BLUE SKY SOLAR BOOST 2000E Скачать руководство пользователя страница 9

Installation and Operation Manual 

 

 

8

 

functioning and adjustment can be made. Verify that the LED remains on at the maximum current adjustment point, and as you check for a slight drop in 
current on either side of the maximum point. If LED does not remain on, MPPT is not operating due to a combination of high PV temperature and/or high 
battery voltage. MPPT can usually be made to operate by lowering battery voltage through application of a heavy DC load. If in doubt, leave the adjustment 
at the factory default position of midway between 11:00 and 12:00 o’clock as shown in Figure 3. Note that the LED briefly turns off every 10 seconds while 
the system recalculates the MPPT operating point. 

 
 

TROUBLESHOOTING GUIDE 

 

SYMPTOM 

PROBABLE CAUSE 

ITEMS TO EXAMINE OR CORRECT 

Completely dead, no 
display 

No battery power 

Battery disconnected, overly discharged, or connected reverse polarity. Battery powers the 
system, not PV. Battery voltage must be present for unit to operate. 

Display OK, but 
system will not turn on 
(charge status LED 
off) 

PV disconnected 

 

PV reverse polarity 
 

 

PV- connected to BAT-  

Verify PV connection. Requires PV to supply at least 0.15A at 

14V to begin charge. 

 

Reverse polarity PV will cause front panel to heat, and display to show “negative” PV current 
if battery is connected. 

 

PV- & BAT- must be separate for proper operation. PV- must receive earth ground via shunts 
in the 2000E which internally connect PV- to BAT-. External connection prevents proper 
operation of the internal current measurement system. 

Charge status LED on 
in Bulk, but no output 
charge current 

Dip switches set incorrectly 

 

Low PV power 

Double check dip switches #1-4. 

 

Correct PV’s. 

Charge status LED on 
& blinking in Constant 
Voltage mode but no 
output charge current 

Battery voltage greater than 
charge voltage setpoint 

 

Temp comp. enabled without 
sensor, or sensor failed open 

 

Battery voltage too low 

This is normal operation. Output is off due to high battery voltage which may be caused by 
other charging systems. 

 

Disable temp compensation, or replace sensor. Proper temp sensor terminal voltage when 
connected is 2.98V at 25

°

C, changing at +10mV/

°

C. 

 

A minimum battery voltage of 

9.0V is required for the unit to operate. 

Charge status LED on 
in Constant Voltage, 
relays click on/off 

Charge current is very low and 
the system is on the edge of 
being able to stay on 

 

PV- connected to BAT-  

If charge current is very low (

0.1 – 0.2A) because battery voltage is at setpoint, relays may 

switch on/off. This normal and will cause no harm. The on/off symptom will go away with a 
slight increase or decrease in battery voltage, or load current. 

 

PV- & BAT- must not connect together external to controller for proper operation. 

Relays click on/off 
rapidly 

Dip switch #2 off 

Double check dip switch #2, must always be on. Used for factory test only. 

Charge status LED 
blinking, charge 
voltage high 

System in equalize mode 

 

Temp sensor failed short, or 
installed reverse polarity  

Disable equalize by pressing the equalize pushbutton. 

 

Replace sensor, or remove sensor and disable temp compensation. Proper temp sensor 
terminal voltage when connected is 2.98V at 25

°

C, changing at +10mV/

°

C. 

Charge current is 
lower than expected, 
PV current may be low 
as well 

Battery is highly charged 
 

 

Worn out PV modules 

 

Low insolation 

 

PV- connected to BAT- 
 
 

 

MPPT improperly setup 

Normal operation, system will be in Constant Voltage mode and current is reduced to control 
battery voltage. 

 

Replace, or use as is. 

 

Atmospheric haze, PV’s dirty, sun low on horizon, etc. 

 

PV- & BAT- must be separate for proper operation. PV- must receive earth ground via shunts 
inside the 2000E which internally connect PV- to BAT-. External connection prevents proper 
operation of the internal current measurement system. 

 

See Maximum Power Voltage and Optimizing MPPT sections. 

MPPT Current boost is 
less than expected 

PV maximum power voltage 
(V

MP

) is not much higher than 

battery voltage, leaving little 
extra power to be extracted 

 
 

 
 
 
PV’s hot 
 
 

 

MPPT improperly setup 

May result from PV’s with low V

MP.

 PV’s with higher V

MP

 produce greater power and current 

boost potential. PV’s with V

MP

 

 17V work best, PV’s with <36 cells tend to work poorly. 

