INSTALLATION INSTRUCTIONS
Cont...
Vent Restrictor (P/N 1748)
Due to the extra flow produced by certain venting configurations a vent restrictor must
be placed in the vent to maintain performance. All top vent installations over 20'
require the use of a 60% restrictor. The restrictor is installed in the exhaust of the
appliance as shown in Figure's 4 & 5.
The rear vent configurations do not require a vent restrictor.
If a restrictor is necessary it can be installed in the following order:
1. Turn off the appliance and allow it to cool to room temperature.
2. Carefully remove the logs and brick panels and place them in a safe location.
3. Remove the firebox baffle (4 screws).
4. Install the vent restrictor in the exhaust (2 screws) as shown in Figure 5.
5. Install the firebox baffle.
6. Install the logs.
firebox baffle
Figure 4
restrictor
Figure 5
Содержание TORINO
Страница 6: ...The torino Page 6 APPLIANCE DIMENSIONS ...
Страница 24: ...The torino Page 24 WIRING DIAGRAMS INTERMITTENT PILOT VALVE Optional Wall thermostat interrupt green wire ...
Страница 25: ...The torino Page 25 WIRING DIAGRAM 120 V AC ...
Страница 26: ...The torino Page 26 LIGHTING INSTRUCTIONS Intermittent Pilot ...
Страница 27: ...The torino Page 27 HANDHELD THERMOSTAT REMOTE CONTROL operation instructions Fig 3 Receiver body ...
Страница 28: ...The torino Page 28 HANDHELD THERMOSTAT REMOTE CONTROL operation instructions ...
Страница 29: ...The torino Page 29 HANDHELD THERMOSTAT REMOTE CONTROL operation instructions ...
Страница 30: ...The torino Page 30 HANDHELD THERMOSTAT REMOTE CONTROL operation instructions ...
Страница 37: ...The torino Page 37 FUEL CONVERSION ...
Страница 47: ...The torino Page 47 ...
Страница 48: ...The torino Page 48 NOTES SERVICE HISTORY DATE CORRECTIVE ACTION INCLUDE REPLACEMENT PARTS ...