background image

12

Full Chrg Amps 

In addition to Voltage, the user can set the Charging Current at which the battery is considered fully charged. The value is a percentage between 0.0 % 
and 10.0 % of the battery’s set Amp-hour capacity. This value should be set to 0.2% higher than the End of Absorption Amps. That is the current where 
the battery charger switches from Absorb to Float stage. Values are typically 2% for AGM and 3% for Lead Acid. As a battery ages, this percentage may 
need to be increased. This is automatically set by CZone.

Charge Eff.  

This setting is for indicating the battery’s percent charge efficiency. The value may be set between 0% and 100%. The user can adjust the charge 
efficiency up or down depending on the age and/or type of battery that they are using. AGM Batteries tend to be much more efficient than Lead Acid 
Batteries. If the M2 meter indicates 100% before the charger is done with its bulk charge then the efficiency is likely too high. Try decreasing it a couple 
percent. If the M2 meter never indicates full charge then efficiency is likely too low. Try increasing it a couple percent. This is automatically  
set by CZone.

The charge efficiency can be calculated as follows:
1.  Set the 

Charge Eff

. Value to 100%.

2.  Discharge the battery somewhere between 25% to 50%.
3.  Check the SoC summary screen and note the 

Ah Used

 value (it will be a negative number). This is

 Discharge Amps

.

4.  Charge the battery using a 3-stage charger.
5.  When the charger goes from Absorption to Bulk, the battery is considered fully charged.
6.  Check the SoC screen again and note the 

Ah Used

 (it will be a positive number). This is 

Charge Amps

.

7.  The new Charge Efficiency value is calculated by 

Discharge Amps/Charge Amps

.

8.  Set the 

Charge Eff

. value to the value above

For example, if we had a 100 Ah battery, we would remove 50 Ah at roughly C/20 (5 Amps for 10 hours). We would then charge the battery and when we 

transition to float, we might see 4 

Ah Used

. So the charge efficiency would be 50/(50 + 4) or 92.5% efficiency.

Temperature

Specify the lowest temperature that the batteries will be exposed to. As temperature drops, the effective capacity of batteries also drops. 

The M2 calculates the battery capacity based on this worst case temperature. This number could be adjusted seasonally to provide better accuracy

SoC Volt. Sync

This setting allow the M2 to estimate the current State-of-Charge after the battery has rested for a period of time. In certain situations where small 
charges are affecting the voltage reading (some solar installations would do this), the synchronization will estimate the SOC incorrectly. In that case, turn 
this feature off.

Shunt Value 

The M2 is shipped with a single 500A/50mV shunt (the ratio is 10000:1). The shunt value assumes that the full scale shunt output voltage is 50 mV. To 
use a shunt with a smaller output voltage use the following formula:  Shunt Value = (New Shunt Ratio) / 20. For example to use a 400A/20mV shunt 
(Note: 20mV = 0.02V), you would set Shunt Value to (400A/0.02) /20 = 1000A. 

Zero Shunt 

Menu->Setup->DC1 Setup->Zero Shunt

. To zero out the shunt, connect both of the current sense wires to the negative bus bar side of the shunt. 

Then press the 

Reset

 button on the M2 Meter to confirm the action. 

State-of-Charge (SoC) Cycles 

Menu->Setup->DC1 Setup->SoC Cycles

. The SoC Cycles option allows the user to reset the battery’s recorded SoC cycles to 0. To do this, scroll to 

and press 

Select 

on SoC Cycles. Text will appear asking to confirm or cancel the reset request. Press 

Yes

 to confirm or 

No 

to cancel the action. 

