Requirements for Commonwealth of Massachusetts

Modifications to NFPA-54, Chapter 10

Revise  NFPA-54  section  10.8.3  to  add  the  following 

requirements:

For all side wall, horizontally vented, gas-fueled equipment 

installed  in  every  dwelling,  building  or  structure  used  in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above the finished grade in the area of the venting, 

including but not limited to decks and porches, the following 

requirements shall be satisfied:

1. 

INSTALLATION OF CARBON MONOXIDE 

DETECTORS

. At  the  time  of  installation  of  the  side 

wall,  horizontally  vented,  gas-fueled  equipment,  the 

installing  plumber  or  gas  fitter  shall  observe  that  a 

hard-wired  carbon  monoxide  detector  with  an  alarm 

and battery backup is installed on the floor level where 

the gas equipment is to be installed. In addition, the 

installing  plumber  or  gas  fitter  shall  observe  that  a 

battery-operated  or  hard-wired  carbon  monoxide 

detector with an alarm is installed on each additional 

level of the dwelling, building or structure served by the 

side wall, horizontally vented, gas-fueled equipment. 

It shall be the responsibility of the property owner to 

secure the services of qualified licensed professionals 

for  the  installation  of  hard-wired  carbon  monoxide 

detectors.

a.  In the event that the side wall, horizontally vented, 

gas-fueled equipment is installed in a crawl space 

or  an  attic,  the  hard-wired  carbon  monoxide 

detector  with  alarm  and  battery  backup  may  be 

installed on the next adjacent floor level.

b.  In the event that the requirements of this subdivision 

cannot  be  met  at  the  time  of  completion  of 

installation, the owner shall have a period of thirty 

(30) days to comply with the above requirements; 

provided,  however,  that  during  said  thirty  (30) 

day  period,  a  battery-operated  carbon  monoxide 

detector with an alarm shall be installed.

2. 

APPROVED CARBON MONOXIDE DETECTORS. 

Each  carbon  monoxide  detector  as  required  in 

accordance  with  the  above  provisions  shall  comply 

with NFPA 720 and be ANSI/UL 2034 listed and IAS 

certified.

3. 

SIGNAGE

. A metal or plastic identification plate shall 

be permanently mounted to the exterior of the building 

at  a  minimum  height  of  eight  (8)  feet  above  grade 

directly in line with the exhaust vent terminal for the 

horizontally  vented,  gas-fueled  heating  appliance  or 

equipment. The sign shall read, in print size no less 

than one-half (1/2) inch in size, “

GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.

4. 

INSPECTION

. The state or local gas inspector of the 

side  wall,  horizontally  vented,  gas-fueled  equipment 

shall  not  approve  the  installation  unless,  upon 

inspection,  the inspector  observes  carbon  monoxide 

detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is exempt 

from 24 CMR 5.08(2)(a) 1 through 4:

1.  The equipment listed in Chapter 10 entitled “Equipment 

Not Required to Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and

2.  Product Approved side wall, horizontally vented, gas-

fueled  equipment  installed  in  a  room  or  structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM PROVIDED. 

When  the  manufacturer  of  Product  Approved  side  wall, 

horizontally  vented,  gas-fueled  equipment  provides  a 

venting  system  design  or  venting  system  components 

with  the  equipment,  the  instructions  provided  by  the 

manufacturer  for  installation  of  the  equipment  and  the 

venting system shall include:

1.  Detailed instructions for the installation of the venting 

system design or the venting system components: and 

2.  A complete parts list for the venting system design or 

venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM NOT PROVIDED. 

When  the  manufacturer  of  Product  Approved  sidewall, 

horizontally  vented,  gas-fueled  equipment  does  not 

provide the parts for venting the flue gases, but identifies 

“special venting systems,” the following requirements shall 

be satisfied by the manufacturer:

1.  The referenced “special venting system” instructions 

shall  be  included  with  the  appliance  or  equipment 

installation instructions; and

2.  The  “special  venting  systems”  shall  be  Product 

Approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions.

A copy of all installation instructions for all Product 

Approved  side  wall,  horizontally  vented,  gas-fueled 

equipment, all venting instructions, all parts lists 

for  venting  instructions,  and/or  all  venting  design 

instructions shall remain with the appliance or 

equipment at the completion of the installation.

Содержание BG921-E

Страница 1: ...injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment person...

Страница 2: ...ide return air with optional RAB Return Air Base 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air See Blower Performance tables for additional information 2 Optional E...

Страница 3: ...lve Combustion Air Inducer Blower Access Door Combustion Air Pressure Prove Switch Cold End Header Box Control Box includes integrated ignition control transformer and interlock switch Blower Assembly...

