Blue Sea Systems P12 7531 Скачать руководство пользователя страница 7

Specifications are subject to change. See bluesea.com/P12 for current information.

Specifications

5

*  Consult battery manufacturer specifications for other battery types to avoid damage. Do not mix battery types. 
** Battery bank sizes are tested to California Energy Commission compliance (CEC). Larger and smaller size banks could charge well, but consume slightly 
  more power over the charging cycle. 

Regulatory

Designed and constructed for compliance to UL-1236 Marine, CSA 22.2 No. 107.2, and ABYC A-31 standards. 
CE Marked
Ignition Protection per ISO 8846 and SAE J1171. Meets FCC Part 15, Class B requirements. To view all regulatory specifications visit www.bluesea.com/P12.
California Energy Commission (CEC) compliant. The energy saving feature may be disabled by the user following the steps on page 14 of this manual.

7531

7532

Total Output Current (continuous)

25A

40A

Input AC Current

4.5A @ 115V AC / 2.25A @ 230V AC

7.5A @ 115V AC / 3.75A @ 230V AC

Nominal Output Voltage

12V DC

12V DC

Output Connections

3 positive, 1 negative

3 positive, 1 negative

Universal AC Input Voltage

115–230V AC

115–230V AC

Input Frequency Range

50–60 Hz

50–60 Hz

Typical Float Voltage

13.5V DC

13.5V DC

Output Voltage Accuracy

0.05V DC

0.05V DC

Minimum Operating Temperature

−20°C (−4°F)

−20°C (−4°F)

Full Output Maximum Temperature

45°C (113°F)

45°C (113°F)

Minimum Storage Temperature

−30°C (−22°F)

−30°C (−22°F)

Maximum Storage Temperature

80°C (176°F)

80°C (176°F)

Warranty

5 Year

5 Year

Battery Types*

Flooded, Gel, AGM, TPPL 

(Thin Plate Pure Lead)

Flooded, Gel, AGM, TPPL 

(Thin Plate Pure Lead)

Recommended for Battery Bank Sizes**

60Ah Minimum, 

Example: 1 x Group 24

330Ah Maximum, 

Example: 3 x Group 31

60Ah Minimum, 

Example: 1 x Group 24

440Ah Maximum, 

Example: 4 x Group 31

Conductor Length in feet (meters)

Charger Rating

25A

40A

6 ft (1.83 meters)

14 AWG (2.5mm²)

8 AWG (10mm²)

10 ft (3.05 meters)

12 AWG (4mm²)

8 AWG (10mm²)

15 ft (4.57 meters)

10 AWG (6mm²)

6 AWG (16mm²)

20 ft (6.09 meters)

8 AWG (10mm²)

6 AWG (16mm²)

25 ft (7.62 meters)

6 AWG (16mm²)

4 AWG (25mm²)

Recommended Battery Fuse

30A

60A

Region

Line

Neutral

Ground (Earth)

North America

Black

White

Green

Europe

Brown

Blue

Green-Yellow

Australia/ New Zealand

Brown or Red

Blue or Black

Green-Yellow

Table A: 

Minimum Recommended Wire Size*

Appropriate Fuses and Fuse Holders

Charger Rating

Fuse Type

Fuse Holder

25A

40A

MRBF Terminal Fuses

5191 Terminal Fuse Block

5175 (30A Fuse)

5178 (60A Fuse)

AMI®/MIDI® Fuses

7720 Safety Fuse Block

5250 (30A Fuse)

5253 (60A Fuse)

Table B: 

Recommended DC Circuit Protection

Table C: 

Typical AC Regional Wire Colors

Table D: 

AC Wire - Circuit Protection Selection Chart

7531

 (25A)

7532 

(40A)

Input Watts

450

750

120V AC Application

4.5A @ 100V AC

7.5A @ 100V AC

Minimum AC Wire Size

18 AWG (0.75mm²)

16 AWG (1.5mm²)

Circuit Breaker

10A

15A

230V AC Application*

2.25A @ 200V AC

3.75A @ 200V AC

Minimum Wire Size

18 AWG (0.75mm²)

18 AWG (0.75mm²)

Circuit Breaker

5A – 10A

5A – 10A

Typical of Europe

Type

Absorb Volts

Float Volts

FLA – Flooded Lead Acid

14.5V

13.5V

AGM – Absorbed Glass Mat

14.35V

13.3V   

Gel – Gelled Electrolyte

14.1V

13.5V

TPPL – Thin Plate Pure Lead

14.7V

13.6V

¹

User Adjustable

12.5V 

Default

12.5V 

Default

¹

 Taken from Odyssey Tech Notes, Northstar operation Manual

Table E: 

Default Voltages by Battery Type

Batteries should match in chemistry, although many AGM’s and flooded batteries are 
compatible. Based on 25°C (77°F)

*

 Based on 3% voltage drop.  If fast charge recovery is important, use larger wire.  Double the conductor 

   length entry to get a 1.5% drop, triple the conductor length to get a 1% voltage drop.

P12

 7531 AND 7532 BATTERY CHARGERS

Содержание P12 7531

Страница 1: ...perational instructions for P12 Battery Chargers This User Manual describes the product mentioned herein at the time of its publication Specifications and performance are subject to change at the disc...

Страница 2: ...roduct Dimensions and Installation Clearances 6 Included Components 7 Supplies Needed 8 Installation Instructions 9 10 Initial Charger Setup 11 Advanced Charger Setup 12 13 Reset to Manufacturer Defau...

Страница 3: ...to property Never charge a frozen battery GROUNDING PRECAUTIONS Marine battery chargers and inverters have two grounding connections one from the AC system and one from the DC system ABYC requires th...

Страница 4: ...as not to cause an arc b Be sure area around battery is well ventilated while battery is being charged c Clean battery terminals Be careful to keep corrosion from coming in contact with eyes d Add dis...

Страница 5: ...tion charging stage the batteries complete their charging by being topped off This is a less aggressive charging stage than Bulk where the current going into a particular battery bank will significant...

Страница 6: ...Charging and Alert indicators Graphic LCD Display Termination insulating cover DC output DC strain relief clamp AC strain relief and insulating cover AC input terminals under cover Mounting holes Clea...

Страница 7: ...Example 1 x Group 24 440Ah Maximum Example 4 x Group 31 Conductor Length in feet meters Charger Rating 25A 40A 6 ft 1 83 meters 14 AWG 2 5mm 8 AWG 10mm 10 ft 3 05 meters 12 AWG 4mm 8 AWG 10mm 15 ft 4...

Страница 8: ...D 7532 BATTERY CHARGERS Clearance for 12 1 4 M6 mounting hardware 7 80 198mm 11 18 284mm 7 40 188mm 8 46 215mm 4 30 109 1mm 12 94 328 8mm 14 20 TOP Recommended side clearance 1 97 50mm Recommended ove...

Страница 9: ...ded torque 5 10 in lb 0 6 1 1 Nm Pan Head Machine Screws M3 5 x 6mm Recommended torque 10 15 in lb 1 0 1 8 Nm DC Strain Relief Clamp Screws M3 x 25mm pan head machine screws Recommended torque 5 10 in...

Страница 10: ...uses or circuit breakers to verify like new condition Confirm no discoloration or corrosion exists and circuit breakers will manually trip and reset Check for proper ventilation and that no debris has...

Страница 11: ...and the battery negative common bus bar Fuses should be installed at the battery positive connections to prevent battery power from feeding back into a fault in the wiring or in the battery charger Se...

Страница 12: ...P12 Battery Charger Remote using dielectric grease Connect to the Remote Display Com port of the charger 2 Connect the Automatic Charging Relay s ACR wire to the ACR Connection port s Optional Install...

Страница 13: ...elect button 4 Once the desired battery type is highlighted press the OK button Press the Cancel button to go back Note If User mode is selected batteries will not charge until Absorb and Float voltag...

Страница 14: ...maximum amperage is the total available amperage to be supplied among all 3 outputs Selecting an amperage less than the maximum could result in under charging of batteries 5 Press the OK button once...

Страница 15: ...lected battery type The default Absorb voltages for each battery type can be seen in Table E above Warning Incorrect Absorb and Float voltages could reduce the life of your batteries Contact your batt...

Страница 16: ...Absorption Amps The maximum amount of current that a battery bank can receive while in Absorption and still change to Float If a load is active and drawing more than the designated End Absorption Amp...

Страница 17: ...rger will increase all output voltages by the value defined in Battery Tempco For example with the default Battery Tempco set to 30mv C if the temperature sensor reads 26 C then all output voltages wi...

Страница 18: ...eries are fully charged by verifying the charger is in Float mode with no active loads 2 Turn off or disconnect all DC devices that are connected to the batteries Disconnect the battery banks not bein...

Страница 19: ...You may pause Equalization at any time by pressing the pause button 17 If at any point during Equalization a DC load is applied to the battery being equalized Equalization will stop 18 You may stop Eq...

Страница 20: ...o Get Here From the Charger Summary Screen select the Menu button From other screens select the Back button Display Setup The Display Setup allows the user to customize the display settings Options Ad...

Страница 21: ...if time is being added or subtracted from the timer If paused the charger is in Float or Standby and the Absorb Timer will remain at its current time Read about Absorb Timers on page 14 Options Selec...

Страница 22: ...ee if the Fan Alert Screen appears If the Fan Alert Screen does not appear and the fan seems to be operating correctly then continue to use the battery charger normally If the Fan Alert Screen appears...

Страница 23: ...use a different AC power source or contact an electrician to diagnose the problem AC Input Voltage Too High If the input voltage rises above 265V AC the alert screen on the right will appear In this s...

Страница 24: ...present in order to share charge between battery banks However due to the P12 Battery Charger s ability to independently optimize charging for each battery bank it is favorable to isolate all battery...

Страница 25: ...or wire running from the start key switch to the starter solenoid NOTE Connecting the SI Start Isolation wire to only one of the ML ACR isolation wires will not properly integrate the P12 battery char...

Страница 26: ...he product was purchased by the first retail customer 2 The date on which the first retail customer purchases a vessel on which the product was installed Blue Sea Systems will at its sole discretion r...

Страница 27: ...oltage and Frequency measurement with alarms 2 AC ELCI Ground Fault Protection 3 AC Source Selection 4 AC Branch Circuit Protection and Switching 5 DC Battery Charger Remote Monitoring and Control 6 D...

Страница 28: ...425 Sequoia Drive Bellingham WA 98226 USA p 360 738 8230 p 800 222 7617 USA and Canada Customer Service conductor bluesea com www bluesea com 980025140 Rev 005...

Страница 29: ...ilisation des chargeurs de batterie P12 Ce manuel d utilisation d crit le produit mentionn dans ce document au moment de sa publication Les sp cifications et les performances sont sujettes modificatio...

Страница 30: ...nsions du produit et d gagements pour l installation 6 Composants inclus 7 Fournitures n cessaires 8 Instructions d installation 9 10 Configuration initiale du chargeur 11 Configuration avanc e du cha...

Страница 31: ...rels et mat riels Ne chargez jamais une batterie gel e PR CAUTION DE MISE LA MASSE Les chargeurs de batteries marines et les inverseurs ont deux raccords de mise la masse un provenant du circuit c a e...

Страница 32: ...ension pour ne pas causer un arc b S assurer que la zone autour de la batterie est bien a r e pendant la charge de la batterie c Nettoyer les bornes de la batterie Faire attention pour viter tout cont...

Страница 33: ...ion constante Dans la phase de charge d absorption les batteries effectuent leur charge en tant remplies Cette phase de charge est moins agressive que la phase Bulk charge initiale dans laquelle le co...

Страница 34: ...dicateurs de charge et d alerte Afficheur LCD graphique Couvercle isolant de connexion de sortie Sortie c c trier anti traction c c Dispositif anti traction c a et couvercle isolant Bornes d entr es c...

Страница 35: ...x groupe 24 440 Ah maximum Exemple 4 x groupe 31 Longueur de conducteur en pieds m tres Puissance du chargeur 25A 40A 6 pi 1 83 m 14 AWG 2 5 mm 8 AWG 10 mm 10 pi 3 05 m 12 AWG 4 mm 8 AWG 10 mm 15 pi...

Страница 36: ...llation P12 CHARGEURS DE BATTERIE 7531 ET 7532 D gagement pour fixations n 12 1 4 M6 7 80 198mm 11 18 284mm 7 40 188mm 8 46 215mm 4 30 109 1mm 12 94 328 8mm 14 20 Sup rieur D gagement sup rieur recomm...

Страница 37: ...10 in lb 0 6 1 1 Nm Vis m canique t te cylindrique M3 5 x 6 mm Couple recommand 10 15 in lb 1 0 1 8 Nm Vis d trier anti traction c c Vis m caniques t te cylindrique M3 x 25 mm Couple recommand 5 10 in...

Страница 38: ...er que leur tat est comme neuf V rifiez l absence de d coloration ou de corrosion et v rifiez le d clenchement et le r armement manuel des disjoncteurs V rifiez l a ration correcte et assurez vous qu...

Страница 39: ...f de la batterie et du n gatif de la batterie Les fusibles doivent tre install s au niveau des bornes positives de la batterie pour viter l alimentation de la batterie de provoquer un d faut dans le c...

Страница 40: ...batterie l arri re de la t l commande du chargeur de batterie en utilisant de la graisse di lectrique Branchez le l orifice Remote Display Com du chargeur 2 Branchez le c ble du des relais de charge a...

Страница 41: ...elect 4 Une fois le type de batterie d sir mis en vidence appuyez sur le bouton OK Appuyez sur le bouton Cancel pour revenir en arri re Note Si le mode Utilisateur est s lectionn les batteries ne se c...

Страница 42: ...tale disponible qui doit tre fournie entre les 3 sorties La s lection d une intensit inf rieure au maximum peut entra ner une charge insuffisante des batteries 5 Appuyez sur le bouton OK une fois que...

Страница 43: ...absorption par d faut pour chaque type de batterie peuvent tre v rifi es dans le Tableau E ci dessus Avertissement Des tensions d absorption et d entretien incorrectes peuvent r duire la dur e de vie...

Страница 44: ...um de courant qu un groupe de batteries peut recevoir pendant la phase d absorption en passant quand m me en phase Float Si une charge est active et absorbe plus que l intensit de fin d absorption pre...

Страница 45: ...dans Compensation de temp rature de batterie Par exemple quand la compensation de temp rature de batterie par d faut est r gl e sur 30 mv C si le capteur de temp rature rel ve 26 C toutes les tension...

Страница 46: ...n v rifiant que le chargeur est en phase Float entretien sans aucune charge active 2 D sactivez ou d branchez tous les dispositifs c c qui sont branch s aux batteries D branchez les groupes de batteri...

Страница 47: ...dure d galisation 16 Vous pouvez interrompre l galisation tout moment en appuyant sur le bouton pause 17 Si tout moment pendant l galisation une charge c c est appliqu e la batterie en cours d galisat...

Страница 48: ...rger Summary s lectionnez le bouton Menu partir d autres crans s lectionnez le bouton Back Configuration de l affichage L cran Display Setup permet l utilisateur de personnaliser les param tres d affi...

Страница 49: ...t e ou soustraite du temporisateur S il est sur pause le chargeur est en mode Float ou Standby et le temporisateur d absorption reste sa dur e actuelle Les temporisateurs d absorption sont d crits la...

Страница 50: ...alerte de ventilateur s affiche Si l cran d alerte de ventilateur ne s affiche pas et que le ventilateur semble fonctionner correctement continuez utiliser le chargeur de batterie normalement Si l cra...

Страница 51: ...entation c a diff rente ou contactez un lectricien pour diagnostiquer le probl me Tension d entr e c a trop lev e Si la tension d entr e augmente au del de 265 Vc a l cran d alerte sur la droite s aff...

Страница 52: ...dant en raison de la capacit du chargeur de batterie P12 d optimiser la charge ind pendamment pour chaque groupe de batteries il est utile d isoler tous les groupes de batteries en d sactivant la capa...

Страница 53: ...de d marreur NOTE Le branchement du fil SI isolement au d marrage un seul des c bles d isolement ML ACR ne permet pas l int gration correcte du chargeur de batterie P12 avec le ML ACR 3 Branchez un c...

Страница 54: ...gnifie 1 La date laquelle le produit a t achet par le premier client au d tail 2 La date laquelle le premier client au d tail ach te un bateau sur lequel le produit a t install Blue Sea Systems sa seu...

Страница 55: ...nsit c a de tension et de fr quence avec alarmes 2 Protection de d faut la masse c a ELCI 3 S lection de source c a 4 Protection et commutation de circuit c c 5 Contr le et commande distance de charge...

Страница 56: ...425 Sequoia Drive Bellingham WA 98226 USA T l 360 738 8230 T l 800 222 7617 Service client tats Unis et Canada conductor bluesea com www bluesea com 980025140 R v 005...

Отзывы: