5. 5     C O N EC T I N G     A N     P R O ST A T 4     T H E R M O ST A T  

 
 

 

Use 1.0mm² 4 core cable 

Connections 

– (Colours for reference only) 

Connect Red wire 

– Terminal 3 of Heater and Power IN - Live Terminal (L) on Thermostat. 

Connect Black wire 

– Terminal 5 of Heater and Heaters Live Terminal (L) on Thermostat. Black wire carries 230v when thermostat is on. 

Connect Blue Neutral wire 

– Terminal N of Heater and Power IN - Neutral Terminal (N) on Thermostat.

 

Connect Green / Yellow wire 

– Terminal E or 

of Heater and Terminal E (Earth connection) on Thermostat. 

 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE 

PLEASE NOTE:-Turn up fully the internal thermostat on the back of the heater so it does not override this thermostat

 

 

 

5 . 6     C O N EC T I N G     A N     P R O T I M - 7         7   D A Y   P R O G R A M A B L E  T I M ER  

 
 
 

 

Use 1.0mm² 4 core cable 

Connections 

– (Colours for reference only) 

Connect Brown Live wire 

– Terminal 1 of Heater and Terminal L on Programmable Timer (230V Live connection). 

Add a Link cable (1mm²) between Timer L connection and Timer 

S

in connection. 

Connect Black wire 

– Terminal 2 of Heater and Terminal 

S

out on Programmable Timer. 

Connect Blue Neutral wire 

– Terminal N of Heater and Terminal N on Programmable Timer (230V Neutral connection). 

Connect Green / Yellow wire 

– Terminal E or 

of Heater and Terminal E (Earth connection) on Programmable Timer. 

 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE 
 

 

Links may be 
required 

– See 

Section 7 

The controls and heaters may be fed from a different source and it is essential that all circuit breakers feeding the heating system are isolated 
prior to any work being carried out on any of the heaters in the system.  

Links may be 
required 

– See 

Section 7 

The  controls  and  heaters  may  be  fed  from  a  different  source  and  it  is 
essential that all circuit breakers feeding the heating system are isolated 
prior to any work being carried out on any of the heaters in the system.  

Содержание OUH2 Series

Страница 1: ...or use only The controls and heaters may be fed from a different source and it is essential that all circuit breakers feeding the heating system are isolated prior to any work being carried out on any...

Страница 2: ...tside walls along the most exposed part of the building which is normally subjected to the prevailing winds see pictures at bottom of page MULTI FUNCTIONAL BRACKET Using the pictures above and to the...

Страница 3: ...ter in mounting position 7 8 or 9 you MUST remove the 2 side panels turn them around 180 and reinstall them Would you also please turn around the front guard so our Logo reads correctly Many Thanks 3...

Страница 4: ...een terminals L1 L2 L2 L3 can be found with this instruction leaflet Cable Sizes OUH2 03 3kW Use minimum 1 5mm 3 Core Mains Cable see note above OUH2 05 5kW Use 4mm 3 Core Mains Cable see note above O...

Страница 5: ...mote thermostats are used turn up the internal thermostat to full allowing the external thermostat to control the heater RST TP Tamperproof Thermostat Used exactly the same as the RST2 IN but temperat...

Страница 6: ...TAT Use 1 0mm 4 core cable Connections Colours for reference only Connect Black wire Terminal 10 of Heater and Terminal 3 on Frost Thermostat Connect Brown Live wire Terminal 11 of Heater and Terminal...

Страница 7: ...Earth connection on Control Switch HEATER to THERMOSTAT Connect Black wire Terminal 5 of Heater and Terminal 1 on Thermostat Please note Black wire can be joined in the control switch using a suitabl...

Страница 8: ...rminal 1 of Heater and Terminal L on Programmable Timer 230V Live connection Add a Link cable 1mm between Timer L connection and Timer Sin connection Connect Black wire Terminal 2 of Heater and Termin...

Страница 9: ...nd still linked as Master Slaves If Using RCD Residual Circuit Device all Heaters connected in a Master Slave arrangement MUST be supplied from the same RCD and not multiple RCD s Multiple MCB s for e...

Страница 10: ...nnect Black wire Terminal 6 of Master heater and Terminal 6 of first Slave heater Connect Grey wire Terminal 7 of Master heater and Terminal 7 of first Slave heater Connect Green Yellow wire Terminal...

Страница 11: ...g can damage the heater and is not covered by the guarantee 9 TROUBLE SHOOTING AND SOLUTIONS Wall thermostat does not work correctly in a Master Slave set up or single heater Check that you have turne...

Страница 12: ...t losses from the entire area you are heating If you are in any doubt please contact BN Thermic and we can carry out a quick check for you Temperature rise OUH2 industrial fan heaters warm a space by...

Отзывы: