background image

4.3.9  

Proportional Dosing

Used to configure proportional Parts Per Million dosing to a system. This method 
of proportional dosing is based off an input signal the pump is receiving from an 
external flow meter. The flow meter must have a high speed pulse output >10Hz. 
You will need to refer to flow meter instruction manual to obtain the K-factor for 
the flow meter.

Default settings:  

12.5% dose solution concentration

 

 

 

 

 

1.25 dose solution Specific Gravity

 

 

 

 

 

5.0 K-factor (Pulses Per Liter), 

see flow meter instruction manual

 

 

 

 

 

1.0 Parts Per Million to dose

Press MODE button until 

Proportional Dosing 

is displayed in the top line of the 

display. 

To configure the pump, navigate to 

Proportional Dosing 

menu by using the 

short-cut method described at the beginning of the section, or by pressing 
MENU button, then selecting Input Setup, Input Modes, and then 

Proportional

.

Press UP or DOWN arrow to scroll through 0 - 9 on selected digit.

Press RIGHT arrow to scroll over to next digit to the right. If you pass your 
desired digit, you can easily scroll back by continuously pressing RIGHT button.

Press ENTER to save the changes.

Continue this process until all four screens have been configured.

If you used the short-cut to enter Proportional Dosing setup, press and hold 
Mode button until Run Mode screen is displayed.

If you used the Menu button to navigate to Proportional Dosing setup, you must 
navigate back out of menu structure. To do this you must select <-Esc at bottom 
of every screen menu until you see Run Mode screen displayed.

- Proportional Dosing

Input K-Factor (pulses):

Pulses Per Liter.
0.0001  -  9999.9999

- Proportional Dosing

Dose Specific Gravity:

Specific Gravity of solution.
Press ENTER to set.

.25

1

- Proportional Dosing

Dose Concentration:

Percentage of concentration.

Press ENTER to set.

- Proportional Dosing

PPM to dose:

Parts Per Million to dose.
000.0  -  100.0 PPM

0

12.5%

0

005.0000

0

01.0

Injection
Point

S3 Series  |  Hybrid Ultrasonic Flowmeter

NEMA 4X

IP 66

Industries, Ltd.

ProSeries

by Blue-White Ind.

TM

Doppler /
Transit Time

Discharge

Line

Paddlewheel

Flow Sensor / Meter

Ultrasonic

Flow Meter

Injection
Point

Example #1, Ultrasonic flow meter

Example #2, Paddlewheel flow meter

Discharge

Line

or

Page 24

MD-3

Page 25

- Menu

+ Configuration

+ Input Setup

+ Pump Output

<- Esc

- Input Setup

+ Contact Closure Input

- Contact Closure Input

    Close: Stop Pump
    Open: Stop Pump

<- Esc

Hidden

+ Motor - Select RPM
+ Tubing - Max Flowrate

+ Set FVS

+ Operating Input Modes

    Disable

Done

4.4   Contact Closure Input (Remote Start/Stop)

Used to remotely start and stop the pump using a close=stop or open=stop 
signal. If the pump must start when the loop is open, then select “Close: Stop 
Pump” option. Can be used with an external foot pedal, a PLC, contact closure, 
or other similar external devices.

Default settings:  

Disable

CC Input Range:  

6 - 30 VDC

 

 

 

 

 

or

 

 

 

 

 

Dry Contact Closure (no voltage required)

 

 

 

 

 

[See section 5.1 for wire connections]

Navigate to 

Contact Input 

menu by MENU button, then selecting Input Setup, 

and then 

Contact Input

.

Press UP or DOWN arrow to scroll through your options.

Press ENTER to make a selection. You should then notice the radio button 
(square box) is now filled in next to your selection.

Press DOWN arrow to scroll down to Done selection. Then press ENTER.

To prevent false triggering due to flickering (high speed) electrical switches, a 
trigger delay time can be configured to delay the pump command. The delay 
time unit of measure is seconds. A two second delay time is recommended.

To navigate back out of menus, select <-Esc and press the ENTER button at the 
bottom of every screen menu until you see the Run Mode screen displayed.

IMPORTANT: To begin operation, press the START button to place pump in 
STANDBY. The display background will turn blue indicating the pump has been 
stopped remotely. When the pump is started by the remote contact, the display 
background will turn green.

IMPORTANT: If the Contact Closure Input is enabled, the pump will display 
STANDBY if the pump has been stopped by the Remote Contact Closure. 

Please use caution in this mode as the pump may Start at anytime. If you 
must perform maintenance to the pump, Press STOP button.

When Contact Closure Input is enabled, the word 

Remote

 will always be 

displayed on the lower left side of the display screen.

Manual Speed Adjust

Waiting for SIGNAL...

STANDBY

REMOTE

Manual Speed Adjust

GAL/DAY

228

Å

É

ÄÈ

REMOTE

Signal stopped pump

Signal started pump

Remote Delay

Input Remote Delay

Max Delay = 999.9 (s)
Press ENTER to set

0

00.0

MD-3

Содержание PROSERIES-M CHEM-PRO MD-3

Страница 1: ...CA 92649 USA Phone 714 893 8529 FAX 714 894 9492 E mail sales blue white com or techsupport blue white com URL www ProSeries M com PROSERIES M MD 3 Operating and Maintenance Manual ProSeries by Blue...

Страница 2: ...Input Hz 19 4 3 5 Pulse Batch low speed batch 20 4 3 6 Manual Cycle Adjust repeating cycle timer 21 4 3 7 Dispensing 22 4 3 8 Manual Dosing 23 4 3 9 Proportional Dosing 24 4 4 Contact Closure Input Re...

Страница 3: ...w Adapters 1 2 MPT Footvalve 9 230V 50HZ power cord BS 1363 A plug United Kingdom MD 3 Multi Diaphragm Metering Pump 2 190 RPM 4 090 stroke large diaphragm X Standard Equipment includes power cord and...

Страница 4: ...O O O O 14 F to 115 F 10 C to 46 C Ambient Storage Temperature O O O O 40 F to 158 F 40 C to 70 C Operating Voltage 96 to 264VAC 50 60Hz 220 Watts Power Cord Options 115V60Hz NEMA 5 15 USA 230V60Hz N...

Страница 5: ...dard Compatible with Blue White s output Flow Verification Sensor FVS system Includes stainless steel extended mounting brackets Lifts pump 4 1 2 11 43 cm for easy access in hard to reach areas MD 3 E...

Страница 6: ...w prevention check valve at discharge side of pump to prevent system fluid from flowing back through pump during pump maintenance A pressure relief valve is recommended at discharge of pump Bolt pump...

Страница 7: ...22cm 8 86in 22 50cm 4 00in 10 15cm n Made out of tough Stainless Steel n Provides a stable mounting surface Stainless Steel extended brackets allow the pump to be securely mounted to most any surface...

Страница 8: ...ly installed and sealed Never strap control input output cables and power cables together Power Interruption This pump has a user programmable auto restart feature which will either restore the pump t...

Страница 9: ...DC Form C 1 AMP MAX AT 125 VOLT AC 0 8 AMP MAX AT 30 VOLT DC 5A SLOW BLOW 20 X 5MM 1 2 3 T1 PULSE GND 4 20 1 2 3 T1 PULSE GND 4 20 0 10 15VDC 1 2 T2 0 1000 HZ MAX NEGATIVE POSITIVE POSITIVE NEGATIVE N...

Страница 10: ...values by one and increase pump output in Manual Speed Adjust mode Press and hold to increase values progressively faster Press and release to stop the pump Press and release to select menu items Pres...

Страница 11: ...l bar example While making a selection where only one choice is allowed you will see a radio button Radio button example In a screen where you are making changes you will see the word Done located at...

Страница 12: ...en to exit the menu structure and enter the run mode MD 3 Configuration Display Language Set Password Display Rate Esc Reset to Default Display Language English Spanish German Done French Display Lang...

Страница 13: ...y may be toggled through Speed RPM and your selected Display Rate by pressing the right arrow button Press MENU button to enter the menu structure Select Configuration and Press ENTER button Select Di...

Страница 14: ...ate Input Max Flowrate Flowrate ML min Press ENTER to set 0000 0 1 Contact Input Close Stop Pump Open Stop Pump Input Time Delay OFF 000 Range 1 255 sec Disable 00 0 Input Setup 4 20 mA Input Frequenc...

Страница 15: ...off Max Flowrate Input Modes Contact Input Set FVS Esc Hidden Remote Local Set DFD Set Rev Alarm Max Flowrate Input Max Flowrate Flowrate ML min Press ENTER to set 0000 0 1 To calculate the Max Flowra...

Страница 16: ...ate back out of the menu structure To do this you must select Esc at the bottom of every screen menu until you see the Run Mode screen displayed Tip The Manual Speed Adjust mode can be combined with C...

Страница 17: ...ontinue this process until all four screens have been configured If you used short cut to enter 4 20 mA input setup press and hold the Mode button until the Run Mode screen is displayed If you used Me...

Страница 18: ...displayed in the top line of the display To configure the pump navigate to 0 10 VDC Input menu by using the short cut method described at the beginning of the section or by pressing MENU button then...

Страница 19: ...GHT ARROW to select the digit to change press UP or DOWN arrow to scroll through 0 9 on selected digit Press enter to save changes and move to the next input screen To input flow rate values press the...

Страница 20: ...easily scroll back by continuously pressing the RIGHT button Press ENTER to save the changes Continue this process until all three screens have been configured If you used the short cut to enter Puls...

Страница 21: ...s have been configured If you used the short cut to enter Manual Cycle Adjustment setup press and hold Mode button until Run Mode screen is displayed If you used the Menu button to navigate to Cycle A...

Страница 22: ...scroll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until two...

Страница 23: ...Press RIGHT arrow to scroll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue thi...

Страница 24: ...ur desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until all four screens have been configured If you used the shor...

Страница 25: ...t false triggering due to flickering high speed electrical switches a trigger delay time can be configured to delay the pump command The delay time unit of measure is seconds A two second delay time i...

Страница 26: ...side Anywhere on discharge side of MD 3 pump Wiring for sensor can be connected directly to a MD 3 pump Pump will stop pumping if sensor detects no flow A relay will then close allowing for remote al...

Страница 27: ...ty of less than 430 microsiemens will not be detected This system is capable of detecting presence of a large number of chemicals including Sodium Hypochlorite Chlorine Hydrochloric muriatic Acid Sodi...

Страница 28: ...sure input menu setting section 4 4 is switched to disabled while LOCAL ONLY is selected This menu setting will return to the previous setting when REMOTE ONLY or DISABLED is selected Input Setup Inpu...

Страница 29: ...00 Pump Run Stop Frequency Mode Cycle Timer Mode Dispensing Mode Manual Dosing Prop Dosing 0 10 VDC Mode Pulse Mode Disable FVS DFD Pump Run Stop 4 20mA Mode Manual Mode Frequency Mode Cycle Timer Mod...

Страница 30: ...ut mA Signal 0 Pump Output 4 mA 100 Pump Output 20 mA Signal Output Frequency Output Disable Done 4 20 mA Output Default 4 20 mA output settings shown Signal Output Disable Done 4 20 mA Output Default...

Страница 31: ...t assume responsibility for damage to pump that has been caused by chemical attack 6 2 Cleaning Pump Pump will require occasional cleaning especially Injection fitting Footvalve Strainer and pump head...

Страница 32: ...Page 32 MD 3 7 0 Exploded view and parts list 1 2 16 4 24 6 8 7 10 22 9 15 14 23 19 21 18 3 13 11 3 17 20 12 25...

Страница 33: ...TFE P 8 70001 346 CARTRIDGE VALVE EP 9 90002 272 PUMP HEAD 2 10 70004 115 PUMP HEAD FACE PLATE 2 11 90011 210 SCREW 10 32 X 2 0 SOC HD 16 12 90011 094 WASHER 10 4 13 90003 141 O RING 2 018 TFE P 4 900...

Страница 34: ...t 40 PSIg ML MIN 32 151 303 751 1508 2252 3041 RPM 1 3 10 19 48 95 142 190 GPH 0 5 2 4 4 8 11 9 23 9 35 7 48 2 Feed Rate at 90 PSIg ML MIN 25 145 278 694 1388 2107 2391 RPM 1 3 10 19 48 95 142 190 GPH...

Страница 35: ...Page 35 MD 3 Page intentionally left blank...

Страница 36: ...etering type of pump Should it become necessary to return the pump for repair or service you must attach information regarding the chemical used as some residue may be present within the unit which co...

Отзывы: