Via Montefeltro, 6 – 20156 Milano (MI) – Italy
- 8 -
Tel. +39 (02) 3088583 – Fax +39 (02) 33406697
www.blinkmarine.com
–
PKP-2200-SI_J1939_UM_REV1.0
11.
Get software revision (2Ah)
Byte 0
04h
Header bytes
Byte 1
1Bh
Byte 2
2Ah
Get software revision
Byte 3,7
FFh
Not used
Answer:
Byte 0
04h
Header bytes
Byte 1
1Bh
Byte 2
2Ah
Get software revision
Byte 3,6
XXh XXh XXh XXh
SW revision ASCII
Byte 7
00h
Not used
12.
Set startup LED show (34h)
Byte 0
04h
Header bytes
Byte 1
1Bh
Byte 2
34h
Startup LED show
Byte 3
XXh
XX:
00h OFF
01h Complete LED show
(default)
02h Fast flash
Byte 4,7
FFh
Not used
Example:
Direction
Identifier
Format Message
Data
To
Keypad
18EF2100h Ext
04 1B 34 00 FF FF FF
FF
Set Startup LED
show OFF
13.
Baud rate setting (6Fh)
This message is used to change the baud rate of the CAN bus. Connecting only one keypad to
the bus when changing the baud rate is recommended. If an invalid value is chosen, then no
change is done to the stored value.
Byte 0
04h
Header bytes
Byte 1
1Bh
Byte 2
6Fh
Set baud rate message
Byte 3
02h
500kbit/s
03h
250kbit/s
Byte 4,7
FFh
Not used
Example:
Example:
Direction
Identifier
Format Message
Data
To Keypad
18EF2100h Ext
04 1B 2A FF FF FF FF FF
Get software
revision
From Keypad
18EFFF21h Ext
04 1B 2A 56 32 2E 34 00 V2.4