M12 Output Connector 2
PIN
Function
Specifications
Reference
P1
Not Used
P2
Not Used
P3
N.O.
Relay Out, N.O. Contact
6 Amp Max @ 250VAC,
5 Amp MAX @ 30VDC
P4
N.C.
Relay Out, N.C. Contact
6 Amp Max @ 250VAC,
5 Amp MAX @ 30VDC
P5
Ground
Relay Out, COM Contact
M12 Output Connector 3
PIN
Function
Specifications
Reference
P1
Not Used
P2
Not Used
P3
N.O.
Relay Out, N.O. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
Page 17
®
FLEXFLO A4
6.0
Layout
6.5 M12 Connector
M12 Input Connector 1
PIN
Function
Specifications
Reference
P1
Remote Start/Stop
No Voltage
P2
FVS (+)
15 VDC @ 60 mA Supply
Power FVS Sensor
P3
FVS (-)
DC GND (0 VDC)
FVS Ground Input
P4
FVS (Signal)
Input Signal
FVS Input Signal
P5
Ground
DC Ground
0 VDC
P4
P1
P2
P5
M12 Input Connector 2
PIN
Function
Specifications
Reference
P1
Dry Contact
N.O. Dry Contact Closure
Open= Stop Gnd= Run
P2
4-20mA In (+)
120Ω Impedance Loop Ref. to Ground
P3
4-20mA In (-)
DC GND (0 VDC)
P4
Pulse In (+)
0-1000 Hz (AC. Square Wave) Ref. to Ground
FVS Input Signal
P5
Ground
DC GND (0 VDC)
M12 Output Connector 1
PIN
Function
Specifications
Reference
P1
4-20mA Out (+)
250Ohm max load
P2
4-20mA Out (-)
DC GND (0 VDC)
P3
N.O.
Relay Out, N.O. Contact 1 Amp @ 125 VAC
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
P1
P4
P5
P3
P2
P3
M12 Input/Output Connector
M12 Profibus Connector
Page 16
®
FLEXFLO A4
6.0
Layout
M12 Output Connector 4
PIN
Function
Specifications
Reference
P1
Pulse Out (+)
0-1000 Hz (AC. Square Wave) Ref. to Ground
P2
Pulse Out (-)
DC GND (0 VDC)
P3
N.O.
Relay Out, N.O. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
M12 Profibus Connector
PIN
Function
Specifications
Reference
P1
VP
+5V supply for terminating resisters
P2
RxD/TxD-N
Data line minus (A-line)
P3
DGND
Data ground
P4
RxD/TxD-P
Data line plus (B-line)
P5
Shield
Ground connection
Note:
M12 connectors not included with product.
Input/Output Connectors requires any A-Type M12 connector with 5 position female sockets
Profibus Connectors requires any B-Type M12 connector with 5 position female sockets
If the pump is the last bus device connected to the PROFIBUS cable it must be terminated using terminating resistor
(PROFIBUS standard EN 50170).
Содержание FLEXFLO A4 Series
Страница 1: ...Peristaltic Metering Pump Series A4 ...
Страница 33: ...Page 33 FLEXFLO A4 10 0 Industrial Protocols 10 1 Control and Status Mapping for Profibus and Ethernet IP ...
Страница 55: ...Page 55 FLEXFLO A4 PAGE INTENTIONALLY LEFT BLANK ...
Страница 60: ... FLEXFLO A4 Page 60 PAGE INTENTIONALLY LEFT BLANK ...