 

Excessive PV wiring voltage drop due to undersize wiring, poor connections, etc., consumes 
and wastes available power. This simulates having PV’s with low V

MP

 

Battery is nearly charged and battery voltage is near setpoint. Output during MPPT operation 
is “constant power” so higher battery voltage produces less charge current. 
 
V

MP

 and available power decrease with increasing PV cell temperature. Cooler PV’s will 

produce greater boost. MPPT LED off indicates that extra power is not available from PV 
array. It is normal for boost to decrease as temperature rises. 

 

See Maximum Power Voltage and Optimizing MPPT sections. 

At high temperature, 
unit shuts down 

System temporarily shuts 
down due to high temperature 

Improve ventilation or reduce PV power. Providing sufficient ventilation or operating 
conditions which do not cause over temperature shut down will improve reliability. 

Содержание SOLAR BOOST 2000E

Страница 1: ...G PHOTOVOLTAIC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODEL SB2000E SAVE THESE INSTRUCTIONS COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS 6 111 391 Blue Sky Energy Inc 2011 430 0012 H ...

Страница 2: ...lectrostatic Handling Precautions 5 Selecting PV Modules 6 Temperature Compensation 6 Battery and PV Wiring 6 Setting Charge Voltage 7 Maximum Power Voltage 7 Optimizing MPPT 7 TROUBLESHOOTING GUIDE 8 SPECIFICATIONS 9 FIVE YEAR LIMITED WARRANTY 9 TABLES AND FIGURES Table 1 Charge Status Indicator 3 Table 2 Maximum Conductor Length 3 Voltage Drop 7 Figure 1 Front Panel and Remote Display Indicators...

Страница 3: ...ry or other electrical part that may cause explosion i Remove personal metal items such as rings bracelets and watches when working with a lead acid battery A lead acid battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION...

Страница 4: ...ghly accurate displayed voltage may be somewhat higher than actual battery terminal voltage when high charge current is being delivered to the battery This is due to voltage drop in the wires between the 2000E and battery Error during charge can be minimized by using large low resistance wiring The 2000E operates on battery power not PV power A battery must be connected with a minimum voltage of 9...

Страница 5: ... should always plan and monitor the process Equalization is essentially a controlled over charge and should only be performed on vented liquid electrolyte lead acid batteries Repeated charge discharge cycles can lead to an imbalance in the specific gravity and state of charge of individual battery cells Equalization brings all battery cells up to the same specific gravity and eliminates electrolyt...

Страница 6: ...0 with a discharged battery in near freezing temperatures For a more complete MPPT description see www blueskyenergyinc com INSTALLATION WARNING Read understand and follow the Important Safety Instructions in the beginning of this manual before proceeding This unit must be installed and wired in accordance with National Electrical Code ANSI NFPA 70 Over current protection must be provided external...

Страница 7: ...s recommendation Most 12 volt flooded or GEL lead acid chemistry batteries require the 30 0 millivolts C 5 00mV C cell setting NiCd and many lead acid chemistry AGM type batteries require the 20 0 millivolts C 3 33mV C cell setting WARNING Do not attach a sensor or any connections other than Blue Sky Energy battery temperature sensor p n 930 0022 20 to the temperature sensor terminals Be certain t...

Страница 8: ... be eliminating the need to have the battery be highly charged To access this and other technical bulletins see www blueskyenergyinc com MAXIMUM POWER VOLTAGE The nominal setting for this adjustment is the difference between the PV panel s open circuit voltage VOC and maximum power voltage VMP These voltage values are typically listed on both the PV panel datasheet and on the rating label affixed ...

Страница 9: ...cause battery voltage is at setpoint relays may switch on off This normal and will cause no harm The on off symptom will go away with a slight increase or decrease in battery voltage or load current PV BAT must not connect together external to controller for proper operation Relays click on off rapidly Dip switch 2 off Double check dip switch 2 must always be on Used for factory test only Charge s...

Страница 10: ...ct of God f operation or installation contrary to instructions pertaining to the product or g cosmetic aging 4 If BSE s examination of the product determines that the product is not defective the consumer shall be charged a test and evaluation fee of 20 and be responsible for all transportation costs and insurance related to returning the product to the consumer The consumer is ultimately responsi...

Страница 11: ...Blue Sky Energy Solar Boost 2000E MOUNTING TEMPLATE Figure 4 ...

Отзывы: