Blue Sky Energy - Solar Boost 2000E 

 

 

PRODUCT DESCRIPTION 

 

 

Solar Boost™ 2000E is a 25 amp 12 volt Maximum Power Point Tracking (MPPT) photovoltaic (PV) battery charge controller with built in digital 

display. Through the use of patented MPPT technology the 2000E can increase charge current up to 30% or more compared to conventional controllers. The 
2000E’s sophisticated charge control system improves battery performance and life while minimizing battery maintenance. The unit is fully protected against 
voltage transients, over temperature, over current, reverse battery and reverse PV connections. An automatic current limit feature allows use of the full 25 
amp capability without worrying about overload or nuisance fuse blow from excessive current. An environmentally sealed high current high reliability relay is 
used to disconnect the PV array at night to prevent unwanted current drain.  

 

PART NUMBERS AND OPTIONS 

 

 SB2000E  ............ Solar Boost 2000E charge controller 

 930-0022-20  ....... Optional battery temperature sensor 

 720-0011-01  ....... Optional wall mount box, black powder coated steel 

 
 

OPERATION 

 

 

Charge control and MPPT current boost operations are fully automatic. Charge turns on whenever the PV array is capable of producing approximately 

0.15 amps at @ 14 volts. Note that there must be a battery in the system with a minimum voltage of 9 volts or greater for the 2000E to operate. Electronic 
current limit prevents the possibility of overload by limiting output current to 25 amps regardless of available PV input current or input power.  

 

 

The highly accurate digital display consumes very little power and is always on and available for use. As shown in Figure 1, the display can be 

selected to show Solar Panel Current, Output Charge Current or Battery Voltage. Solar Panel Current displays current in amps flowing from the PV array to 
the 2000E, whereas Output Charge Current displays current in amps flowing from the 2000E to the battery. When MPPT current boost is functioning, Output 
Charge Current will be greater than Solar Panel Current. If operating conditions are such extra power is not available from the PV array and MPPT current 
boost is unable to operate, Output Charge Current may show 0.1 amps less than Solar Panel Current. This is normal as the 2000E consumes approximately 
0.090 amps to operate when PV charge is on. When PV charge is off, standby current consumption is quite low at approximately 0.017 amps. 

 

 

Battery Voltage is measured at the 2000E’s battery terminals. Although the measurement system is highly accurate, displayed voltage may be 

somewhat higher than actual battery terminal voltage when high charge current is being delivered to the battery. This is due to voltage drop in the wires 
between the 2000E and battery. Error during charge can be minimized by using large low resistance wiring. 
 

¾

 The 2000E operates on battery power, not PV power. A battery must be connected with a minimum voltage of 9 volts for the unit 

to operate.  

 

 

CHARGE CONTROL 

 

The 2000E provides a two stage charging process, Bulk and Constant Voltage. A third manually actuated Equalize mode is also available. The 2000E  

will be in Bulk charge when battery voltage is below the charge voltage setpoint (factory set to 14.0 volts). During Bulk the 2000E delivers as much charge current 
as possible to rapidly recharge the battery and drive battery voltage up to the charge voltage setpoint. Once the battery recovers sufficient charge for battery 
voltage to rise to the charge voltage setpoint, both PV current and output charge current are reduced as necessary to control battery voltage at the charge voltage 
setpoint. 

 

CHARGE STATUS INDICATOR 

 

 

A Charge Status indicator LED is provided on the 2000E panel. For small scale solar electric systems an excellent indication of a highly charged battery is 

when the 2000E is able to hold the battery at the desired charge voltage setpoint. These systems usually consist of 75 – 400 watts of PV power, and charge a 
battery bank in the range of perhaps 100 – 600 amp-hours. With sufficient PV power and the battery under light load so that there is at least 2 amps of net charge 
current per 100 amp-hours of battery capacity, the system will show the battery to be charged when the battery is greater than approximately 90 – 95% full. When 
the Charge Status LED blinks showing the 2000E to be in the constant voltage mode, the battery is considered charged. 

 

 

If PV power generation is too low and/or load current is too high for there to be at least 2 amps of net charge current available per 100 amp-hours of battery 

capacity the Solar Boost 2000E may be unable to hold battery voltage at the desired charge voltage setpoint. This will cause a discharged condition to be 
displayed even though the battery may be highly charged. A charged condition will again be displayed if sufficient net charge current becomes available and the 
battery is indeed charged. A smaller battery and/or larger PV array will tend to show a charged condition sooner.  

 

CHARGE STATUS INDICATOR 

 

CHARGE STATUS INDICATOR 

CHARGE MODE 

APPROXIMATE CHARGE LEVEL 

OFF CHARGE 

OFF 

 

CONTINUOUSLY ON 

BULK 

LESS THAN 90% FULL 

BLINKING  

 2 SEC ON / 2 SEC OFF 

CONSTANT VOLTAGE 

GREATER THAN 90% FULL 

RAPID BLINKING  

  0.2 SEC ON / 0.2 SEC OFF 

EQUALIZE 

 

 

TABLE 1 

)

 

Содержание SOLAR BOOST 2000E

Страница 1: ...G PHOTOVOLTAIC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODEL SB2000E SAVE THESE INSTRUCTIONS COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS 6 111 391 Blue Sky Energy Inc 2011 430 0012 H ...

Страница 2: ...lectrostatic Handling Precautions 5 Selecting PV Modules 6 Temperature Compensation 6 Battery and PV Wiring 6 Setting Charge Voltage 7 Maximum Power Voltage 7 Optimizing MPPT 7 TROUBLESHOOTING GUIDE 8 SPECIFICATIONS 9 FIVE YEAR LIMITED WARRANTY 9 TABLES AND FIGURES Table 1 Charge Status Indicator 3 Table 2 Maximum Conductor Length 3 Voltage Drop 7 Figure 1 Front Panel and Remote Display Indicators...

Страница 3: ...ry or other electrical part that may cause explosion i Remove personal metal items such as rings bracelets and watches when working with a lead acid battery A lead acid battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION...

Страница 4: ...ghly accurate displayed voltage may be somewhat higher than actual battery terminal voltage when high charge current is being delivered to the battery This is due to voltage drop in the wires between the 2000E and battery Error during charge can be minimized by using large low resistance wiring The 2000E operates on battery power not PV power A battery must be connected with a minimum voltage of 9...

Страница 5: ... should always plan and monitor the process Equalization is essentially a controlled over charge and should only be performed on vented liquid electrolyte lead acid batteries Repeated charge discharge cycles can lead to an imbalance in the specific gravity and state of charge of individual battery cells Equalization brings all battery cells up to the same specific gravity and eliminates electrolyt...

Страница 6: ...0 with a discharged battery in near freezing temperatures For a more complete MPPT description see www blueskyenergyinc com INSTALLATION WARNING Read understand and follow the Important Safety Instructions in the beginning of this manual before proceeding This unit must be installed and wired in accordance with National Electrical Code ANSI NFPA 70 Over current protection must be provided external...

Страница 7: ...s recommendation Most 12 volt flooded or GEL lead acid chemistry batteries require the 30 0 millivolts C 5 00mV C cell setting NiCd and many lead acid chemistry AGM type batteries require the 20 0 millivolts C 3 33mV C cell setting WARNING Do not attach a sensor or any connections other than Blue Sky Energy battery temperature sensor p n 930 0022 20 to the temperature sensor terminals Be certain t...

Страница 8: ... be eliminating the need to have the battery be highly charged To access this and other technical bulletins see www blueskyenergyinc com MAXIMUM POWER VOLTAGE The nominal setting for this adjustment is the difference between the PV panel s open circuit voltage VOC and maximum power voltage VMP These voltage values are typically listed on both the PV panel datasheet and on the rating label affixed ...

Страница 9: ...cause battery voltage is at setpoint relays may switch on off This normal and will cause no harm The on off symptom will go away with a slight increase or decrease in battery voltage or load current PV BAT must not connect together external to controller for proper operation Relays click on off rapidly Dip switch 2 off Double check dip switch 2 must always be on Used for factory test only Charge s...

Страница 10: ...ct of God f operation or installation contrary to instructions pertaining to the product or g cosmetic aging 4 If BSE s examination of the product determines that the product is not defective the consumer shall be charged a test and evaluation fee of 20 and be responsible for all transportation costs and insurance related to returning the product to the consumer The consumer is ultimately responsi...

Страница 11: ...Blue Sky Energy Solar Boost 2000E MOUNTING TEMPLATE Figure 4 ...

Отзывы: