11
Wiring diagram 2
Permanent fan operation with automatic humidity and movement control (SMART IR).
The contacts L and N are connected to live and zero of power mains and the contacts L
and LT are bridged with a jumper.
The fan runs permanently at low speed.
24 HOURS mode is not available.
After receipt of a signal from the motion sensor (for SMART IR model only) the fan turns to
QUIET mode. Some time after no movement is detected any more the fan reverts to the
previous mode.
After humidity level increase the fan turns to MAXIMAL mode (by default) or QUIET mode.
Some time following the humidity drop the fan reverts to the previous mode.
Wiring diagram 3
Automatic humidity and movement control (SMART IR), timer and external switch.
The contacts L and N are connected to live and zero of power mains and the contact LT
is connected to live through an external switch, for example, the lighting switch.
The fan is in SLEEP mode (does not run).
If 24 HOURS mode is activated the fan switches to permanent low speed mode to provide
minimum round-the-clock ventilation.
After receipt of a signal from the motion sensor (for SMART IR model only) the fan is turned
to QUIET mode. Some time after no movement is detected any more the fan reverts to the
previous mode.
After closing of the external sensor the fan is turned to QUIET mode. Some time after the
external switch is opened the fan reverts to the previous mode.
After humidity increase the fan turns to MAXIMAL (by default) or QUIET mode.
Some time after humidity drop the fan reverts to the previous mode.
Wiring diagram 4
Automatic humidity and movement control (SMART IR), timer and momentary switch.
The contacts L and N are connected to live and zero of power mains and the contact LT
is connected to live through an external momentary switch, for example, door open sensor.
The fan is in SLEEP mode by default (does not run).
If 24 HOURS mode is activated the fan switches to permanent low speed mode to provide
minimum round-the-clock ventilation.
After receipt of a signal from the motion sensor (for SMART IR model only) the fan is turned
to QUIET mode. Some time after no movement is detected any more the fan reverts to the
previous mode.
After short-term activation of the momentary switch the fan is turned to QUIET mode and
operates in this mode for the time set by the turn-off timer. After that the timer reverts to the
previous mode.
After humidity increase the fan turns to MAXIMAL (by default) or QUIET mode.
Some time after humidity drop the fan reverts to the previous mode.