G:\InDATA\manuals\OM-1607 E V1.02
November 19, 2012
Page 34
TORINO II Insert 1607
TROUBLESHOOTING cont.
SYMPTOM
ACTION
Sooty deposits on the glass door.
1.
If the flame is yellow and lazy, check for lint etc. around primary
air shutter. Increase primary air by opening the primary air
shutter if necessary, see “SERVICING” on page 27.
2.
Check for proper placement of the logs and branches. Ensure
logs and burner are clean, see “INSTALLATION INSTRUCTIONS
cont.” on page 15.
3.
Check for proper venting and blockage of the vent termination.
4.
Check manifold pressure and clock input rating for over-firing.
Sharp blue flames with flames lifting off the
burner at the ends.
1.
Too much primary air. Reduce primary air by closing the primary
air shutter. During cold temperatures, some flame lifting may
occur during start-up, see “SERVICING” on page 27.
Convection blower does not turn on.
1.
The convection fan is thermostatically controlled. It will only turn
on when the appliance is warmed-up. This may take up to 5
minutes with the appliance on high.
2.
Check for 120VAC electrical supply to the appliance. (Is the cord
plugged in?)
3.
Check if speed controller is not in OFF position.
4.
Check electrical connections.
5.
Check for defective convection blower speed controller.
6.
Check for defective convection blower.
Содержание Torino II Insert 1607
Страница 19: ...G InDATA manuals OM 1607 E V1 02 November 19 2012 Page 19 TORINO II Insert1607 LIGHTING INSTRUCTIONS ...
Страница 30: ...G InDATA manuals OM 1607 E V1 02 November 19 2012 Page 30 TORINO II Insert 1607 FUEL CONVERSION cont ...
Страница 36: ...G InDATA manuals OM 1607 E V1 02 November 19 2012 Page 36 TORINO II Insert 1607 REPLACEMENT PARTS cont ...
Страница 41: ...G InDATA manuals OM 1607 E V1 02 November 19 2012 Page 41 TORINO II Insert1607 NOTES ...