Страница 4: ...bushing 1 Snap Plug 1 Wire tie 1 Condensate trap 1 Condensate trap cap 1 Condensate trap clamp 1 2 diameter debris screen 1 3 4 Threaded street elbow Check equipment for shipping damage If you find a...

Страница 5: ...rnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate Failure to do so may cause erratic limit operation and premature heat exchanger failure This furnac...

Страница 6: ...ALL OF THE FOLLOWING CRITERIA ARE MET a Furnace must be in its final location The vent system must be permanently installed per these installation instructions b Furnace must be installed as a two pi...

Страница 7: ...ion from the National Fuel Gas Code ANSI Z223 1 NFPA 54 This reprinted material is not the complete and official position of ANSI on the referenced subject which is represented only by the standard in...

Страница 8: ...e within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly or by ducts with the outdoors or spaces crawl or attic that freely commun...

Страница 9: ...Minimum 12 in 305mm above Crawl Space Floor Coupling or 3 in to 2 in Transition Field Provided See Maximum Vent Lengths table NOTE The inlet and outlet air openings shall each have a free area of at l...

Страница 10: ...ace can result in personal injury or death Combustion and flue products must never be allowed to enter the return air system or air in the living space Use sheet metal screws and joint tape to seal re...

Страница 11: ...ng SIDE VIEW 3 1 4 83 1 23 584 Overall Maximum 584 23 3 4 19 1 22 7 16 570 Overall Maximum SIDE RETURN AIR OPENINGS Either Side 5 5 8 143 1 Minimum 11 279 2 Maximum 14 356 683 26 7 8 7 1 4 184 FURNACE...

Страница 12: ...ion Installation Clearances Top Plenum 1 in 25 mm Front 0 Back 0 Sides 0 Vent 0 Floor 0 Front clearance in alcove installation must be 24 in 610 mm Maintain a minimum of 24 in 610 mm for front service...

Страница 13: ...16 Filters This unit is not equipped with a filter or rack Afield provided filter is required for the unit to operate properly Table 1 list recommended filter sizes A filter must be in place whenever...

Страница 14: ...t pipe hangers Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket Canadian...

Страница 15: ...et surface and end of pipe are wet with cement forcefully insert end of pipe into socket until it bottoms out Turn PVC pipe 1 4 turn Capacity VENT PIPE DIA in STANDARD CONCENTRIC Outdoor Exhaust Accel...

Страница 16: ...blockage restriction leakage corrosion or other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remain...

Страница 17: ...al furnace NOTE In non Direct Vent installations combustion air is taken from indoors and flue gases are discharged outdoors In Direct Vent installations combustion air is taken from outdoors and flue...

Страница 18: ...ck the terminations IMPORTANT Use Figure 24 to correctly size vent pipe diameter 030 045 070 090 110 Standard or Concentric See Table 3 Intake or Exhaust 1 1 2 2 2 1 2 or 3 Furnace capacity 1 Which te...

Страница 19: ...a 75 60 28 n a 97 97 78 78 9 36 21 70 55 23 92 92 73 73 10 31 16 65 50 18 87 87 68 68 Concentric Termination Elevation 0 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacit...

Страница 20: ...50 18 82 82 63 63 8 31 16 60 45 13 77 77 58 58 9 26 11 55 40 8 72 72 53 53 NOTE Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent...

Страница 21: ...n horizontal runs of exhaust pipe When transitioning up in pipe size use the shortest length of 2 PVC pipe possible When transitioning down in pipe size use at least 1 foot of 2 PVC pipe NOTE Exhaust...

Страница 22: ...ntake air will be drawn into the furnace from the surrounding space the indoor air quality must be considered and guidelines listed in Combustion Dilution and Ventilation Air section must be followed...

Страница 23: ...se insulation or other items that may clog the debris screen 2 If intake air is drawn from a ventilated attic Figure 31 or ventilated crawlspace Figure 32 the exhaust vent length must not exceed those...

Страница 24: ...N A 25 N A N A N A N A N A 2 in N A N A 18 16 31 28 50 48 30 30 2 1 2 in N A N A 13 N A 24 N A 42 N A 56 N A 3 in N A N A 9 9 18 18 35 35 47 47 20 to 1 7 to 17 1 1 2 in N A N A 15 N A 20 N A N A N A N...

Страница 25: ...arance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for...

Страница 26: ...s 152mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btu...

Страница 27: ...tallation codes the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches 305 mm IMPORTANT Details of Intake and...

Страница 28: ...44 6 On field supplied terminations a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8 and a minimum distance of 6 with a terminatio...

Страница 29: ...D TO ADAPT DIFFERENT VENT PIPE SIZE TO TERMINATION Figure 41 Direct Vent Concentric Wall Termination 71M80 69M29 or 60L46 US 44W92 or 44W93 Canada Figure 42 3 8 76MM 203MM STRAIGHT CUT OR ANGLE CUT IN...