State-of-Charge (SoC) Default Settings 

To reset the battery’s State-of-Charge settings to the default values, press 

Select

 on SoC Defaults. Text will then appear asking to confirm or cancel the 

reset request. Press 

Yes

 to confirm or

 No

 to cancel. The following changes will occur after a reset: 

1. SoC Cycles will be reset to 0 
2. SoC is Reset to 98% 

Содержание M2 Vessel Systems Monitor

Страница 1: ...Activation High and Low Voltage Current and Frequency Frequency Range 40Hz 90Hz Resolution 1Hz Power Range 0W 45kW Resolution 0W 9990W 10W Resolution 10kW 45kW 0 1kW Tanks Alarm High Low Levels Sender...

Страница 2: ...If an inverter is installed on the vessel its power leads must be disconnected at the battery before the meter is installed If an AC generator is installed on the vessel it must be stopped and render...

Страница 3: ...ount Bezel and Seal Mounting Ring and Nut Surface Mount Gasket Surface Mount Cover NOTE During installation use cover to align the bezel and gasket Flat Mount Surface Mount 360 Panel Mount PN 1525 Mou...

Страница 4: ...d 2 DC Pos connected These pins are used to provide power to the meter Connect pin 1 to ground and pin 2 to a 12V to 48V power source Pin 2 is also used to monitor the voltages on bank 2 The current d...

Страница 5: ...wisted to reduce the effects of interference from other electrical circuits AC Voltage The AC supply HOT Line or Ungrounded Conductor connection should be protected with a fast acting fuse of 0 25A to...

Страница 6: ...button beneath it The pop up menu will disappear after the first button is pressed 6 The menu system is a two dimensional matrix Pressing the UP or DOWN arrow buttons will transition the display betw...

Страница 7: ...ff exclusive of delays If no alarm is set this is the estimated time until the battery is completely empty Ah Remain Estimated remaining capacity of the battery Ah Used This is the actual Ah removed f...

Страница 8: ...to cancel any change NOTE A low voltage threshold cannot be set above a high voltage threshold Likewise a high voltage threshold cannot be set below the low voltage threshold The meter will automatica...

Страница 9: ...es the delay time When it reaches the delay timer an alarm will sound If the alarm condition goes away before the delay timer has been met the timer will count down until the timer is zero again For e...

Страница 10: ...either Imprl imperial or Mtrc metric These are the units used to specify the battery temperature and fluid volume Demo Mode With Demo Mode ON the meter displays factory programmed values for the Batt...

Страница 11: ...Batteries FLRsv Flooded Acid Reserve Premium Flooded Lead Acid Batteries such as Rolls FLLoM Flooded Low Maintenance Sealed Flooded Lead Acid Batteries FFFL Firefly AGM Batteries Bat Capacity This set...

Страница 12: ...or 10 hours We would then charge the battery and when we transition to float we might see 4 Ah Used So the charge efficiency would be 50 50 4 or 92 5 efficiency Temperature Specify the lowest temperat...

Страница 13: ...ngs first go to the Setup menu Scroll to the desired input The tank setup settings are described below To make a change scroll to setting and press Enter Press the LEFT or RIGHT buttons to view the av...

Страница 14: ...ank If the tank cannot be completely emptied the estimation works best if the tank is emptied with the sensor reading under 20 2 Set the tanks shape to Rect Rectangular 3 Set the tank to display perce...

Страница 15: ...te 5 The timer will start counting as the tank fills In addition the sender will indicate that the tank is getting filled When the tank reaches 100 the timer will automatically stop Press the Finish b...

Страница 16: ...nsport Protocol Connection Management 60928 ISO Address Claim 65240 ISO Commanded Address 126208 Request Group Function 126993 Heartbeat CZone Proprietary PGN s 65280 PGN_ZONE_COMMAND_MESSAGE Circuits...

Страница 17: ...USB micro cable into the back of the meter 6 While holding the 2nd button from the left connect the USB cable to a PC or a MAC b On a MAC 7 The computer will create a new drive on the computer Note I...

Страница 18: ...hould power up and you can navigate to Setup Version Info to verify the new SW Revision 4600 Ryzex Way Bellingham WA 98226 USA p 360 738 8230 f 360 734 4195 conductor bluesea com bluesea com 980033760...

Отзывы: