OPTIONAL TEMPERATURE COMPENSATION 

 

 

The charge voltage required by flooded or sealed (AGM or GEL) lead-acid chemistry batteries changes with battery temperature. Temperature 

compensation of charge voltage leads to improved battery performance and life, and decreased battery maintenance. Automatic temperature compensation 
can be provided using the optional battery temperature sensor p/n 930-0022-20. Most 12 volt lead-acid chemistry batteries require a compensation 
characteristic of –30.0 millivolts/

°

C (–5.00mV/

°

C/cell). The graph of Figure 2 shows charge voltage setpoint vs. battery temperature for the factory setting of 

14.0 volts @ 80

°

F and the compensation characteristic of –30.0 millivolts/

°

C. As described in the installation section the 2000E can also provide a –20.0 

millivolts/

°

C compensation characteristic required for 10 cell NiCd batteries and some GEL or AGM lead-acid chemistry batteries. 

 

FACTORY DEFAULT CHARGE VOLTAGE SETPOINT -VS.- BATTERY TEMPERATURE 

 

 

 

FIGURE 2 

 

MAXIMUM POWER POINT TRACKING (MPPT) 

 

 

Patented MPPT technology can extract more power and increase charge current up to 30% or more compared to conventional charge controllers. The 

principal operating conditions which affect current boost performance are PV array temperature and battery voltage. At constant solar intensity, available PV 
voltage and power increase as PV temperature decreases but it takes an MPPT controller to access this extra power. When PV voltage is sufficiently high in Bulk 
for MPPT to operate, a constant power output is delivered to the battery. Since output power is constant a decrease in battery voltage produces a further increase 
in charge current. This means that the 2000E provides the greatest charge current increase when you need it most, in cold weather with a discharged battery. In 
cool comfortable temperatures most systems see about 10 – 20% increase. Charge current increase can go to zero in hot temperatures, whereas charge current 
increase can easily exceed 30% with a discharged battery in near freezing temperatures. For a more complete MPPT description see 

www.blueskyenergyinc.com

.  

 
 

INSTALLATION 

 

¾

 WARNING: Read, understand and follow the Important Safety Instructions in the beginning of this manual before proceeding. 

This unit must be installed and wired in accordance with National Electrical Code, ANSI/NFPA 70. Over current protection must be 
provided externally. To reduce the risk of fire, connect to a circuit provided with 30 amp maximum branch-circuit over current 
protection in accordance with National Electrical Code, ANSI/NFPA 70. Do not connect a PV array capable of delivering greater 
than 20 amps of short circuit current I

SC

 at STC. Do not connect BAT– and PV– together external to the unit or improper operation 

or damage will result. Terminal block connections accept #20

10 AWG wire and are to be tightened to 9 in-lb (1 nm). The front 

panel serves as a heat sink for power control devices and requires free air circulation for cooling. Do not enclose the front panel 
behind a tight fitting door or otherwise substantially restrict air flow. Figure 3 shows generalized connections only and is not intended 
to show all wiring, circuit protection and safety requirements for a photovoltaic or DC battery electrical system. 

 

 
 

¾

 CAUTION: The unit is protected against reverse battery and PV polarity, and swapped PV and battery connections, but will be 

damaged by reverse battery to the PV terminals. Transient voltage protection is provided, but steady state voltage in excess of 
30VDC on the battery or PV terminals will damage the unit. The unit is not water tight and must be installed in an area free from 
rain, snow or excessive moisture. Damage due to improper installation, corrosion, or adjustments or connections other than those 
shown in Figure 3 void the limited warranty. 

 

ELECTROSTATIC HANDLING PRECAUTIONS 

 

 

All electronic circuits may be damaged by static electricity. To minimize the likelihood of electrostatic damage, discharge yourself by touching a water faucet 

or other electrical ground prior to handling the 2000E and avoid touching components on the circuit board. The risk of electrostatic damage is highest when relative 
humidity is below 40%. 

 

 

 

 

Содержание SOLAR BOOST 2000E

Страница 1: ...G PHOTOVOLTAIC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODEL SB2000E SAVE THESE INSTRUCTIONS COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS 6 111 391 Blue Sky Energy Inc 2011 430 0012 H ...

Страница 2: ...lectrostatic Handling Precautions 5 Selecting PV Modules 6 Temperature Compensation 6 Battery and PV Wiring 6 Setting Charge Voltage 7 Maximum Power Voltage 7 Optimizing MPPT 7 TROUBLESHOOTING GUIDE 8 SPECIFICATIONS 9 FIVE YEAR LIMITED WARRANTY 9 TABLES AND FIGURES Table 1 Charge Status Indicator 3 Table 2 Maximum Conductor Length 3 Voltage Drop 7 Figure 1 Front Panel and Remote Display Indicators...

Страница 3: ...ry or other electrical part that may cause explosion i Remove personal metal items such as rings bracelets and watches when working with a lead acid battery A lead acid battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION...

Страница 4: ...ghly accurate displayed voltage may be somewhat higher than actual battery terminal voltage when high charge current is being delivered to the battery This is due to voltage drop in the wires between the 2000E and battery Error during charge can be minimized by using large low resistance wiring The 2000E operates on battery power not PV power A battery must be connected with a minimum voltage of 9...

Страница 5: ... should always plan and monitor the process Equalization is essentially a controlled over charge and should only be performed on vented liquid electrolyte lead acid batteries Repeated charge discharge cycles can lead to an imbalance in the specific gravity and state of charge of individual battery cells Equalization brings all battery cells up to the same specific gravity and eliminates electrolyt...

Страница 6: ...0 with a discharged battery in near freezing temperatures For a more complete MPPT description see www blueskyenergyinc com INSTALLATION WARNING Read understand and follow the Important Safety Instructions in the beginning of this manual before proceeding This unit must be installed and wired in accordance with National Electrical Code ANSI NFPA 70 Over current protection must be provided external...

Страница 7: ...s recommendation Most 12 volt flooded or GEL lead acid chemistry batteries require the 30 0 millivolts C 5 00mV C cell setting NiCd and many lead acid chemistry AGM type batteries require the 20 0 millivolts C 3 33mV C cell setting WARNING Do not attach a sensor or any connections other than Blue Sky Energy battery temperature sensor p n 930 0022 20 to the temperature sensor terminals Be certain t...

Страница 8: ... be eliminating the need to have the battery be highly charged To access this and other technical bulletins see www blueskyenergyinc com MAXIMUM POWER VOLTAGE The nominal setting for this adjustment is the difference between the PV panel s open circuit voltage VOC and maximum power voltage VMP These voltage values are typically listed on both the PV panel datasheet and on the rating label affixed ...

Страница 9: ...cause battery voltage is at setpoint relays may switch on off This normal and will cause no harm The on off symptom will go away with a slight increase or decrease in battery voltage or load current PV BAT must not connect together external to controller for proper operation Relays click on off rapidly Dip switch 2 off Double check dip switch 2 must always be on Used for factory test only Charge s...

Страница 10: ...ct of God f operation or installation contrary to instructions pertaining to the product or g cosmetic aging 4 If BSE s examination of the product determines that the product is not defective the consumer shall be charged a test and evaluation fee of 20 and be responsible for all transportation costs and insurance related to returning the product to the consumer The consumer is ultimately responsi...

Страница 11: ...Blue Sky Energy Solar Boost 2000E MOUNTING TEMPLATE Figure 4 ...

Отзывы: