 12V DC providing the iQ system with power If the buttons on the front panel are not illuminated or operational this would indicate a problem with the internal power supply provided the main isolation switch is in the ON position and voltage is proven at this point If the internal power supply has failed then arrangements should be made to replace the transformer Error Codes on the i...

Страница 25: ...Serial Number Pre filter Combined filter Date Engineer Date Engineer Filter disposal The Pre and Combined filters are manufactured from non toxic materials Filters are not re usable cleaning used filters is not recommended The method of disposal of the used filters depends on the material deposited on them For your guidance Deposit EWC Listing Comment Non Hazardous 15 02 03 Can be disposed of as n...

Страница 26: ...aximum Altitude 2000m Size Metric mm Imperial inches Height 1201 47 2 Depth 787 31 Width 617 24 3 Filters Filter Type Surface area Efficiency Pre filter 30 0m2 95 0 9micron Combined filter 7 5m2 99 997 0 3micron Combined Filter Gas section Filter Type Carbon type Amount Combined filter Gas Activated carbon 34kgs Environmental operating range Temperature 5o C to 40o C Humidity Max 80 RH up to 31o C...

Страница 27: ... Information BOFA Headquarters 21 22 Balena Close Creekmoor industrial Estate Poole Dorset BH17 7DX UK Phone 44 0 1202 699444 BOFA Americas 303 S Madison Street Staunton Illnois 62088 USA Phone 001 618 205 5007 ...

Отзывы: