7.3- Phase failure protection
When motor meet phase failure (Any of two phase over 25% of the rated current, another phase
less than 12.5% of the rated current), will trip the phase failure protection.
Protection mode
OFF / Alarm / Trip
Trip delay
0.1 ~ 50.0 s
7.4- Stall protection
Stall protection to prevent motor-driven equipment in serious operation block or motor overload
operation and heat damage to the motor,
Note
: Stall protection only be act after the motor starter is complete.
Protection mode
OFF / Alarm / Trip
Threshold
100 ~ 1000%Ie
Trip delay
0.5 ~ 50.0 s
7.5- Current imbalance protection
Current imbalance protection based on the maximum phase current imbalance to determine
whether to start phase unbalance protection function. Current unbalance is calculated as follows:
𝐈
𝐢𝐦
=
|𝐈
𝐦𝐚𝐱
−𝐈
𝐚𝐯𝐠
|
𝐈𝐚𝐯𝐠
𝐱 𝟏𝟎𝟎%
or
𝐈
𝐢𝐦
=
|𝐈
𝐦𝐚𝐱
− 𝐈
𝐚𝐯𝐠
|
𝐈𝐚𝐯𝐠
𝐱 𝟏𝟎𝟎%
I
im
-- Three-phase current imbalance;
I
max
-- Maximum phase current in the real-time measurement of three-phase;
I
min
-- Minimum phase current in the real-time measurement of three-phase;
I
avg
-- Three-phase average current.
Notes:
When the three-phase average current (I
avg
) is less than the motor rated current (
Ie
), in
formula
I
avg
= Ie
Protection mode
OFF / Alarm / Trip
Imbalance threshold
5 ~ 60 %
Trip delay
0.1~ 50.0 s