Страница 30: ...d be connected to the 2 or 3 PVC flue pipe as shown in the illustration Do not use an accelerator in applications that include an exhaust termination tee The accelerator is not required 2 As required...

Страница 31: ...XHAUST LINES 12 305MM ABOVE AVE SNOW ACCUMULATION SIZE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 46 Non Direct Vent Field Supplied Wall Termination SIZE TERMINATION PER EXHAUST PIPE TER...

Страница 32: ...ermination Drain Trap assembled Figure 49 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure...

Страница 33: ...ittings glue all joints Glue the provided drain trap as shown in Figure 58 Route the condensate line to an open drain Condensate line must maintain a 1 4 downward slope from the furnace to the drain D...

Страница 34: ...iping from furnace must slope down a minimum of 1 4 per ft toward trap Figure 55 Evaporator Coil Using a Separate Drain Figure 56 Evaporator Coil Using a Common Drain Piping from furnace must slope do...

Страница 35: ...507867 02 Page 35 of 55 Issue 1933 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...

Страница 36: ...line through piping hole Gas line should not touch side of unit See Figure 61 and Figure 62 4 Piping should be sloped 1 4 per 15 feet 6 mm per 5 6 m upward toward the gas meter from the furnace The pi...

Страница 37: ...ted WARNING Figure 61 Gas Piping Upflow Applications NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIELD PROVIDED AND INSTALLED GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Upflow...

Страница 38: ...16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 50...

Страница 39: ...wer for service Complete the wiring connections to the equipment Use the provided unit wiring diagram and the field wiring diagram shown in Figure 66 Use 18 gauge wire or larger that is suitable for C...

Страница 40: ...ously on the heating speed when there is no cooling or heating demand See Table 16 for allowable continuous circulation speeds 2 When the furnace is running in the heating mode the indoor blower will...

Страница 41: ...507867 02 Page 41 of 55 Issue 1933 Figure 67 Typical Wiring Diagram...

Страница 42: ...ARNING Danger of explosion Can cause injury or product or property damage Should the gas supply fail to shut off or if overheating occurs shut off the gas valve to the furnace before shutting off the...

Страница 43: ...r to the unit 11 Set the thermostat to desired setting NOTE When unit is initially started steps 1 through 11 may need to be repeated to purge air from gas line 12 If the appliance will not operate fo...

Страница 44: ...bilize observe the flame Flame should be stable and should not lift from burner Natural gas should burn blue 4 After allowing unit to stabilize for 5 minutes record manifold pressure and compare to va...

Страница 45: ...s installation of a gas valve regulator spring which is provided with the gas conversion Kit LP Kits include low line pressure switch Table 13 Burner Orifice Conversion Kits at Varying Altitudes Capac...

Страница 46: ...d and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dryers and any appliances not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom e...

Страница 47: ...in place Motor Nameplate__________Actual__________ Blower Speeds Follow the steps below to change the blower speeds 1 Turn off electrical power to furnace 2 Remove blower access panel 3 Disconnect ex...

Страница 48: ...0 1390 348 1270 271 1135 199 885 109 735 71 0 20 1355 349 1230 280 1100 207 850 119 680 81 0 30 1330 368 1205 291 1060 220 795 126 625 84 0 40 1295 378 1180 298 1025 226 755 134 570 91 0 50 1265 386 1...

Страница 49: ...06 1275 173 1160 135 0 20 1655 392 1460 273 1315 219 1230 185 1110 142 0 30 1615 408 1410 282 1290 225 1195 192 1065 151 0 40 1595 416 1365 295 1245 236 1155 203 1010 160 0 50 1560 429 1335 308 1200 2...

Страница 50: ...33 1880 441 1715 353 1605 288 1435 210 2135 614 1885 421 1705 342 1595 280 1415 207 0 20 2085 648 1830 455 1665 362 1560 298 1360 220 2085 628 1830 437 1670 351 1545 293 1370 218 0 30 2040 663 1795 46...

Страница 51: ...intake pipes and all connections for tightness and to make sure there is no blockage NOTE After any heavy snow ice or frozen fog event the furnace vent pipes may become restricted Always check the ven...

Страница 52: ...limit from the vestibule panel 20 Remove top cap screws to allow top cap to be tilted upward to allow clearance for removing heat exchanger 21 Remove two screws from the front cabinet flange at the bl...

Страница 53: ...econnect wires to gas valve 44 Replace the blower compartment access panel 45 Refer to instruction on verifying gas and electrical connections when reestablishing supplies 46 Follow lighting instructi...

Страница 54: ...s Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furna...

Страница 55: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...