background image

CAUTION:  

THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE  

     

THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE  

     

INSTALLING OR SERVICING THIS UNIT.

NOTE:

  BEFORE INSTALLING THE CONTROL DEVICE, MAKE SURE THAT THE NECESSARY BRANCH CIRCUIT  

WIRING IS AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO 

A GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED.

STEP #1

MOUNTING THE GTD20A

>  FAMILIARIZE YOURSELF WITH THESE INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

>  Mount GTD20A in a convenient location using appropriate hardware (not supplied). See Illustration 1 for 

typical installation. 

DO NOT MOUNT WITH LID FACING DOWN 

(See Illustration 2)

.

ILLUSTRATION 1

WALL MOUNTING

STEP #2

INSTALLING THE GTD20A 

>  Disconnect AC power from all supply circuits.

>  Remove GTD20A lid and install necessary conduit and wiring (not supplied) to the GTD20A.

>  Refer to the illustrations on the following pages for proper wiring connections and choose the correct  

illustration for your application.

>  Note: When using Class 2 power limited circuits, (for example, 0-10 VDC dimming connections)   

remember to keep this wiring separate from high voltage wiring by using separate conduit and the 
enclosure knockout provided.

>  Replace GTD20A lid and secure.

INSTALLATION

2

ILLUSTRATION 2

FACE DOWN MOUNTING (NOT APPROVED)

Содержание GTD20A

Страница 1: ...ch Circuit Emergency Lighting Transfer Switch BCELTS under UL 1008 or a Switch Bypass under UL 924 Use the proper wiring diagram in the appropriate section of these instructions 6 An unswitched normal AC power source 120 through 277 VAC 50 60 Hz and a direct separate connection to a generator supplied or central inverter system supplied emergency panel are required 7 The use of accessory equipment...

Страница 2: ...cation using appropriate hardware not supplied See Illustration 1 for typical installation DO NOT MOUNT WITH LID FACING DOWN See Illustration 2 ILLUSTRATION 1 WALL MOUNTING STEP 2 INSTALLING THE GTD20A Disconnect AC power from all supply circuits Remove GTD20A lid and install necessary conduit and wiring not supplied to the GTD20A Refer to the illustrations on the following pages for proper wiring...

Страница 3: ...Y LOCAL SWITCHING MEANS LIGHTING LOAD UP TO 20 A 1 2 3 4 5 6 7 HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 1 2 3 4 5 6 7 DIMMING RACK GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL...

Страница 4: ...G DRIVER PURPLE LEADS TO DIMMING DRIVER GRAY LEADS PURPLE GRAY 1 2 3 4 5 6 7 GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 EMERGENCY CKT BKR PANEL LIGHTING LOAD UP TO 20 A HOT NEUTRAL NORMAL CKT BKR PANEL HOT NEUTRAL HOT NEUTRAL WIRE GAUGES FORALLLEADS TERMINATINGATT2 SHOULD BE 18AWG JUMPER CONNECTIONS ON T1AND T2ARE CONTRACTOR INSTALLED 0 10 VDC DIMMER BLK BLK WHT IF PROVIDED NOTE Wire ga...

Страница 5: ...WITCHING MEANS GTD20A ELECTRONICS COVER T1 GTD20A TERMINAL BLOCKS T2 HOT HOT NEUTRAL NEUTRAL WIRE GAUGES FOR ALL LEADS TERMINATING AT T2 SHOULD BE 18 AWG JUMPER CONNECTIONS ON T1 AND T2 ARE CONTRACTOR INSTALLED 4 5 6 7 1 2 3 NORMAL CKT BKR PANEL DIMMED HOT TO DIMMING DRIVERS SWITCHED HOT TO DIMMING DRIVERS NEUTRAL TO DIMMING DRIVERS EMERGENCY CKT BKR PANEL 1 2 3 4 5 6 7 DIMMING CONTROL GTD20A ELEC...

Страница 6: ... LED should extinguish and the controlled lighting load should illuminate regardless of the local switch position provided emergency power is available check red LED During a quick test using a GTD20A with a dimming system the lighting load should illuminate at full lumen levels when the test switch is depressed regardless of the lumen level during normal operation The entire generator or central ...

Отзывы: