Copyright ©2022 SemaConnect, LLC. All rights reserved.
dwfwdfwfwfwfwffffgd
www.SemaConnect.com
System Requirements
General Requirements
SemaConnect EV charging stations require a solidly grounded electrical system with the presence of a main bonding jumper
or system bonding jumper. Ungrounded sources or impedance grounded sources of any type (resistor/reactor) are not
suitable for SemaConnect EV charging stations.
SemaConnect EV charging stations require 240 volt (phase to phase) or 208 volt (phase to phase) input with an equipment
grounding conductor. A grounded conductor (neutral conductor) is not required. All breakers must be non-GFCI breakers.
Anchoring detail is the responsibility of others. Anchoring must be capable of minimum weight and height in accordance with
the provided table. Any seismic, wind-loading and/or snow-loading considerations increasing weights or wind-profile of unit
will be the responsibility of others.
WEIGHT
(LBS)
HEIGHT
(INCHES)
SERIES 7 - 18' OUTPUT CABLES
36
20.5
SERIES 7 - 25' OUTPUT CABLES
41
20.5
SERIES 8 - 18' OUTPUT CABLES
36
24
SERIES 8 - 25' OUTPUT CABLES
41
24
SERIES 7+ - 18' OUTPUT CABLES
36
20.5
SERIES 7+ - 25' OUTPUT CABLES
41
20.5
SERIES 8+ - 18' OUTPUT CABLES
36
24
SERIES 8+ - 25' OUTPUT CABLES
41
24
SERIES 7, 7+, 8, 8+ PEDESTAL
7.7
37.4
SERIES 7, 7+, 8, 8+ Wall Mount Bracket
7.7
18.1
SERIES 7, 8 CABLE MANAGEMENT SYSTEM
75.5
70.6
SERIES 7+, 8+ 80 CABLE MANAGEMENT
SYSTEM
86.6
70.6