Cosmos - Helios - Solaris
COSMOS - HELIOS - SOLARIS
A mini = 1m
B max = A - 0,5 m
mini 1 m
A + B = 14 m. maxi
A
B mini = A + 0,5 m
B
+ 1 m
+ 0,5 m
M
axi 15 m
M
ini 2 m
COSMOS 145
ONTOP System US dia 130/200
* B > A + 3 m : réduction dia.65 mm
** H > 3 m : réduction dia.65 mm
*
**
COSMOS 100
ONTOP System US dia 100/150
* B > A + 3 m : réduction dia.50 mm
** H > 3 m : réduction dia.50 mm
HELIOS SOLARIS
3
CHIMNEY INSTALLATION
- The only two permitted flues are:
Ontop system US diam. 130/200 or POUJOLAT 130/200 EI
Ontop system US diam. 100/150 or POUJOLAT 100/150 EI
- The gas outlet must be protected mechanically by a grill if it is positioned less than 2.2 m
from the ground.
- Any accessible part of the flue must be protected to prevent burning.
The gas air-vent
fireplace must be connected by an approved installer in accordance with the standard NBN
D51/003 or NBN D51/006 LPG and Pr NBN 61-002 (2005) for Belgium and standard NFD 35-377 or
Document Technique Unifié (DTU P45 204) for France
- The minimum and maximum lengths must comply with the chart below.
For each additional horizontal metre, add 1 metre of vertical duct.
For each additional 90° elbow, add 1 metre of vertical duct.
For each additional 45° elbow, add 0.5 metre of vertical duct.
- Only install
the draught limiter or reduction kit
if there is a difference in vertical length
of over 3m in relation to the horizontal length
Category C31s (Renovation kit)
You must use a clean, airtight chimney
flue with a section with diameter
measuring at least 200 for the Cosmos
145 and Argos, and 150 for the Cosmos
100, Helios and Solaris.
The “existing chimney” element is an
integral part of the installation, and
should be considered as a rigid duct for
the regulations concerning acceptable
heights and lengths.
Connections at the bottom and top
of the flue must be made with the
parts supplied by our recommended
manufacturers and must also guarantee
sound airtightness.
Installation must be by an authorized
installer.