Electrical installation 

 

 

 

Heaters  are  factory  fitted  with  high  temperature  silicon  rubber  flexible  cable  conforming  to  BS  6500  having  a 

temperature rating of 180°C continuous.  

 

Appliances must be earthed. 

 

The CH fitting has been packed with a separate wall mounting bracket ready for attachment to the heater.  

Place heater face down and attach one ‘U’ bracket to back. Make sure cable gland is towards the bottom of the heater. 

 

 
 
 
 
 
 
 
 
 
Location 

 

 

Heaters should be angled at 30° to 45° from the vertical whether wall or ceiling mounted.  

 

There must always be a minimum clearance of 450mm between top of heater and ceiling.  

 

Wall mounting 

 

 

Decide whether vertical movement only (Diagram A) or vertical/horizontal movement (Diagram B) is required for 

correct positioning of heaters and assemble as shown.  

 

Avoid mounting heaters on structures liable to vibrate.  

 

Recommended mounting heights and safety distances should always be observed. 

 

Recommended Wall Mounting Heights

 

Model 

Wall Mounting Height 

(Metres) 

Safety Distance from 

Heater (Metres) 

Minimum 

Recommended 

Maximum 

Minimum 

CH-1500 

2.2 

2.5 

3.5 

1.5 

CH-3000 

2.8 

3.5 

4.5 

1.5 

 

 