The ML-Series Remote Battery Switch provides high-current carrying and switching under load.
The Remote Battery Switch should be installed close to the battery banks to avoid voltage drop.
Install a single pole double throw (SPDT) or single pole single throw (SPST) control switch in a convenient
location near other electrical controls or companionway to allow quick access in the event of an emergency
(see Illustration on reverse).*
* Although a SPST switch may be used if desired, use of a SPDT switch improves immunity to inadvertent
switching if the controls become damp.
ML- RBS
Remote Battery Switches
PN 7712 / PN 7712B / PN 7712100B
PN 7714 / PN 7714B / PN 7714100B
980010060 Rev.004
• Magnetic Latch (ML) - draws very low current continuous and draws
moderate current for very short time when changing state
• Silver alloy contacts provide high reliability for switching live loads
• Manual override provides LOCK OFF capability for servicing and ON/OFF control with or without power
• LED output to remotely indicate switch state
• Tin-plated copper studs for maximum conductivity and corrosion resistance
• Label recesses for circuit identification
• PNs 7712 and 7714 include a Remote Control Switch PN 2155
Specifications
12V DC
24V DC
Cranking Rating
See table below
See table below
Intermittent Rating
See table below
See table below
Continuous Rating
See table below
See table below
ML-Coil Function
Auto releasing
Auto releasing
Operating Current: Continuous
<13mA@ 25
°
C nominal voltage <13mA @ 25
°
C nominal voltage
Changing Stage (20 ms) <7A@ 25
°
C nominal voltage
<4A @ 25
°
C nominal voltage
Contact Circuit Voltage
16V DC Max.
32V DC Max.
Live Current Switching
300A @ 12V DC—10,000 Cycles 150A @ 24V DC—10,000 Cycles
‡
Mechanical Endurance
100,000 Cycles
100,000 Cycles
Control Circuit Voltage
9
–
16V DC
18
–
32V DC
Terminal Stud Size
3/8
"
-16
3/8
"
-16
Maximum Terminal Stud Torque
140 in-lb (15.8 N•m)
140 in-lb (15.8 N•m)
Ring Terminal Size
3/8
"
(M10)
3/8
"
(M10)
Terminal Ring Diameter Clearance
1.18
"
(30 mm)
1.18
"
(30 mm)
‡
Predicted performance
Remote Switch PN 2155
Action
SPDT, ON-ON
Seals
Internal & External Gasket Panel Seal
Mounting Hole
0.83
"
x 1.45
"
(21.08 mm x 36.83 mm)
LED Rating
100,000 hours half-life
Harness Connector: (select models)
Deutsch DTM Series DTM 06-6S
Mating Part Requirements
See LADD Industries www.laddinc.com
Receptacle Shell
DTM-04-6P
Wedgelock
WM-6P
Terminal Pins
1060-20-0122
Sealing Plugs
0413-204-2005
Hand Crimp Tooling
DTT-20-0
Regulatory
Meets ISO 8846 and SAE J1171 external ignition protection requirements, CE marked, Rated IP66
Marine Electrical Products
PN
Termination
Control Circuit
Remote Control
Switch Included
7712
Tinned Wires
12V DC
SPDT, ON-ON
7712B
Tinned Wires
12V DC
-
7712100B
Deutsch Connector
12V DC
-
7714
Tinned Wires
24V DC
SPDT, ON-ON
7714B
Tinned Wires
24V DC
-
7714100B
Deutsch Connector
24V DC
-
Overview of Application
Wire Size (AWG)
Metric (mm²)
Cranking 10 sec.
Cranking 1 min. Intermittent 5 min. Continuous (UL 1107)
2/0
70
2,000A
750A
400A
225A
4/0
120
2,200A
750A
400A
300A
2x (4/0)
2x (120)
2,500A
1,100A
700A
500A
Remote LED Indicator embedded in PN 2155 SPDT ON-ON Contura Switch
indicates Remote Battery Switch state or condition as follows:
LED Indication
Remote Battery Switch State or Condition
LED is OFF
Remote Battery Switch is OFF
LED is ON
Remote Battery Switch is ON
LED double blinking ON-OFF
Manual override--check Remote Battery Switch for switch states.
OR Remote Battery Switch mechanical failure
To connect battery bank to load, or combine
battery banks
Set remote switch 2155 to position marked “ON”.
Remote LED indicates closed connection.
To disconnect battery bank from load, or
isolate battery banks that are connected
Set remote switch 2155 to position marked “OFF”.
The remote LED embedded in PN 2155 indicates a closed connection between battery bank and load, or
between two battery banks when used as an emergency cross-connect.
Remote Operation.
PN 2155 (SPDT, ON-ON) Remote Control Contura Switch in the ON position can either
connect the battery bank to the load or combine two battery banks. In the OFF position it can either
disconnect a battery bank from a load or isolate two batteries from each other.
Blue Sea Systems Inc.
p 360.738.8230
425 Sequoia Drive
f 360.734.4195
Bellingham, WA 98226 USA
www.bluesea.com
Remote
Switch
State
ON
OFF
Manual
Control
Knob
Position
Remote Operation Enabled
Remote
Disabled
Remote Operation Enabled
Remote
Disabled
ML-RBS
Relay State
ON
(Closed)
OFF
(Open)
OFF
(Open)
ON
(Closed)
OFF
(Open)
OFF
(Open)
ML-RBS Relay
State will change
to Remote
Switch State
after 10 minutes
-
ON
(Closed)
-
OFF
(Open)
-
-
ON
OFF
ML-RBS 7712 and 7714 Remote Operation Table
CAUTION
If the ML-RBS Relay state is changed using the Manual Control Knob to a state that is
different than the Remote Switch 2155, the relay state will automatically change to match the Remote Switch
state after 10 minutes. The two scenarios where this will occur are shaded in the table above.